13.2.3  Error Codes Table 

 

 

Code

Abnormality/Protection

Judgment

Check

Emergency

Operation

H00

Normal

H11

Indoor/Outdoor abnormal
communication

>1 minute after starting
operation

Connecting cable,
Indoor/outdoor PCB

H14

Indoor intake air temp sensor
abnormality

-

Intake air temperature
sensor(defected or
disconnected)

×

H15

Outdoor compressor
tempearture sensor abnormality

Continue for 5 sec.

Compressor tempeature
sensor(defected or
disconnected)

×

H16

Outdoor Current Transformer
open circuit

-

Outdoor PCB, IPM module

×

H19

Indoor fan motor mechanism
lock

-

Indoor PCB, fan motor

×

H23

Indoor heat exchanger
temperature A sensor
abnormality

Continue for 5 sec.

Heat exchanger
temperature
sensor(defected or
disconnected)

H27

Outdoor air temperature sensor
abnormality

Continue for 5 sec.

Outdoor temperature
sensor(defected or
disconnected)

H28

Outdoor heat exchanger
temperature sensor abnormality

Continue for 5 sec.

Outdoor heat exchanger
sensor(defected
disconnected)

H30

Discharge temperature sensor
abnormality

Continue for 5 sec.

Discharge temperature
sensor(defected or
disconnected)

×

H33

Incorrect connection of
Indoor/Outdoor cable

-

Indoor/outdoor supply
voltage

×

H97

Outdoor fan motor lock

Twice within 30 minutes Outdoor fan motor

×

H98

Indoor high pressure protection -

Air filter dirty
Air circulation short circuit

-

H99

Indoor heat exchanger anti-
freezing protection

Indoor heat exchanger
freezing

Insufficient refrigerant
Air filter dirty

-

F11

Cooling/Heating cycle
changeover abnormality

4 times occurrence
within 30 minutes

4-way valve
V-coil

×

F90

PFC control

4 times occurrence
within 20 minutes

Voltage at PFC

×

F91

Refrigeration cycle abnormality

2 times occurrence
within 20 minutes

No refrigerant(3-way valve is
closed)

×

F93

Compressor abnormality

4 times occurrence
within 20 minutes

Compressor

×

F95

Cool high pressure protection

4 times occurrence
within 20 minutes

Outdoor refrigeration cycle

×

F96

IPM overheating protection

-

Excessive refrigerant
Improper heat radiation
IPM

×

F97

Outdoor compressor
overheating protection

4 times occurrence
within 20 minutes

Insufficient refrigerant
Compressor

×

F98

Total running current protection

3 times occurrence
within 20 minutes

Excess refrigerant
Improper radiation

×

F99

Outdoor Peak Current
Protection Control

4 times occurrcnce
continuously within 30
minutes

Outdoor PCB
IPM
Compressor

×

Содержание CS-RE9PKE-3

Страница 1: ...n Code 22 10 3 Operate and Display of Remote Control 23 11 Operation Control 25 11 1 Basic Function 25 11 2 Indoor Fan Motor Operation 27 11 3 Outdoor Fan Motor Operation 28 12 Protection control 30 1...

Страница 2: ...wn Self Diagnosis Function 36 14 Disassembly and Assembly Instructions 38 15 Technical Data 41 15 1 Operation Characteristic 41 16 Exploded View and Replacement Pars List 53 16 1 Indoor Unit 53 16 2 O...

Страница 3: ...ny substance other than the specified refrigerant eg air etc mix into refrigeration cycle piping Mixing of air etc will cause abnormal high pressure in refrigeration cycle and result in explosio 8 Do...

Страница 4: ...acity abnormal high pressure in the refrigeration cycle explosion and injury 27 Must not use other parts except original parts describe in catalog and manual 28 This equipment must be properly earthed...

Страница 5: ...70 3660 4390 Running Current A 3 80 5 20 Input Power W 170 820 1150 150 1120 1460 W W 5 29 4 02 3 57 6 00 3 79 3 49 BTU hW 18 06 13 71 12 16 20 47 12 94 11 91 COP kcal h W 4 53 3 46 3 07 5 13 3 27 3 0...

Страница 6: ...8 15 49 2 I D O D Height different m ft 10 32 8 10 0 32 8 Additional Gas Amount g m oz ft 20 0 2 20 0 2 Piping Length for Additional Gas m ft 7 0 23 0 7 0 23 0 Inner diameter mm 16 16 Drain Hose Leng...

Страница 7: ...r W 210 1385 2280 W W 4 28 3 61 2 98 BTU hW 14 61 12 31 10 17 COP kcal hW 3 66 3 10 2 56 Pdesign H A kW 3 6 Tbivalent 10 SCOP W W 3 4 Annual Consumption kWh 1482 Erp Class A Power Factor 95 dB A H L Q...

Страница 8: ...t g m oz ft 20 0 2 Piping Length for Additional Gas m ft 7 23 0 Inner diameter mm 16 Drain Hose Length mm 500 Fin Material Pre coated Fin Type Slit Fin Row x Stage x FPI 2 x 15 x 19 Indoor Heat Exchan...

Страница 9: ...te control Quality Improvement o Random auto restart after power failure for safety restart operation o Gas leakage protection o Prevent compressor reverse cycle o Inner protector to protect compresso...

Страница 10: ...e remote control s default setting POWER GREEN TIMER ORANGE QUIET GREEN INDICATOR POWERFUL RED Air inlet side Air outlet Air inlet rear OFF ON Temperature setting Transmitter Fan speed selection Front...

Страница 11: ...11 5 Dimensions 5 1 Indoor Unit Unit mm...

Страница 12: ...12 5 2 Outdoor Unit Unit mm...

Страница 13: ...13 6 Refrigeration Cycle Diagram CS CU RE9PKE 3 CS CU RE12PKE 3 CS CU RE15PKE 3 COOLING HEATING COOLING HEATING...

Страница 14: ...14 7 Block Diagram...

Страница 15: ...15 8 Wiring Diagram...

Страница 16: ...ld not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles which may cause a...

Страница 17: ...e wall with 5 screws or more If mounting the unit on the wall consider using anchor bolts Always mount the installation plate horizontally by aligning the marking off line with the thread and using a...

Страница 18: ...18 9 2 3 Indoor Unit Installation...

Страница 19: ...horizontally by bolt nut 10 mm 2 When installing at roof please consider strong wind and earthquake Please fasten the installation stand firmly with bolt or nails 9 3 2 Connecting the Piping 9 3 2 1 C...

Страница 20: ...side valve of the charging set and turn off the vacuum pump Make sure that the needle in the gauge does not move after approximately five minutes Note BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOI...

Страница 21: ...al position with the screw 5 For wiring stripping and connection requirement refer to instruction 9 2 4 of indoor unit 9 3 5 Pipe Insulation 1 Please carry out insulation at pipe connection portion as...

Страница 22: ...N When the switch is continuously pressed between 16 to 21 seconds either H14 error detection selection mode or remote controller s signal receiving sound can be cancelled or turned on 10 2 Select Rem...

Страница 23: ...ections by pressing AIR SWING button 5 options 10 3 6 QUIET AND POWERFULL button Start Quiet operation Press QUIET button on remote control and then QUIET displays on remote control display QUIET indi...

Страница 24: ...If the OFF ON button on the remote control or the AUTO Switch on the indoor unit is pressed the timer setting will be cancelled If Auto Restart Control occurs timer setting will be cancelled During th...

Страница 25: ...Thermostat control Compressor is OFF when Intake Air Temperature Internal Setting Temperature 1 5 Compressor is ON after waiting for 3 minutes if the Intake Air Temperature Internal Setting Temperatu...

Страница 26: ...ake Air Temperature Internal Setting Temperature Compressor OFF point 0 5K 11 1 5 Automatic Operation Once AUTO mode is selected operation mode is determined by set temperature of remote control and i...

Страница 27: ...asic Rotation Speed i Manual Fan speed Fan motor s number of rotation is determined according to remote control setting Remote control O O O O O QUIET Model Tab Hi Me Me Me Lo QLo COOLING rpm 1150 103...

Страница 28: ...3 2 Horizontal Airflow The horizontal airflow direction louvers can be adjusted manually by hand 11 3 3 Quiet operation To provide quiet operation comparing to normal operation The Quiet operation ca...

Страница 29: ...blinks the possible operation of the unit is operating mode judgment or ON timer sampling If Timer LED blinks there is an abnormal operation occurs 11 3 7 Timer control Delay ON Timer can be set usin...

Страница 30: ...he intake air temperature has reached the thermo off temperature However force stop by pressing the OFF ON button at the remote control is permitted or the Auto OFF ON button at indoor unit The reason...

Страница 31: ...ient temperature This control starts if all following conditions are achieved Outdoor unit stops or operates in fan mode Outdoor unit has stopped or in fan mode for 120 minutes or more Outdoor unit do...

Страница 32: ...ure and outdoor temperature is 20 2 Remote control setting 30 and Hi Fan Speed b Control contents Compressor stops and restart after 3 minutes If the conditions above happen 2 times within 20 minutes...

Страница 33: ...h Cooling or Soft Dry Mode Outdoor air temperature is less than 34 This control stopped if anyone of the following conditions is achieved Outdoor air temperature is over 34 Intake air temperature is l...

Страница 34: ...420 400 420 400 Time Second 20 100 20 100 20 100 3 Hot Start When the heating operation starts the indoor fan stops and the compressor runs with a certain frequency This is to prevent the cold airflo...

Страница 35: ...or temperature 35 C at cooling mode and 7 C at heating mode Compressor operates at rated frequency Different in the intake and outlet air temperatures Normal Value of electric current during operation...

Страница 36: ...be restarted using AUTO Switch on the indoor unit In forced operation the frequency for compressor and fan speed can not be changed and the signal receiving sound is different Normal Operation ON pep...

Страница 37: ...isconnected H33 Incorrect connection of Indoor Outdoor cable Indoor outdoor supply voltage H97 Outdoor fan motor lock Twice within 30 minutes Outdoor fan motor H98 Indoor high pressure protection Air...

Страница 38: ...ailure to heed this caution may result in electric shocks 1 Open the intake grille and pull it to the horizontal position 2 Pull up the intake grille until it falls off 1 Remove the two caps at the di...

Страница 39: ...he whole electronic controller Be sure to avoid cracking of the supporting hook 3 Remove the control board complete Loose the screws of control board complete then the whole control board can be pulle...

Страница 40: ...nd pull out the whole evaporator 2 Loose the fixing screw of the cross flow fan 3 After removing the bearing indoor fan can be taken out from the left side 4 Lift up the indoor fan slightly and then p...

Страница 41: ...41 15 Technical Data 15 1 Operation Characteristic 15 1 1 CS RE9PKE 3 CU RE9PKE 3 Cooling Characteristic at Different Outdoor Air Temperature...

Страница 42: ...42 Cooling Characteristic at Different Piping Length...

Страница 43: ...43 Heating Characteristic at Different Outdoor Air Temperature...

Страница 44: ...44 Heating Characteristic at Different Piping Length...

Страница 45: ...45 15 1 2 CS RE12PKE 3 CU RE12PKE 3 Cooling Characteristic at Different Outdoor Air Temperature...

Страница 46: ...46 Cooling Characteristic at Different Piping Length...

Страница 47: ...47 Heating Characteristic at Different Outdoor Air Temperature...

Страница 48: ...48 Heating Characteristic at Different Piping Length...

Страница 49: ...49 15 1 3 CS RE15PKE 3 CU RE15PKE 3 Cooling Characteristic at Different Outdoor Air Temperature...

Страница 50: ...50 Cooling Characteristic at Different Piping Length...

Страница 51: ...51 Heating Characteristic at Different Outdoor Air Temperature...

Страница 52: ...52 Heating Characteristic at Different Piping Length...

Страница 53: ...53 16 Exploded View and Replacement Pars List 16 1 Indoor Unit CS RE9PKE 3 CS RE12PKE 3 CS RE15PKE 3...

Страница 54: ...WER SUPPLY CORD COMPLETE 1 CWA20C3090 CWA20C3090 CWA20C3107 18 MAIN PCB 1 CWA73C6898 CWA73C6899 CWA73C6900 19 SENSOR 1 CWA50C2755 CWA50C2883 CWA50C2883 20 INDICATOR HOLDER FRONT 1 CWD933546 CWD933546...

Страница 55: ...55 16 2 Outdoor Unit CU RE9PKE 3 CU RE12PKE 3 CU RE15PKE 3...

Страница 56: ...ND PROOF MATERIAL 1 CWG302809 CWG302815 CWG302815 20 SOUND PROOF MATERIAL 1 CWG302693 21 SOUND PROOF MATERIAL 1 CWG302732 CWG302732 CWG302732 22 SOUND PROOF MATERIAL 1 CWG302791 CWG302791 23 TUBE NOIS...

Отзывы: