● The instruction can be executed when the transfer request relays of the HTTPc control relay
and the HTTPc logging/trace control relay are OFF (0: No request). As an execution
condition of the instruction, insert a program that checks the state of the transfer request
relay. The states of the transfer request relay and the logging transfer request relay can be
read with the ETSTAT instruction. Store the state that is read in a device such as an internal
relay. An operation error occurs if the instruction is executed when one of the transfer
request relays is ON.
● After this instruction is executed, the PLC operates as shown in the following table.
Conditions
Operation
The power supply for the PLC is switched from OFF to ON.
Setting using the
configuration
The PLC is changed to
PROG mode.
Changes to RUN mode without rewriting the
configuration.
Setting using instructions
Changes to RUN mode after rewriting the
configuration.
Setting using the
configuration
● If an incorrect IP address is specified, the system relay SR9 (carry flag CY) is set and the
instruction is terminated without being executed.
● This instruction can be executed when the Ethernet initialization active flag (X61) is OFF. As
an execution condition of the instruction, insert a program that checks the status of the flag
(X61). If this instruction is executed when the flag (X61) is ON, the system relay SR9 (carry
flag CY) is set and the instruction is terminated without being executed.
● When the instruction is completed successfully, the system relay SR9 (carry flag CY) and the
system data register SD29 (Ethernet communication error code) are cleared.
■
Precautions for programming
● Insert the UNITSEL instruction immediately before this instruction and specify the unit (built-
in ET-LAN in the CPU unit) and the connection number.
● For [S1] to [S3], specify the starting address of the device area that stores the string data
that indicates the set parameters, or a character constant. When specifying a device area for
an operand, set string data using the SSET instruction in advance. However, the ESSET
instruction cannot be used because the format is different.
● The number of characters should not exceed 256.
● Both upper and lower case characters can be used. "Abcd", "ABCD" and "abcd" are all
synonymous.
● This instruction is not available in interrupt programs.
■
Operand [S1] setting
● Specify the starting address storing the server specification parameter or a character
constant.
● A part of parameters can be omitted. The settings are not changed when parameters are
omitted partially.
● When omitting the part before a specified keyword, omit only "keyword" without omitting ",".
● When omitting the part after a specified keyword, omit both "," and "keyword".
● Specify the HTTP server setting from SV0 in order. When the right order is skipped, an error
occurs. It is possible to specify by overwriting when the setting has been already registered.
● Only one server can be specified at the same time.
● Specify an HTTP server number, the IP address or host name of an HTTP server, a port
number, an open method, and the SSL3/TLS1 authentication setting within 256 one-byte
characters in total.
17.16 HTTPcSV (HTTP Client Connected Server Setting)
17-82
WUME-FP7CPUPGR-12
Содержание FP7 Series
Страница 2: ... MEMO 2 WUME FP7CPUPGR 12 ...
Страница 18: ... MEMO xviii WUME FP7CPUPGR 12 ...
Страница 52: ... MEMO 1 34 WUME FP7CPUPGR 12 ...
Страница 61: ...Example 2 Use PSHS RDS or POPS instruction 2 1 Structure of Instructions WUME FP7CPUPGR 12 2 9 ...
Страница 104: ... MEMO 2 52 WUME FP7CPUPGR 12 ...
Страница 123: ...3 9 ANS AND stack WUME FP7CPUPGR 12 3 19 ...
Страница 125: ...3 10 ORS OR Stack WUME FP7CPUPGR 12 3 21 ...
Страница 129: ...3 11 PSHS Push stack RDS Read stack POPS Pop stack WUME FP7CPUPGR 12 3 25 ...
Страница 139: ...4 CNDE instruction 5 Step ladder instructions 6 Subroutine instructions 3 16 ALT Alternate out WUME FP7CPUPGR 12 3 35 ...
Страница 146: ... Application example of timer instructions serial connection of timers 3 17 TM Timer 3 42 WUME FP7CPUPGR 12 ...
Страница 147: ... Application example of timer instructions parallel connection of timers 3 17 TM Timer WUME FP7CPUPGR 12 3 43 ...
Страница 190: ...3 26 JP LBL Jump Label 3 86 WUME FP7CPUPGR 12 ...
Страница 239: ...Name Description SR8 ER 3 46 ST ST ST ST ST ST Data Comparison Start WUME FP7CPUPGR 12 3 135 ...
Страница 246: ... MEMO 3 142 WUME FP7CPUPGR 12 ...
Страница 251: ...Name Description SRA Depending on the comparison result SRB SRC 4 1 CMP Data Compare WUME FP7CPUPGR 12 4 5 ...
Страница 258: ... MEMO 4 12 WUME FP7CPUPGR 12 ...
Страница 277: ...F E D C B A 9 8 7 6 5 4 3 2 1 0 Digit 3 Digit 2 Digit 1 Digit 0 bit 5 8 DGT Digit Data Transfer WUME FP7CPUPGR 12 5 19 ...
Страница 304: ... MEMO 5 46 WUME FP7CPUPGR 12 ...
Страница 321: ...Name Description ER 6 7 DIVFP2 Division FP2 Compatible WUME FP7CPUPGR 12 6 17 ...
Страница 348: ... MEMO 6 44 WUME FP7CPUPGR 12 ...
Страница 388: ... MEMO 7 40 WUME FP7CPUPGR 12 ...
Страница 438: ... MEMO 8 50 WUME FP7CPUPGR 12 ...
Страница 450: ... MEMO 9 12 WUME FP7CPUPGR 12 ...
Страница 520: ... MEMO 10 70 WUME FP7CPUPGR 12 ...
Страница 602: ... MEMO 11 82 WUME FP7CPUPGR 12 ...
Страница 622: ... MEMO 12 20 WUME FP7CPUPGR 12 ...
Страница 650: ... MEMO 13 28 WUME FP7CPUPGR 12 ...
Страница 1160: ... MEMO 18 66 WUME FP7CPUPGR 12 ...
Страница 1188: ... MEMO 19 28 WUME FP7CPUPGR 12 ...
Страница 1211: ...20 4 ASCII Code Table JIS8 Code Table Reference Table ASCII Codes 20 4 ASCII Code Table JIS8 Code Table WUME FP7CPUPGR 12 20 23 ...
Страница 1220: ... MEMO WUME FP7CPUPGR 12 ...
Страница 1221: ... MEMO WUME FP7CPUPGR 12 ...