 Safety Precautions

8. Removal and evacuation

• When breaking into the refrigerant circuit 

to make repairs – or for any other purpose 
– conventional procedures shall be used. 
However, it is important that best practice is 
followed since 

fl

 ammability is a consideration. 

The following procedure shall be adhered to: 
remove refrigerant -> purge the circuit with 
inert gas -> evacuate -> purge with inert gas 
-> open the circuit by cutting or brazing.

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be purged with OFN to 

render the appliance safe.

• This process may need to be repeated 

several times.

• Compressed air or oxygen shall not be used 

for this task.

• Purging shall be achieved by breaking 

the vacuum in the system with OFN and 
continuing to 

fi

ll until the working pressure is 

achieved, then venting to atmosphere, and 

fi

nally pulling down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the 

fi

 nal OFN charge is used, the 

system shall be vented down to atmospheric 
pressure to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any potential ignition sources and 
there is ventilation available.

OFN = oxygen free nitrogen, type of inert gas.

9. Charging procedures

• In addition to conventional charging 

procedures, the following requirements shall 
be followed.

 

- Ensure that contamination of different 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible 

to minimize the amount of refrigerant 
contained in them. 

 

- Cylinders shall be kept in an appropriate 

position according to the instructions.

 

- Ensure that the refrigerating system is 

earthed prior to charging the system with 
refrigerant.

 

- Label the system when charging is 

complete (if not already). 

 

- Extreme care shall be taken not to over 

fi

ll 

the refrigerating system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior 

to leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant. To avoid 

fi

 re 

or explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 
familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 
case analysis is required prior to re-use of 
recovered refrigerant.

• It is essential that electrical power is available 

before the task is commenced.

a) Become familiar with the equipment and 

its operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure 

that: 

• mechanical handling equipment is 

available, if required, for handling 
refrigerant cylinders; 

• all personal protective equipment is 

available and being used correctly;

• the recovery process is supervised at all 

times by a competent person;

• recovery equipment and cylinders conform 

to the appropriate standards.

d) Pump down refrigerant system, if possible.

Содержание CS-RZ9YKA

Страница 1: ...ler should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control packed with the indoor unit If the equipment is transferred to a new us...

Страница 2: ...R03 3 8 A 1 5 12 am pm 24 2 ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE SLEEP FAN SPEED QUIET POWERFUL ECO AIR CONDITIONER ON OFF TIMER CANCEL AIR SWING SLEEP FAN SPEED QUIET POWERFUL EC...

Страница 3: ...3 B 2 DRY AUTO HEAT COOL 1 POWER ON 3 TEMP UP TEMP DOWN 16 0 C 30 0 C 60 F 86 F 10 C F 4 11 12 13 14 15 16 18 19 AAA R03 2 2 Panasonic...

Страница 4: ...4...

Страница 5: ...5 ON Ni Cd ELCB RCD ELCB BS...

Страница 6: ...6 nanoe G R32 Amin m Amin m A R32 R410A R22 R32 R22 R32 R22 R32 R410A R32 R410A R32 R410A R22 R32 R410A 1 2 R32 R410A AHU a b c d...

Страница 7: ...7 e f g h i j 5 0 25 1 04 MPa 4 15 MPa 1 A Amin m 12 2 2 1 2 2 2 2 2 8 2 2...

Страница 8: ...8 2 3 2 4 CO2 2 5 2 6 2 7 2 8...

Страница 9: ...9 6 7 5 1 04 MPa 4 15 MPa 0 25 LFL 25 8 3 4 5...

Страница 10: ...10 10 a b c d e f g h 80 i j k 11 8 OFN OFN OFN OFN 9 OFN 7...

Страница 11: ...11 12...

Страница 12: ...E SLEEP FAN SPEED QUIET POWERFUL ECO AIR CONDITIONER FAN SPEED QUIET FAN SPEED AUTO FAN QUIET FAN SPEED QUIET POWERFUL 20 ECO POWERFUL ECO POWERFUL ECO nanoe X nanoe G nanoe TECHNOLOGY nanoe TECHNOLOG...

Страница 13: ...EP POWERFUL ECO FAN SPEED QUIET POWERFUL ECO POWERFUL QUIET FAN SPEED 0 5 1 2 3 4 5 6 7 8 9 OFF 0 0h SLEEP ON OFF SET TIMER CANCEL 1 2 3 1 TIMER ON TIMER OFF 22 00 OFF OFF 2 3 SET ON OFF CANCEL ON OFF...

Страница 14: ...COOL 26 0 C 28 0 C 79 F 82 F COOL DRY HEAT AUTO COOL HEAT DRY nanoe X nanoe X nanoe X COOL DRY 2 5 nanoe TECHNOLOGY 2 C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8...

Страница 15: ...15 H 99 pH 7 40 C 104 F nanoeTM G 2 2 nanoe G AUTO OFF ON 1 2 2 AUTO OFF ON 1 3 4...

Страница 16: ...16 POWER TIMER ON 30 TIMER ON 30 nanoe G nanoe TECHNOLOGY nanoe X nanoe TECHNOLOGY OFF ON HEAT COOL nanoe TECHNOLOGY nanoe TECHNOLOGY...

Страница 17: ...17 AUTO OFF ON 1 2 AUTO 3 COOL 4 2 HEAT 5 5 AUTO OFF ON COOL HEAT 15 COOL 8 C 14 4 F HEAT 14 C 25 2 F HEAT 2 3...

Страница 18: ...2 H 14 H 15 H 16 CT H 17 H 19 H 21 H 23 1 H 24 2 H 25 H 26 ION H 27 H 28 1 H 30 H 31 H 32 2 H 33 H 34 H 35 H 36 H 37 H 38 H 39 H 41 H 50 H 51 H 52 H 58 H 59 H 64 H 67 nanoe H 70 H 71 H 72 H 85 H 97 H...

Страница 19: ...19 Pb...

Страница 20: ...ime as 12 hour am pm or 24 hour 2 Press to confirm Use the remote control within 8 m from the remote control receiver on the indoor unit A new built in Network Adaptor that allows you to control your...

Страница 21: ...tely 10 seconds to show the temperature as C or F Table of Contents Safety Precautions 22 29 How to Use 30 31 To Learn More 32 Cleaning the Air Conditioner 33 Troubleshooting 34 36 Information 37 Acce...

Страница 22: ...e supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit I...

Страница 23: ...ic shock nanoe G generator Do not touch the sharp pin which may cause injury Power supply Do not use a modified cord joint cord extension cord or unspecified cord to prevent overheating and fire To pr...

Страница 24: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use o...

Страница 25: ...the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised...

Страница 26: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Страница 27: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Страница 28: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Страница 29: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Страница 30: ...reless LAN feature ON or OFF Press to restore the remote control to default setting This operation combines both nanoe X and nanoe G nanoe TECHNOLOGY nanoe TECHNOLOGY automatically starts when the uni...

Страница 31: ...ion can be cancelled by pressing the respective button until the sleep timer reaches 0 0h SLEEP How to Use To connect to a network For Wireless LAN Module operation setup please refer to Setup Instruc...

Страница 32: ...power failure the operation will restart automatically with the last operation mode and airflow direction This control is not applicable when TIMER is set nanoe X filter deactivation Depending on the...

Страница 33: ...filters Once every 2 weeks Wash rinse the filters gently with water to avoid damaging the surface Dry the filters thoroughly under a shade away from fire or direct sunlight Replace any damaged filter...

Страница 34: ...of materials used in plastic parts It is accelerated when exposed to heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding...

Страница 35: ...r The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL...

Страница 36: ...heat sink temperature sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnorma...

Страница 37: ...ght be used in combination with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flam...

Страница 38: ...Memo...

Страница 39: ...Memo...

Страница 40: ...Printed in Malaysia Panasonic Corporation 1006 Oaza Kadoma Kadoma City Osaka 571 8501 Japan Website http www panasonic com Panasonic Corporation 2022 ACXF55 32270 SS0122 0...

Отзывы: