6 USING THE SYSTEM
B
Touch a distribution group. A keyboard window like the one shown above appears. Use the
keyboard to enter a distribution group number and to select the product type from among PAC,
GHP and HOT.
Select “Simple” or “Load” in the distribution methods.
* Refer to “10. Calculating air conditioner distribution” for details.
The tenant set at “Load” distribution will have its “No” box display in light blue.
* The distribution group number range is from 1 to 8.
* This button is invalid when “No Distrib.” has been set. (Refer to
Main
Sub
1
1
5
5
)
* The distribution group column set at loaded distribution has no product type such as “PAC” and “GHP”
displayed.
* Make manual cut-off in advance to change the distribution method.
C
Press the Type button to select “PAC” or “GHP” for the following unit that is unable to
automatically recognize product type.
- Interface adaptor
This is only for “Simple distribution” setting.
D
Specify which distribution method, “Simple” or “Load,” to apply to the selected distribution
group.
E
Touch Set to con
fi
rm the setting, or Cancel to cancel it.
•
PAC, GHP, and HOT cannot be mixed in the same group. Set up a separate distribution group for each
type.
•
HOT multi units cannot be recognized automatically (they are recognized as PAC). Manually set the
product type to HOT.
•
HOT Tenants cannot be set at the “Load” distribution.
•
“Load” distribution tenants cannot be set at “HOT”.
•
Air conditioners unadaptable to loaded distribution cannot be set at “Load” Distribution.
•
Interface adaptors are also unadaptable to loaded distribution.
Main
Sub
3
3
5
5