Safety precautions

3. Repairs to sealed components

• During repairs to sealed components, all 

electrical supplies shall be disconnected from 
the equipment being worked upon prior to any 
removal of sealed covers, etc.

• If it is absolutely necessary to have an 

electrical supply to equipment during 
servicing, then a permanently operating 
form of leak detection shall be located at the 
most critical point to warn of a potentially 
hazardous situation.

• Particular attention shall be paid to the 

following to ensure that by working on 
electrical components, the casing is not 
altered in such a way that the level of 
protection is affected.This shall include 
damage to cables, excessive number of 
connections, terminals not made to original 
speci

fi

 cation, damage to seals, incorrect 

fi

 tting 

of glands, etc.

• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have 

not degraded such that they no longer serve 
the purpose of preventing the ingress of 

fl

 ammable atmospheres.

• Replacement parts shall be in accordance 

with the manufacturer’s speci

fi

 cations.

NOTE: The use of silicon sealant may inhibit 
the effectiveness of some types of leak 
detection equipment.
Intrinsically safe components do not have to be 
isolated prior to working on them.

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 
presence of a 

fl

 ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts speci

fi

 ed 

by the manufacturer. Unspeci

fi

 ed parts by 

manufacturer may result ignition of refrigerant 
in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 
sources such as compressors or fans.

6. Detection of 

fl

 ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching or 
detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked 

fl

 ame) shall not be used.

7. The following leak detection methods 

are deemed acceptable for all refrigerant 
systems

• No leaks shall be detected when using 

detection equipment with a sensitivity of 
5 grams per year of refrigerant or better 
under a pressure of at least 0.25 times the 
maximum allowable pressure (>1.04 MPa, 
max 4.15 MPa), for example, a universal 
sniffer.

• Electronic leak detectors may be used 

to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need 
re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 
refrigerant used.

• Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and 
shall be calibrated to the refrigerant employed 
and the appropriate percentage of gas (25 % 
maximum) is con

fi

 rmed.

• Leak detection 

fl

uids are also suitable for use 

with most refrigerants, for example, bubble 
method and 

fl

uorescent method agents. The 

use of detergents containing chlorine shall 
be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

• If a leak is suspected, all naked 

fl

 ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. The precautions 
in #8 must be followed to remove the 
refrigerant.

English

ACXF55-26911_YZ0120-1.indb   27

ACXF55-26911_YZ0120-1.indb   27

11/19/2019   11:15:08 AM

11/19/2019   11:15:08 AM

Содержание CS-XKU9WKT

Страница 1: ...ed Installation Instructions should be kept and read by the installer before installation Remote control is packaged in the indoor unit and removed by the installer before installation ACXF55 26911 Mo...

Страница 2: ...2 O PE N 2 3 1 1 2 AAA 3 A 1 5 12 am pm 24 2 SET 8 B A ACXF55 26911_YZ0120 1 indb 2 ACXF55 26911_YZ0120 1 indb 2 11 19 2019 11 14 55 AM 11 19 2019 11 14 55 AM...

Страница 3: ...11 12 13 14 15 16 18 19 AAA R03 2 2 2 MODE DRY AUTO COOL 1 POWER 3 TEMP 16 0 C 30 0 C 60 F 86 F 10 C F ACXF55 26911_YZ0120 1 indb 3 ACXF55 26911_YZ0120 1 indb 3 11 19 2019 11 14 56 AM 11 19 2019 11 14...

Страница 4: ...4 ACXF55 26911_YZ0120 1 indb 4 ACXF55 26911_YZ0120 1 indb 4 11 19 2019 11 14 57 AM 11 19 2019 11 14 57 AM...

Страница 5: ...5 ELCB RCD ELCB Ni Cd nanoe G ACXF55 26911_YZ0120 1 indb 5 ACXF55 26911_YZ0120 1 indb 5 11 19 2019 11 14 57 AM 11 19 2019 11 14 57 AM...

Страница 6: ...in A Amin R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A R32 R410A R22 R32 R410A 1 2 R32 R410A a b c d e ACXF55 26911_YZ0120 1 indb 6 ACXF55 26911_YZ0120 1 indb 6 11 19 2019 11 14 58 AM 11 19 2019 11 1...

Страница 7: ...7 2 2 1 2 2 2 2 2 8 2 2 f g h i j 5 0 25 1 04MPa 4 15MPa 1 Amin A 12 ACXF55 26911_YZ0120 1 indb 7 ACXF55 26911_YZ0120 1 indb 7 11 19 2019 11 14 58 AM 11 19 2019 11 14 58 AM...

Страница 8: ...8 2 7 2 8 2 3 2 4 CO2 2 5 2 6 ACXF55 26911_YZ0120 1 indb 8 ACXF55 26911_YZ0120 1 indb 8 11 19 2019 11 14 58 AM 11 19 2019 11 14 58 AM...

Страница 9: ...9 3 4 5 6 7 5 0 25 1 04MPa 4 15MPa LFL 25 OFN 8 ACXF55 26911_YZ0120 1 indb 9 ACXF55 26911_YZ0120 1 indb 9 11 19 2019 11 14 58 AM 11 19 2019 11 14 58 AM...

Страница 10: ...10 9 OFN 7 10 a b c d 8 OFN OFN OFN OFN ACXF55 26911_YZ0120 1 indb 10 ACXF55 26911_YZ0120 1 indb 10 11 19 2019 11 14 59 AM 11 19 2019 11 14 59 AM...

Страница 11: ...11 e f g h 80 i j k 11 12 Waste Transfer Note ACXF55 26911_YZ0120 1 indb 11 ACXF55 26911_YZ0120 1 indb 11 11 19 2019 11 14 59 AM 11 19 2019 11 14 59 AM...

Страница 12: ...LOGY POWER TIMER nanoe TECHNOLOGY ECO AIR SWING POWERFUL 4 ECO POWERFUL ECO POWERFUL ECO FAN SPEED QUIET FAN SPEED AUTO QUIET FAN SPEED QUIET ACXF55 26911_YZ0120 1 indb 12 ACXF55 26911_YZ0120 1 indb 1...

Страница 13: ...SET SLEEP POWERFUL ECO FAN SPEED QUIET POWERFUL ECO POWERFUL QUIET FAN SPEED ON OFF SET TIMER CANCEL CANCEL 1 2 3 1 ON OFF 22 00 OFF 2 3 SET SLEEP ACXF55 26911_YZ0120 1 indb 13 ACXF55 26911_YZ0120 1 i...

Страница 14: ...O nanoe X nanoe X nanoe X 2 5 AUTO COOL DRY 2 nanoe TECHNOLOGY C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT ACXF55 26911_YZ0120 1 indb 14 ACXF55 26...

Страница 15: ...15 H 99 pH 7 40 C 104 F nanoe G 2 2 2 1 1 2 AUTO OFF ON 3 4 nanoe G AUTO OFF ON ACXF55 26911_YZ0120 1 indb 15 ACXF55 26911_YZ0120 1 indb 15 11 19 2019 11 15 01 AM 11 19 2019 11 15 01 AM...

Страница 16: ...ER 15 TIMER nanoe G nanoe TECHNOLOGY nanoe X nanoe TECHNOLOGY COOL nanoe TECHNOLOGY nanoe TECHNOLOGY ACXF55 26911_YZ0120 1 indb 16 ACXF55 26911_YZ0120 1 indb 16 11 19 2019 11 15 03 AM 11 19 2019 11 15...

Страница 17: ...17 AUTO OFF ON 1 2 AUTO 3 1 COOL 4 5 OFF ON COOL 15 COOL 8 C 14 4 F nanoe TECHNOLOGY 2 3 ACXF55 26911_YZ0120 1 indb 17 ACXF55 26911_YZ0120 1 indb 17 11 19 2019 11 15 04 AM 11 19 2019 11 15 04 AM...

Страница 18: ...H 26 H 27 H 28 1 H 30 H 31 H 32 2 H 33 H 34 H 35 H 36 H 37 H 38 H 39 H 41 H 50 H 51 H 52 H 58 H 59 H 64 H 67 H 70 H 71 H 72 H 85 LAN H 97 H 98 H 99 F 11 4 F 16 F 17 F 18 F 87 F 90 PFC F 91 F 93 F 94 F...

Страница 19: ...19 Pb 2 ACXF55 26911_YZ0120 1 indb 19 ACXF55 26911_YZ0120 1 indb 19 11 19 2019 11 15 04 AM 11 19 2019 11 15 04 AM...

Страница 20: ...the batteries O PE N 2 3 1 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press and set the time Press and hold for approximately 5 secon...

Страница 21: ...to change without notice for future improvement B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press to start stop the operation POWER Please note that the indication is on...

Страница 22: ...ill cause leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damag...

Страница 23: ...ote control To prevent malfunction or damage of the remote control Remove the batteries if the unit is not going to be used for a long period of time New batteries of the same type must be inserted fo...

Страница 24: ...is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the ma...

Страница 25: ...tions Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service per...

Страница 26: ...erating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines sh...

Страница 27: ...ing will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual v...

Страница 28: ...Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging the system with refrigerant Label the system when cha...

Страница 29: ...for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refr...

Страница 30: ...ration can be activated even when the unit is turned off In this condition the flap and fan speed will operate based on remote control setting If power failure occurs during this operation this operat...

Страница 31: ...F at 22 00 Each time pressed OFF exit setting 2 Set the time 3 Confirm SET To cancel ON or OFF timer press ON or OFF to select respective or then press CANCEL If timer is cancelled manually or due to...

Страница 32: ...the unit s accumulated operation time nanoe X deactivation may activate only once a day after the unit is turned off During the nanoe X deactivation the flap will open slightly with low fan speed oper...

Страница 33: ...eeks Wash rinse the filters gently with water to avoid damage to the filter surface Dry the filters thoroughly under shade away from fire or direct sunlight Replace any damaged filters Remove air filt...

Страница 34: ...d around the front panel grilles and wall surrounding the unit after extended use The dust accumulation is due to air purification effect of negative ions from nanoe G Remove the dust regularly with a...

Страница 35: ...the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F The units are not going to be used for a long period of time Activate nanoe TECHNOLOGY operation for 2 3 hou...

Страница 36: ...outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mismatch brand code H 39 Abn...

Страница 37: ...ems please contact your local authorities or dealer and ask for the correct method of disposal Pb Note for the battery symbol bottom two symbol examples This symbol might be used in combination with a...

Страница 38: ...Memo ACXF55 26911_YZ0120 1 indb 38 ACXF55 26911_YZ0120 1 indb 38 11 19 2019 11 15 13 AM 11 19 2019 11 15 13 AM...

Страница 39: ...Memo ACXF55 26911_YZ0120 1 indb 39 ACXF55 26911_YZ0120 1 indb 39 11 19 2019 11 15 13 AM 11 19 2019 11 15 13 AM...

Страница 40: ...YZ0120 1 Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2020 ACXF55 26911_YZ0120 1 indb 40 ACXF55 26911_YZ0120 1 indb 40 11 19 2019 11...

Отзывы: