(Cooling and Soft Dry Operation condition)
8.9. Powerful Operation
•
The Powerful operation is to achieve the setting temperature quickly.
•
When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present
setting temperature (Lower temperature limit: 16°C).
•
This operation automatically will be running under SHi Fan Speed (Cooling).
•
Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
•
Powerful operation stops when:-
−
Powerful operation has operate for 15 minutes.
−
Powerful button is pressed again.
−
Quiet button is pressed.
−
Stopped by OFF/ON operation button.
−
Timer OFF activates.
−
Operating mode is changed.
8.10. Quiet Operation
•
The Quiet operation is to provide quiet cooling/heating operation condition compare to normal operation.
(Cooling and Soft Dry Operation condition)
•
Once the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around
2 dB(A) for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present sound level operation.
•
Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo
+ 100 rpm). After that, it goes back to QLo +180 rpm (However Quiet LED remains on).
•
Manual Fan Speed:-
−
RPM control during Lo cool
−
RPM control during Hi & Me cool
24
CS-V18DKE CU-V18DKE / CS-V24DKE CU-V24DKE
Содержание CS-V18DKE
Страница 11: ...4 2 Outdoor Unit 4 2 1 CU V18DKE CU V24DKE 11 CS V18DKE CU V18DKE CS V24DKE CU V24DKE ...
Страница 12: ...5 Refrigeration Cycle Diagram 12 CS V18DKE CU V18DKE CS V24DKE CU V24DKE ...
Страница 13: ...6 Block Diagram 13 CS V18DKE CU V18DKE CS V24DKE CU V24DKE ...
Страница 14: ...7 Wiring Diagram CS V18DKE CU V18DKE CS V24DKE CU V24DKE 14 ...
Страница 15: ...CS V18DKE CU V18DKE CS V24DKE CU V24DKE 15 ...
Страница 71: ...71 CS V18DKE CU V18DKE CS V24DKE CU V24DKE ...
Страница 73: ...19 2 Remote Control 73 CS V18DKE CU V18DKE CS V24DKE CU V24DKE ...
Страница 74: ...19 3 Print Pattern Indoor Unit Printed Circuit Board 74 CS V18DKE CU V18DKE CS V24DKE CU V24DKE ...
Страница 75: ...75 CS V18DKE CU V18DKE CS V24DKE CU V24DKE ...