27
9.4.3
Manual Fan Speed Control
z
Manual fan speed can be set with Fan Speed selection button at the remote control
z
There are 3 level of fan speed setting : Lo, Me, Hi
9.5 Outdoor Fan Speed Control
z
There is only one speed for outdoor fan motor.
z
When compressor stops, outdoor fan will continue running for 30 seconds.
9.6 Vertical Airflow Direction Control.
z
The louver can be adjusted by pressing the button at remote control to the desired position.
z
When operation stops using remote control, the discharge vent is reset ,and stop at the closing position..
Operation mode
Manual 18
°
28
°
37
°
46
°
55
°
Cooling/ Soft Dry
Auto 18
°
~ 55
°
Manual
Depending on remote control setting
During judgment
Auto 18
°
9.7 Horizontal Airflow Direction Control
z
Horizontal airflow direction louver can be adjusted manually by hand.
9.8 Timer
Control
z
Timer can be set using remote control (12-hour timer setting). When Timer- ON is set for cooling and Soft Dry
operation, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortable
environment when reaching the set ON time.
z
For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
z
For Automatic operation, the indoor fan will operate at Slo speed for 25 seconds, 30 minutes before the set time
to detect the intake air temperature to determine the operation mode. The power LED will blink during detection.
z
If main power supply is switched off or encounter power failure, timer setting will be cancel. Timer needs to be
reset.
z
The ON timer or OFF timer will be cancel by pressing CANCEL button.
z
The ON timer or OFF timer will be cancel is ON/OFF operation button is pressed.
z
Each timer setting is effective only once.
9.9 Random Auto Restart Control
z
If there is a power failure during operation, the air conditioner will automatically restart after 3 minutes when the
power is resumed.
z
It will start with previous operation mode and airflow direction.
z
If timer is set, timer setting will be cancel. The timer needs to be reset after the power is resumed.
Содержание CS-YC9MKV
Страница 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Страница 12: ...12 4 Dimensions 4 1 Indoor Unit Unit mm...
Страница 13: ...13 4 2 Outdoor Unit...
Страница 14: ...14 5 Refrigeration Cycle Diagram Evaporator Condenser...
Страница 15: ...15 6 Block Diagram POWER SUPPLY AC 220v 60 Hz SINGLE PHASE...
Страница 16: ...16 7 Wiring Connection Diagram 7 1 Indoor unit...
Страница 17: ...17 7 2 Outdoor Unit...
Страница 20: ...20 8 2 3 Indoor Unit Installation...