Panasonic CSC18DKU - AIR CONDITIONER - SPLIT Скачать руководство пользователя страница 49

(Lack of refrigerant in the refrigeration cycle)

Procedure:

 1. 

Confirm that both the 3-way valves are set to the open
position.

 2. 

Connect the charge set to the 3-way valve’s service
port.

 • 

Leave the valve on the charge set closed.

 • 

Connect the charge hose with the push-pin to the
service port.

 • 

Confirm whether the pressure indicates more than 14.5
PSI (1 kg/cm

2

G).

 3. 

Connect the charge set’s centre hose to refrigerant
reclaiming equipment.

 4. 

Open the valve (Low side) on the charge set and loosen
the hose connected with the Refrigerant Reclaiming
Equipment to purge the air from the hose.

 5. 

Turn on refrigerant reclaiming equipment to collect the
refrigerant until the needle indicates 0 (no refrigerant is
remaining.)

11.4. Balance refrigerant of the 3-way valves

49

CS-C18DKU CU-C18DKU / CS-C24DKU CU-C24DKU

Содержание CSC18DKU - AIR CONDITIONER - SPLIT

Страница 1: ...ditioning M Sdn Bhd 11969 T All rights reserved Unauthorized copying and distribution is a violation of law CS C18DKU CU C18DKU CS C24DKU CU C24DKU 5 Refrigeration Cycle Diagram 13 6 Block Diagram 14 7 Wiring Diagram 15 8 Operation Details 17 8 1 Cooling Operation 17 8 2 Soft Dry Operation 18 8 3 Automatic Operation 19 8 4 Operation Control 20 Air Conditioner CONTENTS Page Page Order No MAC0502036...

Страница 2: ...s leakage detection Prevent Compressor reverse cycle Inner protector to protect Compressor Noise prevention during soft dry operation Blue coated Condenser for high resistance to corrosion Anti dew formation control Cooling Soft Dry Operation Improvement Quiet mode to provide quiet operation Powerful mode to reach the desired room temperature quickly 24 hour timer setting Serviceability Improvemen...

Страница 3: ...2 Functions 3 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 4: ...4 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 5: ...5 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 6: ...n Hose Inner diameter inch mm 6 10 32 16 Length inch mm 25 19 32 650 Power Cord Length m Number of core wire Dimensions Height inch mm 10 13 16 275 26 17 32 685 Width inch mm 39 9 32 998 31 1 2 800 Depth inch mm 9 1 16 230 11 13 16 300 Net Weight lb kg 24 11 0 106 48 0 Compressor Description Rotary 1 cylinder rolling piston type Motor Type Induction 2 poles Rated Output kW 1 2 Air Circulation Desc...

Страница 7: ...evice Overload Protector Capillary Tube Length inch mm 25 19 32 650 Flow Rate l min 20 9 Inner Diameter inch mm 2 32 1 9 Air Filter Material Style P P Honeycomb Capacity Control Capillary Tube Compressor Capacitor µF VAC 40 µF 400VAC Fan Motor Capacitor µF VAC 3 0 µF 450VAC Note Specifications are subjected to change without prior notice for further improvement 7 CS C18DKU CU C18DKU CS C24DKU CU C...

Страница 8: ...32 650 Power Cord Length m Number of core wire Dimensions Height inch mm 10 13 16 275 29 17 32 750 Width inch mm 39 9 32 998 34 7 16 875 Depth inch mm 9 1 16 230 13 19 32 345 Net Weight lb kg 26 12 0 131 59 5 Compressor Description Rotary 1 cylinder rolling piston type Motor Type Induction 2 poles Rated Output kW 1 8 Air Circulation Description Cross flow Fan Propeller Fan Material ASHT 18 PP Moto...

Страница 9: ...0 0 Flow Rate l min 21 0 Inner Diameter inch mm 3 32 2 0 Air Filter Material Style P P Honeycomb Capacity Control Capillary Tube Compressor Capacitor µF VAC 60 µF 400 440VAC Fan Motor Capacitor µF VAC 3 5 µF 440VAC Note Specifications are subjected to change without prior notice for further improvement 9 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 10: ...4 Dimensions 4 1 Indoor Unit Remote Control 4 1 1 CS C18DKU CS C24DKU 10 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 11: ...4 2 Outdoor Unit 4 2 1 CU C18DKU 11 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 12: ...4 2 2 CU C24DKU 12 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 13: ...5 Refrigeration Cycle Diagram 13 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 14: ...6 Block Diagram 14 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 15: ...7 Wiring Diagram CS C18DKU CU C18DKU CS C24DKU CU C24DKU 15 ...

Страница 16: ...CS C18DKU CU C18DKU CS C24DKU CU C24DKU 16 ...

Страница 17: ...hes the setting temperature set on the remote control The remote control setting temperature which takes the reading of intake air temperature sensor can be adjusted from 60 F to 86 F During cooling operation the compressor will stop running and restart as shown in below figure 8 1 1 Cooling Operation Time Diagram 17 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 18: ...hen operation begins Soft Dry will be switched ON for a maximum 10 minutes then Soft Dry operation will be turned OFF for a minimum 6 minutes After that the Soft Dry operation will be ON and OFF based on the setting temperature as shown in below figure However after 3 minutes of compressor off during Soft Dry OFF within 6 minutes Soft Dry restart control the indoor unit will start to operate at no...

Страница 19: ...mode until it is switched off using remote control with the setting temperature as shown in below table The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as shown in below table by pressing on the temperature up or temperature down button at remote control The operation mode judging temperature and standard setting temperatur...

Страница 20: ...non is to reduce the built up humidity inside a room 8 4 3 60 Seconds Forced Operation Once the air conditioner is turned on the compressor will not stop within 60 seconds in a normal operation although the intake air temperature has reached the thermo off temperature However force stop by pressing the OFF ON operation button at the remote control is permitted The reason for the compressor to forc...

Страница 21: ...e reason of the difference is to reduce the starting current flow 8 4 7 Anti Dew Formation Control Purpose is to prevent dew formation on indoor unit air discharge area When room temperature is constant 1 8 F the following conditions occur for 30 minutes continuously anti dew formation will activate Remote Control setting temperature is less than 77 F Compressor is on Cooling operation mode Indoor...

Страница 22: ...from 10 14 18 22 27 to 10 13 16 19 22 under Cooling and Soft Dry operation mode 3 Narrowing Horizontal Airflow Direction During Anti dew condensation prevention Airflow Direction Auto control angle change from 0 44 to 14 30 under Cooling and Soft Dry operation mode During Anti dew condensation prevention Airflow Direction Manual control angle change from 0 11 22 33 44 to 14 18 22 26 30 under Cooli...

Страница 23: ...ration indoor fan will increase fan speed gradually for deodorizing purpose 3 For the first time the compressor operate indoor fan will be switched to Hi fan speed from Lo after 70 seconds from the start of compressor This cause the room temperture to achieve the setting temperature quickly 4 During compressor stop indoor fan will operate at Lo for the beginning 20 seconds to prevent higher volume...

Страница 24: ...se 3 When compressor at turn off condition for 6 minutes indoor fan will start fan speed at Lo to circulate the air in the room This is to obtain the actual reading of intake air temperature 8 5 3 Manual Fan Speed Control Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control There are 3 types of fan speed settings Lo Me Hi 8 6 Outdoor Fan Spee...

Страница 25: ...tic airflow is released and the airflow direction vane move left and right in the range shown in the diagram The louver can be adjusted by pressing the button to the desired vane position When stopped with remote control the vanes is reset and stopped at reset position 8 7 2 Manual Control 8 8 Horizontal Airflow Direction Control 8 8 2 Manual Control 8 9 Powerful Operation The Powerful operation i...

Страница 26: ...tion Once the Quiet Mode is set at the remote control the Quiet Mode LED illuminated The sound level will reduce around 2 dB A for Lo fan speed or 3 dB A for Hi Me fan speed against the present operation sound level Manual Fan Speed RPM control during Lo cool RPM control during Hi Me cool Auto Fan Speed Quiet operation stops when Quiet button is pressed again Stopped by OFF ON operation button Tim...

Страница 27: ...the set time For Automatic operation the indoor fan will operate at SLo speed for 20 seconds 30 minutes before the set time to detect the intake air temperature to determine the operation mode The operation indication lamp will blink at this time 8 12 2 OFF Timer When the OFF Timer is set by using the remote control the unit will stop operate according to the desired setting Notes 1 By pressing ON...

Страница 28: ...ng Sound Long beep sound will be heard when Stopping the air conditioner using ON OFF switch Stopping the Quiet Mode Stopping the Powerful Mode Short beep sound will be heard for others setting 28 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 29: ...9 Operating Instructions 29 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 30: ...30 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 31: ...31 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 32: ...32 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 33: ...33 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 34: ...34 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 35: ...user is defective it will cause water leakage electrical shock or fire 2 Install according to this installation instruction strictly If installation is defective it will cause water leakage electrical shock or fire 3 Use the attached accessories parts and specified parts for installation Otherwise it will cause the set to fall water leakage fire or electrical shock 4 Install at a strong and firm l...

Страница 36: ...ains using one of the following method Power supply point should be in an easily accessible place for the power disconnection in case of emergency Power supply point should be in an easily accessible place for the power disconnection in case of emergency Power supply connection to a circuit breaker for the permanent connection Use an approved fuse or circuit breaker refer to name plate for the per...

Страница 37: ...cles Recommended installation height for indoor unit shall be at least 8 2 OUTDOOR UNIT If an awning is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed Keep animals or plants away from the unit as they may be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not...

Страница 38: ...tally by aligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with ø2 3 4 hole core drill Line according to the arrows marked on the lower left and right side of the installation plate The meeting point of the extended line is the centre of the hole Another method is by putting measuring tape at position as shown in the diagram above The hole centre i...

Страница 39: ...39 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 40: ...TALLATION OF AIR PURIFYING FILTER 1 Open the front panel 2 Remove the air filters 3 Put air purifying filter into place as shown in illustration at below HOW TO TAKE OUT FRONT GRILLE Please follow the steps below to take out front grille if necessary such as when servicing 1 Open the intake grille and remove the screw at the front of the front grille 2 Set the vertical airflow direction louver to ...

Страница 41: ...SOUND ON OFF The ON OFF of Remote Controller receiving sound can be change over by the following steps a Release the Auto Switch after Test Run operation is activated b Then within 20 sec after a press Auto Switch for more than 5 sec A beep beep sound will occur at the fifth sec then release the Auto Switch c Within 20 sec after b press Auto Switch again Everytime Auto Switch is pressed within 20 ...

Страница 42: ...able MODEL Piping size Torque Gas Liquid C18DK 1 2 40 6 lbf ft 1 4 13 3 lbf ft C24DK 5 8 47 9 lbf ft 1 4 13 3 lbf ft Connecting The Piping To Outdoor Unit Decide piping length and then cut by using pipe cutter Remove burrs from cut edge Make flare after inserting the flare nut located at valve onto the copper pipe Align center of piping to valves and then tighten with torque wrench to the specifie...

Страница 43: ...e after approximately five minutes Note BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE 5 Disconnect the charging hose from vacuum pump and from the service port of the 3 way valve 6 Tighten the service port caps of the 3 way valve at a torque of 13 3 lbf ft with a torque wrench 7 Remove the valve caps of both of the 3 way valves Position both of the valves to OPEN using...

Страница 44: ...nit at cooling operation mode for fifteen minutes or more Measure the temperature of the intake and discharge air Ensure the difference between the intake temperature and the discharge is more than 14 4 F CHECK ITEMS Is there any gas leakage at flare nut connections Has the heat insulation been carried out at flare nut connection Is the connecting cable being fixed to terminal board firmly Is the ...

Страница 45: ...d Closed Open Open Transferring Clockwise With cap Counter Clockwise Connected manifold gauge Evacuation Open Open Open Open Servicing Counter clockwise Connected manifold gauge Counter clockwise Connected manifold gauge Gas charging Open Open Open Open Servicing Counter clockwise Connected manifold gauge Counter clockwise Connected manifold gauge Pressure check Open Closed Open Open Servicing Cou...

Страница 46: ...in in the indoor unit and refrigeration pipes it will affect the compressor reduce to cooling capacity and could lead to a malfunction 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighten the service port caps of both the 3 way valves at a torque of 4 05lbf with a torque wrench 7 Remove the valve caps of the 3 way valves Position both of the va...

Страница 47: ...perate the air conditioner at the cooling cycle and stop it when the gauge indicates 0 kg cm2 G 0 PSI If the unit cannot be operated at the cooling condition weather is rather cool press the Pump Down switch on the Indoor Unit So that the unit can be operated 7 Immediately set the gas side 3 way valve to the close position Do this quickly so that the gauge ends up indicating 1 to 3 kg cm2 G 14 5 P...

Страница 48: ...frigerant from liquid High side 3 way valve service port and then discharge the refrigerant until gas Low side gauge needle indicates 3 kg cm2 G 43 5 PSI If air remain in the indoor unit and refrigeration pipes it will affect the compressor reduce to cooling capacity and could lead to a malfunction 7 Tighten the service port caps of both the 3 way valves at a torque of 4 05 lbf with a torque wrenc...

Страница 49: ...hether the pressure indicates more than 14 5 PSI 1 kg cm2 G 3 Connect the charge set s centre hose to refrigerant reclaiming equipment 4 Open the valve Low side on the charge set and loosen the hose connected with the Refrigerant Reclaiming Equipment to purge the air from the hose 5 Turn on refrigerant reclaiming equipment to collect the refrigerant until the needle indicates 0 no refrigerant is r...

Страница 50: ...oved toward 76 cmHg 14 5 PSI Apply the vacuum for approximately 1 hour vacuum of 4mmHg or less 3 Close the valve Low side and High side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approximately 5 minutes after the vacuum pump is turned off 4 Disconnect the charge hose from the vacuum pump 11 5 Evacuation 50 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 51: ... to the unit Be sure to open only the High side valve on the charge set to charge the system from the liquid side high pressure pipe If the system cannot be charged with the specified amount of refrigerant operate the compressor until the specified amount can be charged and then close the valve at the bottom of the charge cylinder 4 Immediately disconnect the charge hose from both the 3 way valve ...

Страница 52: ...Release the CN STM1 connector Fig 4 Release the CN STM2 connector Fig 4 Release the hooks that hold the Electronic Controller and pull out the Electronic Controller Fig 4 Release the CN FM connector Fig 4 Release the AC01 white connector Fig 4 Release the two RY PWR connector Fig 4 Fig 1 Fig 2 Fig 3 Fig 4 12 Servicing Information Caution Pb free solder has a higher melting point than standard sold...

Страница 53: ...or Fig 5 e Release the indicator Fig 5 f Pull out the Drain Hose from outlet to remove the Discharge Grille Fig 5 2 Release the 2 screws Fig 6 3 By pressing down the hook at the left you will be able to remove the Control Board Fig 6 4 Remove the screw at the Cross Flow Fan Fig 7 5 Remove the Bearing Fig 8 6 Remove the screws at the left of the Evaporator Fig 8 Fig 5 Fig 6 Fig 7 Fig 8 12 2 Cross F...

Страница 54: ... in the Fig 7 before installing the Cross Flow Fan When the batteries are inserted for the first time or the batteries are replaced all the indications will blink and the remote control might not work If this happen remove the cover of the remote control and you will find a resetting terminal and by shorting it with a minus screwdriver it will return to normal Fig 9 12 3 Remote Control Reset 54 CS...

Страница 55: ...ong beep Turn OFF remote control signal receiving sound After Auto OFF ON Button is pressed the 20s counter for various setting mode is restarted 12 4 2 Select Remote Control Transmission Code There are 4 type of remote control transmission code could be selected and stored in EEPROM of indoor unit The indoor unit will only operate when received signal with same transmission code from remote contr...

Страница 56: ...cle Such problems include insufficient insulation problem with the power source malfunction of a compressor and a fan The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table on the right 13 Troubleshooting Guide 56 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 57: ...perature fifteen minutes after an operation is started 13 1 2 Diagnosis methods of a malfunction of a compressor Nature of fault Symptom Electric current during operation becomes approximately 20 lower than the normal value Insufficient compressing of a compressor The discharge tube of the compressor becomes abnormally hot normally 158 to 194 F The difference between high pressure and low pressure...

Страница 58: ...14 Technical Data 14 1 Thermostat characteristics 58 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 59: ...14 2 Operation characteristics CS C18DKU CU C18DKU 59 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 60: ...60 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 61: ... CS C24DKU CU C24DKU 61 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 62: ...62 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 63: ...or Unit 15 1 CS C18DKU CS C24DKU Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts 63 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 64: ...0 19 BACK COVER CHASSIS 1 CWD932162B 20 CONTROL BOARD CASING 1 CWH102250B 21 TERMINAL BOARD COMPLETE 1 CWA28C2226 0 23 ELECTRONIC CONTROLLER MAIN 1 CWA743810 CWA743809 0 24 INDICATOR COMPLETE 1 CWE39C1122 0 25 INDICATOR HOLDER 1 CWD932435 26 INDICATOR HOLDER 1 CWD932436 27 SENSOR COMPLETE 1 CWA50C2135 28 CONTROL BOARD TOP COVER 1 CWH131210 29 CONTROL BOARD FRONT COVER 1 CWH131209 30 REMOTE CONTROL...

Страница 65: ... Outdoor Unit 17 1 CU C18DKU Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts 65 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 66: ...7 2 CU C24DKU Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts 66 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 67: ...ROL BOARD CASING 1 CWH10K1057 22 CAPACITOR FM 3 0µF 450V 3 5µF 440V 1 F0GAH305A002 0 23 CAPACITOR COMP 40µF 400V 60µF 440V 1 CWA312078 0 24 HOLDER CAPACITOR 1 CWH301005 25 HOLDER CAPACITOR 1 CWH30060 26 THERMOSTAT 1 CWA151029 27 TERMINAL BOARD ASS Y 1 CWA28K1123 0 28 FUSE 250V 1 XBA2C31TR0 0 29 FUSE HOLDER 1 K3GB1BH00006 0 30 TERMINAL BOARD ASS Y 1 CWA4711013 0 31 CABINET FRONT PLATE ASS Y 1 CWE06...

Страница 68: ...CONTROL BOARD CASING 1 CWH102221 21 CAPACITOR COMP 40µF 400V 60µF 440V 1 DS441606CPNA 0 22 CAPACITOR FM 3 0µF 450V 3 5µF 440V 1 DS441355NPQA 0 23 HOLDER CAPACITOR 1 CWH30071 24 TERMINAL BOARD ASS Y 1 CWA28K1097 25 CABINET SIDE PLATE L 1 CWE041096A 26 HANDLE 1 CWE161010 27 CABINET SIDE PLATE R 1 CWE041097A 28 HANDLE 2 CWE16000E 29 CABINET FRONT PLATE ASS Y 1 CWE06K1046 30 WIRE NET 1 CWD041041A 31 C...

Страница 69: ...RFUL ORG D104 BZ01 BZ e c b Q01 R55 1k 1 2 3 4 5 6 7 9 8 16 15 14 13 12 11 10 IC05 B1HBGGF00013 ELECTRONIC CONTROL UNIT IC101 3 1 2 HA XH4 C22 0 01 R68 10k e c b Q08 e c b Q07 C49 D13 R38 R16 R88 10k R69 10k C35 C34 C33 R15 R12 R13 D102 D103 D105 D101 R101 47 R14 R17 R34 10k C01 0 01 R40 10k C32 0 1 3 2 1 CN SONIC 1 2 R39 1k e c b Q06 R28 1k JP6 C101 47 6 3V CS C18DK CU C18DK CS C24DK CU C24DK 69 ...

Страница 70: ... P70 P03 NTP3 P02 NTP2 P01 NTP1 P00 NTP0 Vss1 X1 X2 IC XT1 XT2 AVref P10 ANO Reset AVd0 CN STM1 1 2 3 4 5 1 2 3 4 5 ZH5 VERTICAL IC06 B1HBGGF00013 R04 R05 43 2W 43 2W 1 2 3 4 5 6 7 9 8 16 15 14 13 12 11 10 CN STM2 1 2 3 4 5 1 2 3 4 5 ZH5 HORIZONTAL R09 10k IC02 5 6 8 3 1 RS DO DI R B CS SK 4 Vcc GND 2 7 C3EBD0000021 JX2 R57 20k C05 0 1 R06 24k C03 0 01 1 6V C30 0 1 R10 10k AIR TEMP SENSOR 15k 3950...

Страница 71: ... 75k R76 10k ZD01 7 5V ZD02 8 2V R111 6 2k 1 4W R112 6 2k 1 4W R113 6 2k 1 4W R114 6 2k 1 4W PC04 4 1 2 3 R75 7 5k PC06 feedback 1 4 3 2 R78 5 62k C46 10 50V C11 0 01 25V ZD03 8 5V PC05 Q04 1 4 3 2 c b e C48 0 01 PC03 4 1 2 3 D03 R72 3 9k R73 330k R74 330k R71 100k R70 100k Z01 L01 DB03 TH01 TH02 C47 0 1 450V C20 3300 35V C14 410 25V C26 100 16V R99 82k 1 4W R98 82k 1 4W R97 82k 1 4W R96 82k 1 4W ...

Страница 72: ...TERMINAL TO POWER SUPPLY SOURCE TO INDOOR UNIT MAGNETIC RELAY CAPACITOR CAPACITOR COMPRESSOR MOTOR 1 2 3 L N BROWN BROWN YELLOW WHITE 1 1 4 6 5 BLUE RED BLACK BLACK BLUE 2 BLUE RED YELLOW BLUE ORANGE BROWN OR YELLOW BLUE RED TERMINAL TO POWER SUPPLY SOURCE TO INDOOR UNIT MAGNETIC RELAY CAPACITOR THERMOSTAT CAPACITOR COMPRESSOR MOTOR C H L 72 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 73: ...0 sec 0 sec Soft Dry OFF 6 min 36 sec ON 10 min 60 sec Soft Dry 10 min operation Deodorizing Control Cooling 40 sec 4 sec 70 sec 7 sec 20 sec 2 sec 180 sec 18 sec Soft Dry 40 sec 4 sec 360 sec 36 sec Comp Reverse Rotation Detection 5 min 30 sec Comp ON 5 min and above 2 min 0 sec Comp Fan Motor Delay Timer 1 6 sec 0 sec Powerful Mode Operation 15 min 15 sec Random Auto Restart Control 0 62 sec 0 6...

Страница 74: ...19 2 Remote Control 74 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 75: ...19 3 Print Pattern Indoor Unit Printed Circuit Board TOP VIEW BOTTOM VIEW 75 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...

Страница 76: ...19 4 Print Pattern Indicator Receiver Printed Circuit Board TOP VIEW BOTTOM VIEW 76 CS C18DKU CU C18DKU CS C24DKU CU C24DKU PHAAM Printed in Malaysia ...

Отзывы: