8 Operation Details
8.1. COOLING MODE OPERATION
Cooling in operation according to the remote control setting.
8.1.1. Time Delay Safety Control (3 minutes)
·
When the compressor is stopped by Power Switch, Remote Control or when there is a power failure, it restarts after 3 minutes
when the Power Switch, Remote Control is turned ON or when the power supply is resumed.
·
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
8.1.2. 7 Minutes Time Save Control
·
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is below the compressor
ON temperature.
8.1.3. Anti-Freezing Control
·
If the
temperature
of the
indoor
heat
exchanger
falls
continously below 2°C for 4 minutes, the compressor turns off
to protect the indoor heat exchanger from freezing.The fan
speed setting remains the same.
·
Compressor recommences when the indoor heat exchanger
temperature rises to 10 °C (Recovery).
*3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
8.1.4. Compressor Protection Control
·
After the compressor operates for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
automatically.(Time Delay Safety Control is valid).
·
If the above phenomenon is repeated 3 times, the compressor will stop.
·
The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
8.1.5. Compressor Reverse Rotation Protection Control
·
If the compressor is operating continually for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5 °C or less for 2 minutes, the compressor will stop and restart automatically.
(Time Delay Safety Control is valid).
T =Intake air temperature - Indoor heat exchanger temperature
This is to protect the compressor against reverse rotation when there is an instantaneous power failure.
19
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE
Содержание CS-VA120KE
Страница 4: ...2 Functions 2 1 REMOTE CONTROL 4 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 5: ...2 2 INDOOR UNIT 5 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 6: ...2 3 OUTDOOR UNIT 6 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 22: ...8 2 6 Soft Dry Operation Time Diagram 22 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 42: ...10 3 INDOOR OUTDOOR UNIT INSTALLATION DIAGRAM 42 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 54: ...13 Troubleshooting Guide 54 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 57: ...14 2 OPERATION CHARACTERISTICS 57 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 58: ...58 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 59: ...59 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 64: ...15 4 REMOTE CONTROLLER 64 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 69: ...17 2 CS VA120KE 17 2 1 Exploded View 69 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 71: ...17 3 CU VA70KE CU VA90KE 17 3 1 Exploded View 71 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 73: ...17 4 CU VA120KE 17 4 1 Exploded View 73 CS VA70KE CU VA70KE CS VA90KE CU VA90KE CS VA120KE CU VA120KE ...
Страница 76: ...MEMO ...
Страница 77: ...MEMO ...
Страница 78: ...Printed in Japan MS1299SO ...