![Panasonic CSS18NKUA Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/panasonic/css18nkua/css18nkua_service-manual_4708360051.webp)
51
14.4.11 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Malfunction Decision Conditions
•
Freeze prevention control takes place (when indoor pipe temperature is lower than 35.6°F)
Malfunction Caused
•
Clogged air filter of the indoor unit
•
Dust accumulation on the indoor unit heat exchanger
•
Air short circuit
•
Detection error due to faulty indoor pipe temperature sensor
•
Detection error due to faulty indoor unit PCB
Troubleshooting