Panasonic CU-2Z35TBE Скачать руководство пользователя страница 6

2. Precaution for Using R32 Refrigerant 

  Pay careful attention to the following precaution points and the installation work procedures: 

 

  WARNING

 

1. 

The appliance shall be stored, installed and operated in a well ventilated room with indoor floor area larger than A

min

 (m

2

) [refer 

Table A] and without any continuously operating ignition source. 
Keep away from open flames, any operating gas appliances or any operating electric heater. Else, it may explode and cause 
injury or death. 

 

2. 

When connecting flare at indoor side, make sure that the flare connection is used only once, if torqued up and released, the 
flare must be remade.  
Once the flare connection was torqued up correctly and leak test was made, thoroughly clean and dry the surface to remove oil, 
dirt and grease by following instructions of silicone sealant. Apply neutral cure (Alkoxy type) & ammonia-free silicone sealant 
that is noncorrosive to copper & brass to the external of the flared connection to prevent the ingress of moisture on both the gas 
& liquid sides. 
(Moisture may cause freezing and premature failure of the connection)

 

3. 

The mixing of different refrigerants within a system is prohibited. Models that use refrigerant R32 and R410A have a different 
charging port thread diameter to prevent erroneous charging with refrigerant R22 and for safety. 
Therefore, check beforehand. [The charging port thread diameter for R32 and R410A is 12.7 mm (1/2 inch).] 

 

4. 

Ensure that foreign matter (oil, water, etc.) does not enter the piping. 
Also, when storing the piping, securely seal the opening by pinching, taping, etc. (Handling of R32 is similar to R410A.) 

 

5. 

Operation, maintenance, repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of 
flammable refrigerants and as recommended by the manufacturer.  
Any personnel conducting an operation, servicing or maintenance on a system or associated parts of the equipment should be 
trained and certified. 

 

6. 

Any part of refrigerating circuit (evaporators, air coolers, AHU, condensers or liquid receivers) or piping should not be located in 
the proximity of heat sources, open flames, operating gas appliance or an operating electric heater. 

 

7. 

The user/owner or their authorized representative shall regularly check the alarms, mechanical ventilation and detectors, at 
least once a year, where as required by national regulations, to ensure their correct functioning. 

 

8. 

A logbook shall be maintained. The results of these checks shall be recorded in the logbook. 

 

9. 

In case of ventilations in occupied spaces shall be checked to confirm no obstruction. 

 

10. 

Before a new refrigerating system is put into service, the person responsible for placing the system in operation should ensure 
that trained and certified operating personnel are instructed on the basis of the instruction manual about the construction, 
supervision, operation and maintenance of the refrigerating system, as well as the safety measures to be observed, and the 
properties and handling of the refrigerant used. 

 

11. 

The general requirement of trained and certified personnel are indicated as below: 
a)  Knowledge of legislation, regulations and standards relating to flammable refrigerants; and, 
b)  Detailed knowledge of and skills in handling flammable refrigerants, personal protective equipment, refrigerant leakage 

prevention, handling of cylinders, charging, leak detection, recovery and disposal; and, 

c)  Able to understand and to apply in practice the requirements in the national legislation, regulations and Standards; and, 
d)  Continuously undergo regular and further training to maintain this expertise. 

 

12. 

Air-conditioner piping in the occupied space shall be installed in such a way to protect against accidental damage in operation 
and service. 

 

13.  Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping. 

 

14. 

Ensure protection devices, refrigerating piping and fittings are well protected against adverse environmental effects (such as the 
danger of water collecting and freezing in relief pipes or the accumulation of dirt and debris). 

 

15. 

Expansion and contraction of long runs piping in refrigerating systems shall be designed and installed securely (mounted and 
guarded) to minimize the likelihood hydraulic shock damaging the system. 

 

16.  Protect the refrigerating system from accidental rupture due to moving furniture or reconstruction activities. 

 

17. 

To ensure no leaking, field-made refrigerant joints indoors shall be tightness tested. The test method shall have a sensitivity of  
5 grams per year of refrigerant or better under a pressure of at least 0,25 times the maximum allowable pressure (>1.04MPa, 
max 4.15MPa). No leak shall be detected. 

 

 
 
 
 
 
 
 
 
 
 
 
 

Содержание CU-2Z35TBE

Страница 1: ...serviced or repaired only by experienced professional technicians Any attempt to service or repair the products dealt with in this service information by anyone else could result in serious injury or death There are special components used in this equipment which are important for safety These parts are marked by in the Schematic Diagrams Circuit Board Diagrams Exploded Views and Replacement Parts...

Страница 2: ...efrigerant 6 3 Specifications 11 4 Exploded View and Replacement Parts List 13 4 1 CU 2Z35TBE CU 2Z41TBE CU 2Z50TBE 13 4 2 CU 3Z52TBE CU 3Z68TBE CU 4Z68TBE 16 4 3 CU 4Z80TBE CU 5Z90TBE 20 Specifications designs and contents in this Service Manual are subject to change without notice ...

Страница 3: ... into the unit high speed rotating fan may cause injury 6 Do not sit or step on the unit you may fall down accidentally 7 Keep plastic bag packaging material away from small children it may cling to nose and mouth and prevent breathing 8 When installing or relocating air conditioner do not let any substance other than the specified refrigerant eg air etc mix into refrigeration cycle piping Mixing ...

Страница 4: ...on will cause suck in of air abnormal high pressure in refrigeration cycle and result in explosion injury etc 21 During pump down operation stop the compressor before removing the refrigeration piping Removal of refrigeration piping while compressor is operating and valves are opened will cause suck in of air abnormal high pressure in refrigeration cycle and result in explosion injury etc 22 Tight...

Страница 5: ...e solder has a higher melting point than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to splash when heated too high about 1100 F 600 C 11 Power supply connection to the room air conditioner Use power supply cord 3...

Страница 6: ...arly check the alarms mechanical ventilation and detectors at least once a year where as required by national regulations to ensure their correct functioning 8 A logbook shall be maintained The results of these checks shall be recorded in the logbook 9 In case of ventilations in occupied spaces shall be checked to confirm no obstruction 10 Before a new refrigerating system is put into service the ...

Страница 7: ...m 2 3 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapour being present while the work is being performed 2 4 General work area All maintenance staff and others working in the local area shall be instructed and supervised on the nature of work being carried out Avoid working in confined spaces Always ensure away from source a...

Страница 8: ...nals not made to original specification damage to seals incorrect fitting of glands etc Ensure that apparatus is mounted securely Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be in accordance with the manufacturer s specifications NOTE The use of silicon sealant may inh...

Страница 9: ...eate a hazardous condition when charging and discharging the refrigerant To avoid fire or explosion dissipate static electricity during transfer by grounding and bonding containers and equipment before charging discharging 9 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good pra...

Страница 10: ...frigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigera...

Страница 11: ...30 Additional gas amount over chargeless length g m 15 15 15 20 20 Note Available Remarks for CU 2Z35TBE CU 2Z41TBE CU 2Z50TBE 1 At least two indoor units must be connected 2 The total nominal cooling capacity of indoor unit that will be connected to outdoor unit must be within connectable capacity range of indoor unit as shown in the table above Example The indoor units combination below is possi...

Страница 12: ...18 3kW Pipe length 1 room maximum pipe length m 25 25 25 Allowable elevation m 15 15 15 Total allowable pipe length m 60 70 80 Total pipe length for maximum chargeless length m 30 45 45 Additional gas amount over chargeless length g m 20 20 20 Note Available Remarks for CU 4Z68TBE CU 4Z80TBE CU 5Z90TBE 1 At least two indoor units must be connected 2 The total nominal cooling capacity of indoor uni...

Страница 13: ...9 77 72 50 80 64 65 66 67 68 69 70 40 36 47 3 56 75 4 5 32 34 52 31 13 2 55 19 26 21 78 20 27 14 29 35 48 8 46 73 73 41 6 8 7 18 10 11 12 76 9 54 1 24 25 74 43 44 22 18 57 49 37 38 51 45 53 33 82 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 14: ...B111080 24 V COIL COMPLETE CN EV1 WHITE 1 CWA43C2579 Ο 25 V COIL COMPLETE CN EV2 YELLOW 1 CWA43C2580 Ο 26 V COIL COMPLETE 4 WAY VALVE 1 CWA43C2585 Ο 27 SOUND PROOF BOARD 1 CWH151364 29 SENSOR COMPLETE AIR TEMP SENSOR CN TH1 1 CWA50C3078 Ο 31 SENSOR COMPLETE GAS PIPE TEMP CN TH4 1 CWA50C3070 Ο 32 SENSOR COMPLETE DEFROST SENSOR CN TH2 1 CWA50C3069 Ο 33 HOLDER SENSOR 6 CWH32143 34 SENSOR COMPLETE TAN...

Страница 15: ...INSTRUCTION 1 ACXF60 06580 66 INSTALLATION INSTRUCTION 1 ACXF60 06590 67 INSTALLATION INSTRUCTION 1 ACXF60 06600 68 INSTALLATION INSTRUCTION 1 ACXF60 06610 69 INSTALLATION INSTRUCTION 1 ACXF60 06620 70 INSTALLATION INSTRUCTION 1 ACXF60 06630 71 INSTALLATION INSTRUCTION 1 ACXF60 06640 72 INSTALLATION INSTRUCTION 1 ACXF60 06650 73 DISCHARGE MUFFLER 2 ACXB12 00610 74 DISCHARGE MUFFLER 1 ACXB12 01180 ...

Страница 16: ... 50 89 5 4 8 9 6 7 3 4 2 29 28 31 44 60 59 24 25 24 57 38 32 40 41 39 15 36 37 35 34 23 26 79 22 21 33 82 56 76 19 20 17 18 27 16 77 53 30 80 81 74 13 12 11 1 47 10 14 75 83 54 91 78 79 CU 4Z68TBE only 84 85 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 17: ...2 Ο 19 HOLDER COUPLING 1 CWH351258 20 STRAINER 1 CWB11061 21 STRAINER 3 4 CWB111024 22 EXPANSION VALVE 3 4 CWB051029 Ο 23 4 WAYS VALVE WITH SCREW 1 CWB001026JX Ο 24 DISCHARGE MUFFLER 2 ACXB12 00650 25 HEATING PRESSURE SWITCH 1 CWA101013 26 FLARE NUT 1 4 3 4 CWT251030 27 FLARE NUT 3 8 3 4 CWT251031 28 SOUND PROOF MATERIAL 1 CWG302246 29 SOUND PROOR MATERIAL 1 CWG302520 30 SOUND PROOR MATERIAL 1 CWG...

Страница 18: ...0300J 61 INSTALLATION INSTRUCTION 1 ACXF60 06660 62 INSTALLATION INSTRUCTION 1 ACXF60 06670 63 INSTALLATION INSTRUCTION 1 ACXF60 06680 64 INSTALLATION INSTRUCTION 1 ACXF60 06690 65 INSTALLATION INSTRUCTION 1 ACXF60 06700 66 INSTALLATION INSTRUCTION 1 ACXF60 06710 67 INSTALLATION INSTRUCTION 1 ACXF60 06720 68 INSTALLATION INSTRUCTION 1 ACXF60 06730 69 INSTALLATION INSTRUCTION 1 ACXF60 06740 70 INST...

Страница 19: ...87 BASE BOARD COMPLETE 1 CWG62C1081 88 SHOCK ABSORBER 1 CWG712879 89 SHOCK ABSORBER 1 CWG712880 90 C C CASE 1 ACXG50 52321 91 MODEL LABEL 2 ACXF82 22640 ACXF82 22660 ACXF82 22670 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 20: ...8 74 1 16 10 13 12 60 14 59 58 21 17 18 22 78 6 2 55 47 3 7 4 9 54 58 61 I I 66 I I 67 I I 68 I I 69 I I 80 I I 81 I I 62 I I 63 I I 64 I I 65 I I 56 57 82 83 86 85 84 92 90 88 89 91 90 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 21: ...22 EXPANSION VALVE 4 CWB051029 Ο 23 4 WAYS VALVE WITH SCREW 1 CWB001026JX Ο 24 DISCHARGE MUFFLER 2 ACXB12 00650 25 HEATING PRESSURE SWITCH 1 CWA101013 Ο 26 FLARE NUT 1 4 4 CWT251030 27 FLARE NUT 3 8 4 CWT251031 28 SOUND PROOF MATERIAL 1 CWG302804 31 SOUND PROOF MATERIAL 1 CWG302801 32 SENSOR COMPLETE DISCHARGE TEMP SENSOR CN DIS 1 CWA50C3091 Ο 33 V COIL CO 4 WAY VALVE CN HOT 1 CWA43C2586 Ο 34 V CO...

Страница 22: ...COVER 1 CWH7080300J 61 INSTALLATION INSTRUCTION 1 ACXF60 16610 62 INSTALLATION INSTRUCTION 1 ACXF60 16620 63 INSTALLATION INSTRUCTION 1 ACXF60 16630 64 INSTALLATION INSTRUCTION 1 ACXF60 16640 65 INSTALLATION INSTRUCTION 1 ACXF60 16650 66 INSTALLATION INSTRUCTION 1 ACXF60 16660 67 INSTALLATION INSTRUCTION 1 ACXF60 16670 68 INSTALLATION INSTRUCTION 1 ACXF60 16680 69 INSTALLATION INSTRUCTION 1 ACXF60...

Страница 23: ...TBE REMARK 90 SHOCK ABSORBER 2 CWG713581 91 SHOCK ABSORBER 1 CWG713582 92 C C CASE 1 ACXG50 52041 93 MODEL LABEL 2 ACXF82 44380 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 24: ... EXPANSION VALVE 5 CWB051029 Ο 23 4 WAYS VALVE WITH SCREW 1 CWB001026JX Ο 24 DISCHARGE MUFFLER 2 ACXB12 00650 25 HEATING PRESSURE SWITCH 1 CWA101013 Ο 26 FLARE NUT 1 4 5 CWT251030 27 FLARE NUT 3 8 5 CWT251031 28 SOUND PROOF MATERIAL 1 CWG302804 31 SOUND PROOF MATERIAL 1 CWG302801 32 SENSOR COMPLETE DISCHARGE TEMP SENSOR CN DIS 1 CWA50C3091 Ο 33 V COIL CO 4 WAY VALVE CN HOT 1 CWA43C2586 Ο 34 V COIL...

Страница 25: ...171039A 60 NUT TERMINAL COVER 1 CWH7080300J 61 INSTALLATION INSTRUCTION 1 ACXF60 16610 62 INSTALLATION INSTRUCTION 1 ACXF60 16620 63 INSTALLATION INSTRUCTION 1 ACXF60 16630 64 INSTALLATION INSTRUCTION 1 ACXF60 16640 65 INSTALLATION INSTRUCTION 1 ACXF60 16650 66 INSTALLATION INSTRUCTION 1 ACXF60 16660 67 INSTALLATION INSTRUCTION 1 ACXF60 16670 68 INSTALLATION INSTRUCTION 1 ACXF60 16680 69 INSTALLAT...

Страница 26: ...K ABSORBER 2 CWG713581 91 SHOCK ABSORBER 1 CWG713582 92 C C CASE 1 ACXG50 52041 93 MODEL LABEL 2 ACXF82 44390 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock PAPAMY Printed in Malaysia SY0321 0 ...

Отзывы: