16
3. Installation Process
3-1.
Embedding the Tubing and Wiring
Do not connect tubes to locations that are embedded.
Be sure to bind refrigerant tubing and inter-unit cables
together with vinyl tape.
The power cable must be obtained on-site.
(#12: Less than 85 ft.)
# ... AWG (American Wire Gauge)
Be sure to apply the provided labels to both ends of
the inter-unit cables to prevent miswiring.
Securely seal the end of embedded tubing with vinyl
tape in order to prevent dirt or moisture entry.
In order to prevent insulation breakdown and ground
faults, do not allow the wire ends to come in contact
with rainwater, or be subject to dew condensation.
Deburring
Before
After
Fig. 8
3-2. Use of the Flaring Method
Many of the conventional split system air conditioners
employ the flaring method to connect refrigerant tubes
which run between indoor and outdoor units. In this
method, the copper tubes are flared at each end and
connected with flare nuts.
3-3. Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 12" to
20" (30 to 50 cm) longer than the tubing length you
estimate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and
should be done carefully to make a good flare.
(Fig. 8)
Содержание CU-3KS19NBU
Страница 62: ...6 ELECTRICAL DATA 6 1 Electric Wiring Diagrams Outdoor Unit CU 3KS19NBU 8FA2 5251 11800 1 62 ...
Страница 63: ...Outdoor Unit CU 4KS24NBU 8FA2 5251 11600 1 63 ...
Страница 64: ...Outdoor Unit CU 4KS31NBU 8FA2 5251 11400 1 64 ...
Страница 86: ...INSTALLATION INSTRUCTIONS CU 3KS19NBU CU 4KS24NBU CU 4KS31NBU 852 6 4190 581 00 1 APPENDIX A A 1 ...
Страница 114: ...DC1111 0 ...