1. The main power is turned on while the transmission
wires between the indoor unit and the outdoor unit are
not connected (open circuit at section A).
Symptom:
Operation of indoor unit No. 1 and indoor unit No. 3 is
possible.
However, “CHECK” flashes in the remote control unit
display for 3-5 minutes after the main power is turned
on.
−
−
−
−
Remote control . . . “CHECK” flashes.
−
−
−
−
Indoor unit No. 2 . . . LED2 on the printed circuit
board flashes (both master and slave units).
−
−
−
−
Outdoor unit No. 2 . . . LED3 and LED7 on the
printed circuit board flash.
2. The main power is turned on while the power supply
wires between the indoor units are not connected (open
circuit at section B).
Symptom:
Operation of indoor unit No. 1 and indoor unit No. 3 is
possible.
However, if operation is then started in this condition,
the combination of the 28BB outdoor unit and the 14BB
indoor unit (master unit) will cause abnormal operation
of indoor unit No. 2 to occur.
↓
If operation continues, an abnormality will occur on the
refrigeration cycle and aoperation will stop.
−
−
−
−
Remote control . . . “CHECK” flashes (indoor unit
No. 2 abnormality).
−
−
−
−
Indoor unit No. 2 . . . LED2 on the printed circuit
board flashes (both master and slave units).
−
−
−
−
Outdoor unit No. 2 . . . The LEDs on the printed
circuit board flash.
3. The main power is turned on while the remote control
connection cord is not connected (open circuit at section
C).
Symptom:
Nothing abnormal appears on the remote control
display, and operation of indoor unit. No. 1 and indoor
unit No. 2 is possible.
However, indoor unit No. 3 cannot be operated.
Remedy
1. Turn off the main power.
↓
2. Connect the disconnected wires correctly.
↓
3. Turn the main power back on.
↓
4. After 1 minute, start operation using the remote control.
(Indoor units . . . Operation will start according to the
remote control setting.)
(Outdoor units . . . Operation will start after 3-5 minutes.)
If slave units do not operate even after the wiring has been
corrected (automatic addressing is not possible)
1. Check that DIP switches 1 to 4 and DIP switch 8 are all
set to OFF, and then stop operation.
↓
2. Press the “AIRSWING AUTO”, “OPERATION” and “A/C
No.” buttons simultaneously.
The addresses will be momentarily reset, and then
automatic address setting will be carried out once more.
The above procedure cannot be used to carry out automatic
address resetting of twin/triple control.
(Note on automatic address setting)
The printed circuit boards automatically store the connected
system configuration when power is supplied. As a result,
once the power has been turned on for these printed circuit
boards, the units can not be changed about within the
system, even if the units are of the same model and have
same capacity.
51
Содержание CS-W50BD3P
Страница 11: ...5 TECHNICAL DRAWING CS W50BD3P OUTSIDE DIMENSIONS 11 ...
Страница 12: ...CU V50BBP8 12 ...
Страница 13: ...6 CIRCUIT DIAGRAM CS W50BD3P 13 ...
Страница 14: ...CU W50BBP8 14 ...
Страница 15: ...CU V50BBP8 15 ...
Страница 16: ...APPLICABLE FOR ALL MODELS 16 ...
Страница 17: ...APPLICABLE FOR ALL MODELS 17 ...
Страница 18: ...APPLICABLE FOR ALL MODELS 18 ...
Страница 19: ...19 ...
Страница 20: ...20 ...
Страница 21: ...21 ...
Страница 22: ...7 OPERATING INSTRUCTION 7 1 Wired Remote Control Name and function of each part 22 ...
Страница 23: ...23 ...
Страница 24: ...8 REFRIGERATION CYCLE 8 1 Heating Model CS W50BD3P CU W50BBP8 8 2 Cooling Only Model CS W50BD3P CU V50BBP8 24 ...
Страница 35: ...17 SOUND DATA 35 ...
Страница 36: ...36 ...
Страница 44: ...20 3 Test operation using the wired remote control 44 ...
Страница 45: ...45 ...
Страница 46: ...O O O OSelf diagnosis error code table 46 ...
Страница 61: ...25 8 Indoor thermostat characteristic 1 Thermostat characteristic during cooling and heating modes 61 ...
Страница 62: ...62 ...
Страница 63: ...63 ...
Страница 65: ...25 14 DIP switch settings Indoor unit printed circuit board DSW1 65 ...
Страница 66: ...26 INSTALLATION INDOOR UNIT 66 ...
Страница 67: ...67 ...
Страница 68: ...68 ...
Страница 69: ...69 ...
Страница 70: ...70 ...
Страница 71: ...71 ...
Страница 72: ...72 ...
Страница 73: ...73 ...
Страница 74: ...74 ...
Страница 75: ...75 ...
Страница 76: ...76 ...
Страница 77: ...77 ...
Страница 78: ...27 INSTALLATION OUTDOOR UNIT 78 ...
Страница 79: ...79 ...
Страница 80: ...80 ...
Страница 81: ...81 ...
Страница 82: ...82 ...
Страница 83: ...83 ...
Страница 84: ...84 ...
Страница 85: ...85 ...
Страница 86: ...86 ...
Страница 87: ...87 ...
Страница 88: ...88 ...
Страница 89: ...89 ...
Страница 90: ...28 REPLACEMENT PARTS 28 1 INDOOR UNIT CS W50BD3P 90 ...
Страница 92: ...28 2 OUTDOOR UNIT 92 ...
Страница 93: ...93 ...
Страница 94: ...94 ...
Страница 95: ...95 ...