1. Safety Precautions 

 

Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. 

 

Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and 
main circuit for the model installed. 

 

The caution items stated here must be followed because these important contents are related to safety. The meaning of each 
indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage, 
and the seriousness is classified by the following indications. 

 

 WARNING

 

This indication shows the possibility of causing death or serious injury. 

 CAUTION

 

This indication shows the possibility of causing injury or damage to properties. 

 

 

The items to be followed are classified by the symbols: 

 

 

This symbol denotes item that is PROHIBITED from doing. 

 

 

Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and 
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference. 

 

  

WARNING

 

1. 

Do not modify the machine, part, material during repairing service. 

2. 

If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit. 

3. 

Do not wrench the fasten terminal. Pull it out or insert it straightly. 

4. 

Engage dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause water 
leakage, electrical shock or fire. 

5. 

Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire. 

6. 

Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, 
fire or electrical shock. 

7. 

Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly 
done, the set will drop and cause injury. 

8. 

For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single 
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.

 

9. 

This equipment must installed with an Earth Leakage Circuit Breaker (ELCB) or Ground Fault Current Interrupter (GFCI) or Appliance 
Leakage Current Interrupter (ALCI) that has been certified by an NRTL Certified Testing Agency and that is suitable for the voltages and 
amperages involved. Otherwise, if may cause electrical shock and fire in case of equipment breakdown. 

10. 

Do not use joint cable for indoor / outdoor connection cable. Use the specified Indoor/Outdoor connection cable, refer to installation 
instruction 

CONNECT THE CABLE TO THE INDOOR UNIT

 and connect tightly for indoor / outdoor connection. Clamp the cable so that 

no external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.

 

11. 

Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will 
cause heat-up or fire at the connection point of terminal, fire or electrical shock.

 

12. 

When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration 
cycle (piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.). 

13. 

Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb 
up to outdoor unit and cross over the handrail and causing accident.

 

14. 

This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and 
telephone. Otherwise, it may cause electric shock in case equipment breakdown or insulation breakdown. 

 

15.  Keep away from small children, the thin film may cling to nose and mouth and prevent breathing. 

 

16. 

Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with 
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire. 

 

17. 

Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the 
flare may break and cause refrigerant gas leakage. 

 

18. 

For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant. Using of existing (R22) piping, flare nut 
and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury. 
Thickness or copper pipes used with R410A must be more than 1/32" (0.8 mm). Never use copper pipes thinner than 1/32"  
(0.8 mm). It is desirable that the amount of residual oil is less than 0.0008 oz/ft (40 mg/10 m). 

 

19. 

During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration 
piping and valves at opened condition will caused suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, 
injury etc).

 

 

Содержание CS-XE12SKUA-1

Страница 1: ...rvice or repair the products dealt with in this service information by anyone else could result in serious injury or death PRECAUTION OF LOW TEMPERATURE In order to avoid frostbite be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit CLOCK A IR C O N D IT IO N E R OFF ON SET CHECK RESET AC RC O N O F F S E T 1 2 3 T IM E R AU TO CO M FO RT POWERFUL QUIET...

Страница 2: ...SKUA 1 5 2 2 CS XE15SKUA 1 CU XE15SKUA 1 8 3 Technical Data 11 3 1 Cool Mode Performance Data 11 3 2 Heat Mode Performance Data 13 4 Service Data 14 4 1 Cool Mode Outdoor Air Temperature Characteristic 14 4 2 Heat Mode Outdoor Air Temperature Characteristic 16 4 3 Piping Length Correction Factor 18 5 Exploded View and Replacement Parts List 19 5 1 Indoor Unit 19 5 2 Outdoor Unit 22 ...

Страница 3: ...ed Testing Agency and that is suitable for the voltages and amperages involved Otherwise if may cause electrical shock and fire in case of equipment breakdown 10 Do not use joint cable for indoor outdoor connection cable Use the specified Indoor Outdoor connection cable refer to installation instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor outdoor connection Clamp th...

Страница 4: ... fin It may cause injury 5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher melting point than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to splash when heated too high ...

Страница 5: ...B A 45 28 20 45 28 20 Power Level dB 61 61 Outdoor Noise H L QLo dB A 49 49 Power Level dB 64 64 Heating Capacity kW 0 89 3 66 6 72 0 89 3 66 6 72 BTU h 3000 12500 23000 3000 12500 23000 kcal h Running Current A 4 50 4 00 Input Power W 150 860 2 10k 150 860 2 10k COP W W 5 93 4 26 3 20 5 93 4 26 3 20 BTU hW 20 00 14 50 10 95 20 00 14 50 10 95 kcal hW Power Factor 92 93 Indoor Noise H L QLo dB A 44...

Страница 6: ...h 1 1 2 3 Indoor Airflow QLo Cool m 3 min ft 3 min 5 83 205 Heat m 3 min ft 3 min 8 87 310 Lo Cool m 3 min ft 3 min 7 58 268 Heat m 3 min ft 3 min 9 79 345 Me Cool m 3 min ft 3 min 11 08 391 Heat m 3 min ft 3 min 11 99 420 Hi Cool m 3 min ft 3 min 14 7 520 Heat m 3 min ft 3 min 14 3 505 SHi Cool m 3 min ft 3 min 15 57 550 Heat m 3 min ft 3 min 15 46 545 Outdoor Airflow Hi Cool m 3 min ft 3 min 40 ...

Страница 7: ...tat Electronic Control Protection Device Electronic Control Dry Bulb Wet Bulb Indoor Operation Range Cooling Maximum F C 89 6 32 73 4 23 Minimum F C 60 8 16 51 8 11 Heating Maximum F C 86 0 30 Minimum F C 60 8 16 Outdoor Operation Range Cooling Maximum F C 114 8 46 78 8 26 Minimum F C 0 0 17 8 Heating Maximum F C 75 2 24 64 4 18 Minimum F C 15 26 0 16 26 7 1 Cooling capacities are based on indoor ...

Страница 8: ...7 34 45 37 34 Power Level dB 61 61 Outdoor Noise H L QLo dB A 51 51 Power Level dB 66 66 Heating Capacity kW 0 98 5 04 7 03 0 98 5 04 7 03 BTU h 3300 17200 24000 3300 17200 24000 kcal h Running Current A 6 5 5 7 Input Power W 200 1 23k 2 65k 200 1 23k 2 65k COP W W 4 90 4 10 2 65 4 90 4 10 2 65 BTU hW 16 50 13 95 9 05 16 50 13 95 9 05 kcal hW Power Factor 91 94 Indoor Noise H L QLo dB A 47 37 34 4...

Страница 9: ... 1 3 2 7 Indoor Airflow QLo Cool m 3 min ft 3 min 9 56 340 Heat m 3 min ft 3 min 9 56 340 Lo Cool m 3 min ft 3 min 10 56 370 Heat m 3 min ft 3 min 10 56 370 Me Cool m 3 min ft 3 min 13 10 460 Heat m 3 min ft 3 min 13 76 485 Hi Cool m 3 min ft 3 min 15 6 550 Heat m 3 min ft 3 min 16 9 595 SHi Cool m 3 min ft 3 min 15 98 560 Heat m 3 min ft 3 min 18 15 640 Outdoor Airflow Hi Cool m 3 min ft 3 min 43...

Страница 10: ...stat Electronic Control Protection Device Electronic Control Dry Bulb Wet Bulb Indoor Operation Range Cooling Maximum F C 89 6 32 73 4 23 Minimum F C 60 8 16 51 8 11 Heating Maximum F C 86 0 30 Minimum F C 60 8 16 Outdoor Operation Range Cooling Maximum F C 114 8 46 78 8 26 Minimum F C 0 17 8 Heating Maximum F C 75 2 24 64 4 18 Minimum F C 15 26 0 16 26 7 1 Cooling capacities are based on indoor t...

Страница 11: ...1 18 64 4 3743 2426 516 3508 2236 696 3176 2288 780 2744 1749 935 20 68 0 13 55 4 2623 2596 236 2599 2573 541 2845 2817 793 1930 1910 726 16 60 8 3007 2137 455 3125 2188 713 2892 2196 785 2444 1711 957 3 1 2 CS XE15SKUA 1 CU XE15SKUA 1 Rated frequency compressor speed is fixed during forced heating or cooling for capacity measurement and diagnosis purpose Indoor C F Outdoor C F DB WB 20 4 0 10 14 ...

Страница 12: ... 3411 2496 595 3567 2497 854 3528 2679 1057 2982 2088 1108 3 1 4 CS XE15SKUA 1 CU XE15SKUA 1 Maximum Capacity Indoor C F Outdoor C F DB WB 20 4 0 10 14 0 0 32 0 5 41 0 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 27 80 6 19 66 2 5421 4686 863 5416 4682 853 5409 4766 873 5394 4660 895 22 71 6 6219 3830 754 6213 3827 745 5922 3743 864 5524 3510 862 23 73 4 16 60 8 4771 4723 953 4766 4718 941 5067 5016 78...

Страница 13: ...24 75 2 1156 385 1567 853 2934 1135 3745 1145 4910 1300 5126 1293 5524 1242 20 68 0 1186 379 1613 822 2943 1092 3800 1097 5040 1230 5330 1241 5744 1191 16 60 8 1123 364 1506 785 2968 1044 3841 1051 5165 1163 5473 1175 5899 1128 3 2 3 CS XE12SKUA 1 CU XE12SKUA 1 Maximum Capacity Indoor C F Outdoor C F DB 26 14 8 20 4 0 8 3 17 06 1 7 35 06 8 3 46 94 12 53 6 23 9 75 02 TC IP TC IP TC IP TC IP TC IP T...

Страница 14: ...g Pressure PSI MPa Indoor Discharge Air Temprature F C 208 230 60 0 15 5 61 0 16 1 62 0 16 6 63 0 17 2 64 0 17 7 65 0 18 3 66 0 18 8 67 0 19 4 2 500 3 000 3 500 4 000 4 500 5 000 120 000 0 827 125 000 0 861 130 000 0 896 135 000 0 930 140 000 0 965 145 000 0 999 150 000 1 034 155 000 1 068 160 000 1 103 165 000 1 137 4 20 0 6 14 4 16 8 8 26 3 3 36 2 2 46 7 7 56 13 3 66 18 8 76 24 4 86 30 0 96 35 5...

Страница 15: ...5 000 0 930 140 000 0 965 145 000 0 999 150 000 1 034 155 000 1 068 160 000 1 103 165 000 1 137 170 000 1 172 4 20 0 6 14 4 16 8 8 26 3 3 36 2 2 46 7 7 56 13 3 66 18 8 76 24 4 86 30 0 96 35 5 106 41 1 116 46 6 Outdoor Air Temperature F C 4 20 0 6 14 4 16 8 8 26 3 3 36 2 2 46 7 7 56 13 3 66 18 8 76 24 4 86 30 0 96 35 5 106 41 1 116 46 6 Outdoor Air Temperature F C 4 20 0 6 14 4 16 8 8 26 3 3 36 2 2...

Страница 16: ...Discharge Air Temprature F C 208 230 65 0 18 3 70 0 21 1 75 0 23 8 80 0 26 6 85 0 29 4 90 0 32 2 95 0 35 0 100 0 37 7 105 0 40 5 110 0 43 3 2 000 2 500 3 000 3 500 4 000 4 500 5 000 5 500 200 000 1 378 250 000 1 723 300 000 2 068 350 000 2 413 400 000 2 757 450 000 3 102 15 26 1 5 20 5 5 15 15 9 4 25 3 8 35 1 6 45 7 2 55 12 7 65 18 3 75 23 8 Outdoor Air Temperature F C 15 26 1 5 20 5 5 15 15 9 4 2...

Страница 17: ... 500 5 000 5 500 6 000 6 500 7 000 7 500 200 000 1 378 250 000 1 723 300 000 2 068 350 000 2 413 400 000 2 757 450 000 3 102 15 26 1 5 20 5 5 15 15 9 4 25 3 8 35 1 6 45 7 2 55 12 7 65 18 3 75 23 8 Outdoor Air Temperature F C 15 26 1 5 20 5 5 15 15 9 4 25 3 8 35 1 6 45 7 2 55 12 7 65 18 3 75 23 8 Outdoor Air Temperature F C 15 26 1 5 20 5 5 15 15 9 4 25 3 8 35 1 6 45 7 2 55 12 7 65 18 3 75 23 8 Out...

Страница 18: ... 0 95 0 97 0 99 1 01 1 03 2 6 5 3 9 8 4 13 1 5 16 4 6 19 6 7 22 9 8 26 2 9 29 5 10 32 8 11 36 0 12 39 3 13 42 6 14 45 9 15 49 2 16 52 4 17 55 7 18 59 0 19 62 3 20 65 6 21 68 8 Piping length m ft Capacity correction factor 0 95 0 96 0 97 0 98 0 99 1 00 1 01 1 02 2 6 5 3 9 8 4 13 1 5 16 4 6 19 6 7 22 9 8 26 2 9 29 5 10 32 8 11 36 0 12 39 3 13 42 6 14 45 9 15 49 2 16 52 4 17 55 7 18 59 0 19 62 3 20 6...

Страница 19: ...arts disassembly and replacement The non numbered parts are not kept as standard service parts CWH55025J CWH55051AJ O I I I I I 39 A B A 34 A 30 29 61 A A B B B B B A 23 43 42 10 1 3 4 46 45 44 59 58 62 60 57 33 8 7 39A 6 4A 2 9 24 27 28 25 31 32 31A 40 17 22 21 11 41 17A 18 13 19 14 20 36 38 37 35 12 22A 64 65 63 ...

Страница 20: ...8K1020 23 CAP DRAIN TRAY 1 CWH521259 24 SENSOR COMPLETE 1 CWA50C2800 25 ELECTRONIC CONTROLLER MAIN 1 ACXA73C42410 ACXA73C42420 O 27 CONTROL BOARD CASING 1 CWH102564A 28 CONTROL BOARD TOP COVER 1 CWH131531 29 CONTROL BOARD FRONT COVER CO 1 CWH13C1309 30 TERMINAL BOARD COMPLETE 1 CWA28C2616 31 ELECTRONIC CONTROLLER INDICATOR 1 CWA747456 O 31A ELECTRONIC CONTROLLER RECEIVER 1 CWA747457 O 32 INDICATOR...

Страница 21: ...TRONIC CONTROLLER 1 CWA747279 O 61 PARTICULAR PIECE TERMINAL 1 CWD933464A 62 BAG COMPLETE TIBE CONNECTOR 1 CWH82C2030 63 SHOCK ABSORBER L 1 CWG713484 64 SHOCK ABSORBER R 1 CWG713485 65 C C CASE 1 CWG568509 NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 22: ...r the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts x 2 x 2 6 63 10 41 40 38 9 7 22 12 47 31 27 15 30 49 67 43 33 48 20 19 11 45 42 59 5 58 1 25 24 23 3 4 62 28 14 71 18 2 8 69 46 60 64 74 73 72 ...

Страница 23: ...OMP TEMP 1 CWA50C2343 O 27 V COIL COMPLETE 4 WAY VALVE 1 CWA43C2392 O 28 V COIL COMPLETE EXP VALVE 1 ACXA43C00490 ACXA43C00320 O 30 SENSOR COMPLETE AIR TEMP AND PIPE TEMP 1 CWA50C2710 O 31 REACTOR 1 G0C193J00004 G0C203J00003 O 33 TERMINAL BOARD ASSY 1 CWA28K1154 O 38 ELECTRONIC CONTROLLER MAIN 1 ACXA73C42440R ACXA73C42450R O 40 CONTROL BOARD COVER TOP 1 CWH131333 O 41 CABINET SIDE PLATE LEFT 1 CWE...

Страница 24: ...E DESCRIPTION QTY CU XE12SKUA 1 CU XE15SKUA 1 REMARK 74 C C CASE 1 CWG568360 NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock Printed in Malaysia FY0218 0 ...