37
13.2.3 Error Codes Table
Code
Abnormality/Protection
Judgment
Check
Emergency
Operation
H00
Normal
H11
Indoor/Outdoor abnormal
communication
>1 minute after starting
operation
Connecting cable,
Indoor/outdoor PCB
○
H14
Indoor intake air temp sensor
abnormality
-
Intake air temperature
sensor(defected or
disconnected)
×
H15
Outdoor compressor
tempearture sensor abnormality
Continue for 5 sec.
Compressor tempeature
sensor(defected or
disconnected)
×
H16
Outdoor Current Transformer
open circuit
-
Outdoor PCB, IPM module
×
H19
Indoor fan motor mechanism
lock
-
Indoor PCB, fan motor
×
H23
Indoor heat exchanger
temperature A sensor
abnormality
Continue for 5 sec.
Heat exchanger
temperature
sensor(defected or
disconnected)
○
H27
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
Outdoor temperature
sensor(defected or
disconnected)
○
H28
Outdoor heat exchanger
temperature sensor abnormality
Continue for 5 sec.
Outdoor heat exchanger
sensor(defected
disconnected)
○
H30
Discharge temperature sensor
abnormality
Continue for 5 sec.
Discharge temperature
sensor(defected or
disconnected)
×
H33
Incorrect connection of
Indoor/Outdoor cable
-
Indoor/outdoor supply
voltage
×
H97
Outdoor fan motor lock
Twice within 30 minutes Outdoor fan motor
×
H98
Indoor high pressure protection -
Air filter dirty
Air circulation short circuit
-
H99
Indoor heat exchanger anti-
freezing protection
Indoor heat exchanger
freezing
Insufficient refrigerant
Air filter dirty
-
F11
Cooling/Heating cycle
changeover abnormality
4 times occurrence
within 30 minutes
4-way valve
V-coil
×
F90
PFC control
4 times occurrence
within 20 minutes
Voltage at PFC
×
F91
Refrigeration cycle abnormality
2 times occurrence
within 20 minutes
No refrigerant(3-way valve is
closed)
×
F93
Compressor abnormality
4 times occurrence
within 20 minutes
Compressor
×
F95
Cool high pressure protection
4 times occurrence
within 20 minutes
Outdoor refrigeration cycle
×
F96
IPM overheating protection
-
Excessive refrigerant
Improper heat radiation
IPM
×
F97
Outdoor compressor
overheating protection
4 times occurrence
within 20 minutes
Insufficient refrigerant
Compressor
×
F98
Total running current protection
3 times occurrence
within 20 minutes
Excess refrigerant
Improper radiation
×
F99
Outdoor Peak Current
Protection Control
4 times occurrcnce
continuously within 30
minutes
Outdoor PCB
IPM
Compressor
×
Содержание CS-RE9PKE-3
Страница 11: ...11 5 Dimensions 5 1 Indoor Unit Unit mm...
Страница 12: ...12 5 2 Outdoor Unit Unit mm...
Страница 13: ...13 6 Refrigeration Cycle Diagram CS CU RE9PKE 3 CS CU RE12PKE 3 CS CU RE15PKE 3 COOLING HEATING COOLING HEATING...
Страница 14: ...14 7 Block Diagram...
Страница 15: ...15 8 Wiring Diagram...
Страница 18: ...18 9 2 3 Indoor Unit Installation...
Страница 42: ...42 Cooling Characteristic at Different Piping Length...
Страница 43: ...43 Heating Characteristic at Different Outdoor Air Temperature...
Страница 44: ...44 Heating Characteristic at Different Piping Length...
Страница 45: ...45 15 1 2 CS RE12PKE 3 CU RE12PKE 3 Cooling Characteristic at Different Outdoor Air Temperature...
Страница 46: ...46 Cooling Characteristic at Different Piping Length...
Страница 47: ...47 Heating Characteristic at Different Outdoor Air Temperature...
Страница 48: ...48 Heating Characteristic at Different Piping Length...
Страница 49: ...49 15 1 3 CS RE15PKE 3 CU RE15PKE 3 Cooling Characteristic at Different Outdoor Air Temperature...
Страница 50: ...50 Cooling Characteristic at Different Piping Length...
Страница 51: ...51 Heating Characteristic at Different Outdoor Air Temperature...
Страница 52: ...52 Heating Characteristic at Different Piping Length...
Страница 53: ...53 16 Exploded View and Replacement Pars List 16 1 Indoor Unit CS RE9PKE 3 CS RE12PKE 3 CS RE15PKE 3...
Страница 55: ...55 16 2 Outdoor Unit CU RE9PKE 3 CU RE12PKE 3 CU RE15PKE 3...