5 Air Conditioner Performance Evaluation
5.1. Cooling
Intake & Discharge Air
Temperature Difference
Current Drain
Determination
Remedy
•
•
•
•
8°C and over (14.4°F)
•
•
•
•
As specified.
•
•
•
•
Nothing wrong.
•
•
•
•
None.
•
•
•
•
8°C and over (14.4°F)
•
•
•
•
Higher than specified.
•
•
•
•
Nothing wrong, outdoor
temperature is too high, heat
radiation is not efficient.
•
•
•
•
Improve heat radiation.
•
•
•
•
Under 8°C (14.4°F)
•
•
•
•
Higher than specified.
•
•
•
•
Something is preventing heat
radiation.
•
•
•
•
Excessive amount of refrigerant.
•
•
•
•
Improve heat radiation.
•
•
•
•
Under 8°C (14.4°F)
•
•
•
•
Lower than specified.
•
•
•
•
Leakage of refrigerant or
refrigerant system is blocked.
•
•
•
•
Locate and repair leak.
•
•
•
•
Flush refrigeration cycle.
•
•
•
•
Under 8°C (14.4°F)
•
•
•
•
Higher than specified by
50%.
•
•
•
•
Compressor defect or
compressor capacitor defect.
•
•
•
•
Replace the compressor or
compressor capacitor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
5.2. Heating
Intake & Discharge Air
Temperature Difference
Current Drain
Determination
Remedy
•
•
•
•
14°C and over (25.2°F)
•
•
•
•
As specified.
•
•
•
•
Nothing wrong.
•
•
•
•
None.
•
•
•
•
14°C and over (25.2°F)
•
•
•
•
Higher than specified.
•
•
•
•
Nothing wrong, outdoor
temperature is high.
•
•
•
•
Something is preventing heat
radiation at indoor heat
exchanger.
•
•
•
•
None.
•
•
•
•
Clean air filter.
•
•
•
•
Under 14°C (25.2°F)
•
•
•
•
Lower than specified.
•
•
•
•
Nothing wrong, outdoor
temperature is low.
•
•
•
•
Something is preventing heat
radiation at outdoor heat
exchanger.
•
•
•
•
Leakage of refrigerant.
•
•
•
•
Refrigerant system is blocked.
•
•
•
•
None.
•
•
•
•
Improve heat radiation at outdoor
heat exchanger.
•
•
•
•
Locate and repair leak.
•
•
•
•
Flush refrigeration cycle.
•
•
•
•
Under 14°C (25.2°F)
•
•
•
•
Higher than specified by
50%.
•
•
•
•
Compressor defect.
•
•
•
•
Compressor capacitor defect
•
•
•
•
Replace the compressor.
•
•
•
•
Replace the compressor
capacitor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
6 Troubleshooting Guide
Warning: Disconnect unit from electrical power supply before making any electrical checks.
Trouble
Check
Result
Cause
Remedy
Fan Motor and
Compressor won’t run.
•
•
•
•
Supply Voltage
•
•
•
•
Fuse Box or Circuit
Breaker.
•
•
•
•
Power cord or
Wiring Harness.
•
•
•
•
Temperature
Setting.
•
•
•
•
Less than 10% by
Rated.
•
•
•
•
Open Contacts.
•
•
•
•
Pulled loose or
Shorted.
•
•
•
•
Higher than room
temperature
•
•
•
•
Temporary or Permanent?
•
•
•
•
Customer Restarted unit
immediately without waiting
3 minutes.
•
•
•
•
Consult ELECTRICIAN, if
permanent.
•
•
•
•
WAIT FOR 3 MINUTES.
•
•
•
•
Repair Open Circuit.
•
•
•
•
Repair or Replace it.
•
•
•
•
Set it LOWER.
Fan Motor won’t run
(Compressor run).
•
•
•
•
Objects around
Fan.
•
•
•
•
RESISTANCE
between Wires.
•
•
•
•
Capacitor Fan
Motor.
•
•
•
•
Main Control
Switch.
•
•
•
•
Locked Fan.
•
•
•
•
Shorted / Open
circuit.
•
•
•
•
OHM Meter doesn’t
Deflect.
•
•
•
•
No contacts at
Position Shown.
•
•
•
•
Fan Hitting Cowling
•
•
•
•
Foreign Materials.
•
•
•
•
Frozen Bearings.
•
•
•
•
Shorted or Burned out.
•
•
•
•
Capacitor Defect.
•
•
•
•
Main Control Switch defect.
•
•
•
•
Adjust Fan position setting
screw.
•
•
•
•
Remove Foreign Materials.
•
•
•
•
Replace Fan Motor.
•
•
•
•
Replace Fan Motor.
•
•
•
•
Replace Capacitor Fan.
•
•
•
•
Replace Main Control
Switch.
6
CW-A90VE / CW-A120VE