27 

9.4.3 

Manual Fan Speed Control 

z

 

Manual fan speed can be set with Fan Speed selection button at the remote control 

z

 

There are 3 level of fan speed setting : Lo, Me, Hi 

 

9.5  Outdoor Fan Speed Control 

z

 

There is only one speed for outdoor fan motor. 

z

 

When compressor stops, outdoor fan will continue running for 30 seconds. 

 

9.6  Vertical Airflow Direction Control. 

z

 

The louver can be adjusted by pressing the button at remote control to the desired position. 

z

 

When operation stops using remote control, the discharge vent is reset ,and stop at the closing position.. 

 

Operation mode 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual 18

°

 28

°

 37

°

 46

°

 55

°

 

Cooling/ Soft Dry 

Auto 18

°

  ~  55

°

 

Manual 

Depending on remote control setting 

During judgment 

Auto 18

°

 

 
 

9.7  Horizontal Airflow Direction Control 

z

 

Horizontal airflow direction louver can be adjusted manually by hand. 

 

9.8 Timer 

Control 

z

 

Timer can be set using remote control (12-hour timer setting). When Timer- ON is set for cooling and Soft Dry 
operation, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortable 
environment when reaching the set ON time. 

z

 

For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time. 

z

 

For Automatic operation, the indoor fan will operate at Slo speed for 25 seconds, 30 minutes before the set time 
to detect the intake air temperature to determine the operation mode. The power LED will blink during detection. 

z

 

If main power supply is switched off or encounter power failure, timer setting will be cancel. Timer needs to be 
reset. 

z

 

The ON timer or OFF timer will be cancel by pressing CANCEL button. 

z

 

The ON timer or OFF timer will be cancel is ON/OFF operation button is pressed. 

z

 

Each timer setting is effective only once.  

 

9.9  Random Auto Restart Control 

z

 

If there is a power failure during operation, the air conditioner will automatically restart after 3 minutes when the 
power is resumed. 

z

 

It will start with previous operation mode and airflow direction. 

z

 

If timer is set, timer setting will be cancel. The timer needs to be reset after the power is resumed. 

 
 

Содержание CS-YC9MKV

Страница 1: ...g Connection Diagram 16 7 1 Indoor unit 16 7 2 Outdoor Unit 17 8 Installation Instruction 18 8 1 Select The Best Location 18 8 2 Indoor Unit 19 8 3 Outdoor Unit 22 9 Operation Control 24 9 1 Cooling O...

Страница 2: ...s Forced Operation 28 10 5 Anti Freezing Control 28 10 6 Compressor Reverse Rotation Protection Control 28 10 7 Dew Prevention Control 29 11 Servicing Mode 30 11 1 Auto Off On Button 30 11 2 Remote Co...

Страница 3: ...Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 8 This equipment must be properly...

Страница 4: ...tenance 5 Power supply connection to the air conditioner Connect the power supply cord of the air conditioner to the mains using one of the following methods Power supply point should be in easily acc...

Страница 5: ...ion 4 poles Input Power W Output Power W 20 20 Lo rpm 780 850 Me rpm 880 960 Indoor Fan Hi rpm 1010 1060 Type Propeller Propeller Material PP PP Motor Type Induction 6 poles Induction 6 poles Input Po...

Страница 6: ...H x L mm 610 x 336 x 25 4 610 x 315 x 25 4 Fin Material Bear Fin Bear Fin Fin Type Slit Fin Slit Fin Row x Stage x FPI 1 x 24 x 18 2 x 24 x 18 Outdoor Heat Exchanger Size W x H xD mm 570 7 x504 0 x 12...

Страница 7: ...n 4 poles Input Power W Output Power W 20 20 Lo rpm 780 850 Me rpm 880 960 Indoor Fan Hi rpm 1010 1060 Type Propeller Propeller Material PP PP Motor Type Induction 6 poles Induction 6 poles Input Powe...

Страница 8: ...H x L mm 610 x 336 x 25 4 610 x 315 x 25 4 Fin Material Bear Fin Bear Fin Fin Type Slit Fin Slit Fin Row x Stage x FPI 1 x 24 x 18 2 x 24 x 18 Outdoor Heat Exchanger Size W x H xD mm 570 7 x504 0 x 12...

Страница 9: ...s Compressor Output Power W 1100 Type Cross flow fan Material AS Motor Type Induction 4 poles Input Power W Output Power W 20 Lo rpm 850 Me rpm 960 Indoor Fan Indoor Airflow Hi rpm 1060 Type Propeller...

Страница 10: ...coated Fin Type Slit fin Row x Stage x FPI 2 x 16 x 19 Indoor Heat Exchanger Size W x H x L mm 610 x 315 x 25 4 Fin Material Bear Fin Fin Type Slit Fin Row x Stage x FPI 2 x 24 x 18 Outdoor Heat Excha...

Страница 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...

Страница 12: ...12 4 Dimensions 4 1 Indoor Unit Unit mm...

Страница 13: ...13 4 2 Outdoor Unit...

Страница 14: ...14 5 Refrigeration Cycle Diagram Evaporator Condenser...

Страница 15: ...15 6 Block Diagram POWER SUPPLY AC 220v 60 Hz SINGLE PHASE...

Страница 16: ...16 7 Wiring Connection Diagram 7 1 Indoor unit...

Страница 17: ...17 7 2 Outdoor Unit...

Страница 18: ...ondenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not p...

Страница 19: ...h 5 screws or more If mounting the unit on the wall consider using anchor bolts Always mount the installation plate horizontally by aligning the marking off line with the thread and using a level gaug...

Страница 20: ...20 8 2 3 Indoor Unit Installation...

Страница 21: ...prene sheathed 3x 1 0 mm2 YC9MKV YC9MKV 7 or 3 x 1 5mm2 YC12MKV YC12MKV 6 YC12MKV 7 flexible cords type designation 245 IEC 57 or heavier cord Ensure the color of wires of outdoor unit and the termina...

Страница 22: ...flare nut with fingers Further tighten the flare nut with torque wrench in specified torque as stated in the table 8 3 2 2 Connecting the piping to outdoor unit Decide piping length and then cut by us...

Страница 23: ...cmHg 0Mpa to 76cmHg 0 1Mpa in step 3 above take the following measure If the leak stops when the piping connections are tightened further continue working from step 3 If the leak does not stop when th...

Страница 24: ...own the room temperature to the setting temperature set on the remote control z The remote control setting temperature which takes the reading of intake air temperature sensor can be adjusted from 16...

Страница 25: ...t Dry operation runs for less tan 10 minutes and once stop it will not be activated within 6 minutes z Dry operation area is shown as follows 9 2 1 Time Graph for Soft Dry operation 9 3 Automatic oper...

Страница 26: ...Manual o o z Auto Fan Speed during cooling operation 1 At the beginning of each compressor starts operation indoor fan speed increases gradually for deodorizing purpose 2 Indoor fan will rotate altern...

Страница 27: ...operation the unit with timer set will start operate earlier than the setting time This is to provide a comfortable environment when reaching the set ON time z For Cooling and Soft Dry operation the...

Страница 28: ...n Once the air conditioner is turned on the compressor will not stop within 30 seconds in a normal operation although the intake air temperature has reached the thermo off temperature However force st...

Страница 29: ...tivated when Compressor runs continuously for 60 minutes Horizontal air vane is at position 4 or 5 refer to 9 6 Actual fan speed is lower than Lo level Intake air temperature is lower than 29 Intake a...

Страница 30: ...e z To switch ON the sounds repeat above operation 4 Random Auto Restart Function OFF ON z Factory setting is ON z To close this function press and hold AUTO OFF ON button for approximately 15 seconds...

Страница 31: ...ndard Gas Pressure Mpa kg cm 2 G Outlet air Temperature C Cooling Mode 0 4 0 6 4 6 12 16 Condition Indoor fan speed High Outdoor temperature 35 C at cooling mode Different in the intake and outlet air...

Страница 32: ...ectric current and temperature fifteen minutes after an operation is started Diagnosis methods of a malfunction of a compressor Nature of fault Symptom Insufficient compressing of a compressor z Elect...

Страница 33: ...his caution may result in electric shocks 1 Open the intake grille and pull it to the horizontal position 3 Pull up the front panel and be careful of the hooks on both sides of intake grille Slightly...

Страница 34: ...e the air filters and then pull out the front grille form the unit body 1 Separate the drain hose and the drain plate 2 Pull out the discharge grille slightly Front grille Removal Procedure for Discha...

Страница 35: ...side and pull out the whole evaporator 2 Loose the fixing screw of the cross flow fan 3 After removing the bearing indoor fan can be taken out from the left side 4 Lift up the indoor fan slightly and...

Страница 36: ...Exploded View and Replacement Pars List 14 1 Indoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service p...

Страница 37: ...E 1 CWD933355 CWD933355 CWD933355 15 TERMINAL BOARD COMPLETE 1 CWA28C2384 CWA28C2384 CWA28C2384 16 POWER SUPPLY CORD COMPLETE 1 CWA20C3005 CWA20C3005 CWA20C3007 17 MAIN PCB 1 CWA73C4900 CWA73C4900 CWA...

Страница 38: ...CE 1 CWD933355 CWD933355 CWD933355 15 TERMINAL BOARD COMPLETE 1 CWA28C2384 CWA28C2384 CWA28C2384 16 POWER SUPPLY CORD COMPLETE 1 CWA20C3004 CWA20C3004 CWA20C3006 17 MAIN PCB 1 CWA73C4899 CWA73C4899 CW...

Страница 39: ...39 14 2 Outdoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 40: ...CWB021260 CWB021260 O 14 3 WAY VALVE 1 CWB011322 CWB011322 CWB011322 O 15 NUT FOR TERMIANL COVER 1 CW7080300J CW7080300J CW7080300J 16 SOUND PROOF BOARD 1 CWH151080 CWH151080 CWH151080 17 SOUND PROOF...

Страница 41: ...4 3 WAY VALVE 1 CWB011323 CWB011323 CWB011323 O 15 NUT FOR TERMIANL COVER 1 CW7080300J CW7080300J CW7080300J 16 SOUND PROOF BOARD 1 CWH151080 CWH151080 CWH151080 17 SOUND PROOF MATERIAL 1 CWG302554 CW...

Отзывы: