Main board 5012 is backward compatible with 5010 and can be connected to an
existing TLON network with software ≥ V2.10.4.
•
MMI board 5015 is backward compatible with 5011.
•
Higher stabilised supply voltage results in approximately 55% longer loop length.
•
Improved monitoring due to accurate measuring the loop resistance which
increases the reliability.
•
Redundant communication (only software V3.x.x) and power supply for display
units. Other Connection and wiring are identical.
•
Large number of fuses have been replaced with PTC resettable electronic fuses
e.g. supervised voltage output. Remaining fuses uses M205 ceramic tube fuses.
•
Easy and quick repair with individual loop boards 5017 with connectors
•
Isolated USB interface to avoid generating earth fault if the PC is connected without
external isolator.
•
Replace jumper links to activate service signal in TLON applications by
pushbuttons.
•
5012 and 5015 are Compliant with the latest Australian standards AS7240.2:2018
and AS7240.4:2018.
•
Must use software ≥ V2.10.4.
5012 PCB layout and terminations are shown in Figure 9 below.
Figure 9 Main Board 5012
1. J9, connection for 458X expansion boards
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Страница 2: ...This page has deliberately been left blank...
Страница 174: ...174 Operation Manual FT1020G3 Rev 2 10 4 Figure 22 19 Rack 22U FT1020G3 General Arrangement with 6U battery box...
Страница 175: ...175 Operation Manual FT1020G3 Rev 2 10 4 Figure 23 19 Rack 13U FT1020G3 General Arrangement with 6U battery box...
Страница 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Страница 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...