18
3
Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0cmHg (0 Mpa) to -76cmHg (-0.1Mpa). Then evacuate the air approximately ten minutes.
4
Close the Low side valve of the charging set and turn off the vacuum pump. Make sure the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5
Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6
Tighten the service port caps of the 3-way valve at a torque of 18N
m with a torque wrench.
7
Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4mm).
8
Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
Caution
•
If gauge needle does not move from 0cmHg (0Mpa) to -76cmHg (-0.1Mpa), in step 3 above take the following
measure:
•
If the leak stops when the piping connections are tightened further, continue working from step 3.
•
If the leak does not stop when the connections are retightened, repair location of leak.
•
Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant,
it may cause frostbite.
8.3.4 Connect the cable to the outdoor unit
1
Remove the control board cover from the unit by loosening the screw.
2
Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 x
1.5mm
2
flexible cords, type designation 245 IEC 57 or heavier cord.
3
Secure the cable onto the control board with the holder (clamper).
4
Attach the control board cover back to the original position with the screw.
5
For wiring stripping and connection requirement, refer to instruction 8.2.3.1of indoor unit.
8.3.5 Piping insulation
1
Please carry insulation at piping connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram.
Please wrap the insulated piping end to prevent water from going inside the piping.
2
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E-FOAM with thickness 6mm or above.
Содержание CS-YC12NKV-6
Страница 8: ...8 4 Dimensions 4 1 Indoor Unit Unit mm Unit mm Unit mm Unit mm ...
Страница 9: ...9 4 2 Outdoor Unit ...
Страница 10: ...10 5 Refrigeration Cycle Diagram Evaporator Condenser ...
Страница 11: ...11 6 Block Diagram POWER SUPPLY AC 220V 60 Hz SINGLE PHASE ...
Страница 12: ...12 7 Wiring Connection Diagram ...
Страница 15: ...15 8 2 3 Indoor Unit Installation ...
Страница 32: ...32 Cooling Characteristics at Different Piping Length ...