background image

Panasonic Eco Solutions Nordic AB 

 

MEW01603  Rev:  - 

EBL512 G3 version 2.0.x, Daily user's manual 

 

15 

Present system status  (H4) 

If the c.i.e. has a printer it is possible to get a print-out from some of 
the sub menus U1-U8. 

If  it  is  possible  to  get  a  print-out,  the  Soft  key  "

Print

"  is  shown  and 

shall be used to start the print-out. 

During printing the same Soft key might change to "

Abort printing

". 

NOTE!

    After  pressing  the  Soft  key  "

Abort  printing

"  it  will  change 

back to "

Print

" but the printing might continue for a few seconds. 

If the list in the selected menu is empty, "

- - -  List is empty  - - -

" will 

be shown. 

 

  Press the Soft key "

Menu

". 

  With the keypad select 0, 1, 2 - - 8 or 9 for a 

User name

  Type the 

Password

 for that user name.  (Six digits.    * * * * * *) 

H1  Perform monthly test 

  

Press ( 

 )  three times to highlight menu H4.  

H4  Present system status 

  Press 

(

 )

.  A sub menu list (U1 – U8) will be displayed. 

B1  

Disable zone

 

U1  Disablement 

U2  Disablement by time channel 

U3  Open doors 

U4  Sensor values 

U5  Sensors activating SERVICE signal 

U6  Technical warning

 

U7  Event log 

U8  Information 

 

  To open the sub menu respectively, see the following chapters. 

 

Menu

Print

Содержание EBL512 G3 5000

Страница 1: ...User manual MEW01603 Revision Fire alarm system EBL512 G3 EBL512 G3 version 2 0 x Daily user s manual Author Jan Pettersson Date of issue 2013 01 10 Date of rev...

Страница 2: ...This page has deliberately been left blank...

Страница 3: ...____ 14 7 Present system status H4 __________________ 15 7 1 Disablement U1 _________________________________ 16 7 2 Disablement by time channel U2 ____________________ 16 7 3 Open doors U3 __________...

Страница 4: ...ailed and shorter than the Operating Instruction MEW01552 NOTE In the left margin are pictures of the buttons soft keys used in the menu respectively Each picture is only shown one time in each menu n...

Страница 5: ...3 Rev EBL512 G3 version 2 0 x Daily user s manual 3 2 Front Front upper light grey part Fire Brigade Panel FBP Front lower dark grey part LEDs and keypad Soft keys Information will be visible above th...

Страница 6: ...ccess levels access types Information only will give access to the menus H4 H6 H9 and H10 Building officer will give access to the menus H1 H2 H3 H4 H6 H7 H9 and H10 Described in this document Service...

Страница 7: ...rform monthly test H2 Disable or re enable H3 Set calendar and clock H4 Present system status H5 Service H6 FAULT Acknowledge H7 Perform ZONE TEST H8 Maintenance H9 Interlocking outputs and inputs H10...

Страница 8: ...has a printer it has made a print out ABC Z abc z Press Up to four zones can be set in test mode Use the keypad to type the zone numbers Press Perform the test To end the test press If the routing equ...

Страница 9: ...isablements also the LED Alarm devices and or Fire brigade tx Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform mon...

Страница 10: ...blement to toggle between Zone 000 Zone 000 address 00 Use the keypad to type the Zone or Zone Address Press If Automatically re enablement shall be used press and to highlight Yes accept the suggeste...

Страница 11: ...l unit 00 S0 Control unit 00 R0 Control unit 00 expansion board output 0 Use the keypad to type the required data Press A successful disablement is indicated by a beep and a It will also be shown in t...

Страница 12: ...Ventilation outputs Extinguishing outputs Interlocking outputs Press and type the control unit number if not All outputs shall be disabled Press A successful disablement is indicated by a beep and a I...

Страница 13: ...le see below By default is All alarm devices selected Press A successful disablement is indicated by a beep and a It will also be shown in the Re enable list A not successful disablement is indicated...

Страница 14: ...highlight Fault After Fire or Fault is selected press A successful disablement is indicated by a beep and a It will also be shown in the Disabled routing equipment list A not successful disablement is...

Страница 15: ...from page 7 B1 Zone or Zone Address Press five times B6 Alert annunciation function Press Disable NOTE To Re enable see below By default is Alert annunciation selected Press A successful disablement...

Страница 16: ...ave the menu Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press two times to highlight menu H3 H3...

Страница 17: ...ge back to Print but the printing might continue for a few seconds If the list in the selected menu is empty List is empty will be shown Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for...

Страница 18: ...or Fire brigade tx Press The list is dynamic i e you can scroll in the list with or If a printer is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC...

Страница 19: ...4 Sensor values U4 Cont from page 15 U1 Disablement Press three times U4 Sensor values Press Use the keypad to enter the technical number and or press This is a list i e you can scroll in the list wit...

Страница 20: ...inter is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC To leave the menu system press the Soft key Escape menu NOTE Sensors activating SERVICE si...

Страница 21: ...rinter is available the Soft key Print is shown and can be used to start a print out Print items from latest hour day week month All Scroll in the list with or and select Press To leave a menu press E...

Страница 22: ...Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press five times to highlight menu H6 H6 FAULT Acknowledge Press This...

Страница 23: ...cept the fire door outputs The test mode alarm will be automatically reset after approx 10 seconds Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for tha...

Страница 24: ...of test mode for a zone is indicated by a beep and it will also disappear from the End test mode list To leave a menu press ESC To leave the menu system press the Soft key Escape menu NOTE After one h...

Страница 25: ...a User name Type the Password for that user name Six digits H1 Perform monthly test Press eight times to highlight menu H9 H9 Interlocking outputs and inputs Press A sub menu list C1 C3 will be displ...

Страница 26: ...ed deactivated via menu C2 If an interlocking output is activated via its control expression and with latching output selected in EBLWin the output has to be deactivated via this menu Cont from page 2...

Страница 27: ...page 23 C1 Activated interlocking outputs inputs Press two times C3 Disable re enable interlocking output Press Disable By default is Interlocking output area 000 point 00 shown Use the keypad to type...

Страница 28: ...ith the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press nine times to highlight menu 10 H10 Change password Press The User name...

Страница 29: ...Panasonic Eco Solutions Nordic AB MEW01603 Rev EBL512 G3 version 2 0 x Daily user s manual 27 12 Revision history...

Страница 30: ...This page has deliberately been left blank...

Страница 31: ...Panasonic Eco Solutions Nordic AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info pesn eu panasonic com http pesn panasonic se...

Отзывы: