background image

29

11. Service 

Mode 

11.1  Auto OFF/ON Button 

1.  AUTO OPERATION MODE 

Once the Auto OFF/ON button is slightly pressed, the unit will immediately operate in Auto operation. This 
operation can be used to operate air conditioner with limited function if remote control is misplaced or 
malfunction. 

2.  TEST RUN OPERATION( FOR PUMP DOWN/ SERVICING PURPOSE) 

Press the button continuously for approximate 5 second and then release. A “beep” sound will be heard to 
identify the starting of TEST RUN OPERATION. 

3. HEATING 

OPERATION 

A)  Within 5 minutes after TEST RUN operation starting, press the button again for more than 5 seconds until 2 

“beep” sounds are heard, the unit will operate in heating mode. 

B)  Pressed the button continuously for approximate 8 second and then released. 2 “beep” sounds will be 

heard to identify the starting of HEATING operation.

4. DIFFERENT CONTROLLING SETTING. 

Press the button continuously for approximate 11 until 3 “beep” sounds are heard and together with the signal 
from remote controller, the unit can be changed to different controlling setting. 
For transmission code selection method, please refer to “Select Remote Control Transmission Code” 

5. INDIVIDUAL COUNTER-ACTION 

When the switch is continuously pressed between 16 to 21 seconds, either H14 error detection selection mode or 
remote controller’s signal receiving sound can be cancelled or turned on. 

11.2  Select Remote Control Transmission Code 

—

 

There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor PCB. 
The indoor unit will only operate when received signal with same transmission code from remote control. This 
could prevent signal interference when there are 2 or more indoor units installed near by together. 

—

 

To Change the code of remote controller, following table I to join or cut jumper wire on the remote controller and 
setting with "Forced operation button". Four codes (A, B, C, D) can be selected. Taking code "B" for example, 
the process below should be follow. 

       1. Press the "Auto OFF/ON” button on the indoor unit for approximate 11 seconds until 3 "Beep’s signal receiving 

sounds are heard. 

2. Within 5 minutes, gently press the "RESET" button on the remote control towards the indoor unit. One "Beep" 

sound is heard. 

3. Within 60 seconds, press any button on the remote control, the frequency of which was set as "B". Setting is 

completed after a "Beep" sound is heard. The corresponding signal sent by remote control "B" will be received 
by this indoor unit 

Table 1 

Remote control 

J02

J03

A(STANDARD) SHORT  OPEN 
B OPEN 

OPEN 

C SHORT 

SHORT 

D OPEN 

SHORT 

Auto OFF/ON 
Button Pressed 

Содержание CS-RE9JKE

Страница 1: ...24 10 3 Outdoor Unit 26 11 Service Mode 29 11 1 Auto OFF ON Button 29 11 2 Select Remote Control Transmission Code29 11 3 Operate and Display of Remote Control 30 12 Operation Control 32 12 1 Basic Fu...

Страница 2: ...g Guide 40 14 1 Refrigeration Cycle System 40 14 2 Break Down self Diagnosis Function 40 15 Disassembly and Assembly Instructions 43 16 Exploded View and Replacement Pars List 46 16 1 Indoor Unit 46 1...

Страница 3: ...gly recommended to be installed with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakd...

Страница 4: ...elect an installation location which is easy for maintenance 6 Power supply connection to the air conditioner Connect the power supply cord of the air conditioner to the mains using one of the followi...

Страница 5: ...ch 6 35 1 4 Pipe Length m ft 3 9 8 15 49 2 Height Difference m ft 5 16 4 Additional Gas Amount g m oz ft 20 0 2 Refrigerant Charge Less m ft 7 5 24 6 Inner diameter mm 14 Drain Hose Length mm 500 Type...

Страница 6: ...NG A 3 45 HEATING A 3 70 Maximum Current A 6 00 Power Factor COOLING 88 HEATING 96 Power factor means total figure of compressor indoor fan motor and outdoor fan motor Number of core 3 1 5mm Power Cor...

Страница 7: ...5 1 4 Pipe Length m ft 3 9 8 15 49 2 Height Difference m ft 5 16 4 Additional Gas Amount g m oz ft 20 0 2 Refrigerant Charge Less m ft 7 5 24 6 Inner diameter mm 14 Drain Hose Length mm 500 Type Rotar...

Страница 8: ...ING A 4 70 HEATING A 5 20 Maximum Current A 6 80 Power Factor COOLING 93 HEATING 93 Power factor means total figure of compressor indoor fan motor and outdoor fan motor Number of core 3 1 5mm Power Co...

Страница 9: ...1 4 Pipe Length m ft 3 9 8 15 49 2 Height Difference m ft 5 16 4 Additional Gas Amount g m oz ft 20 0 2 Refrigerant Charge Less m ft 7 5 24 6 Inner diameter mm 14 Drain Hose Length mm 500 Type Scroll...

Страница 10: ...LING A 6 05 HEATING A 7 10 Maximum Current A 9 70 Power Factor COOLING 90 HEATING 94 Power factor means total figure of compressor indoor fan motor and outdoor fan motor Number of core 3 1 5mm Power C...

Страница 11: ...Improvement o Random auto restart after power failure for safety restart operation o Gas leakage protection o Prevent compressor reverse cycle o Inner protector to protect compressor x Operation Impr...

Страница 12: ...se z Press RESET button to restore the remote control s default setting POWER GREEN TIMER ORANGE QUIET GREEN INDICATOR POWERFUL RED OFF ON Operation mode Airflow direction adjustment Timer setting Tem...

Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 60 Unit mm 55 290 825 848 204 61 10 5 49 63 60 119 3 404 6 38 12 5 56 16 195 60 548 398 Air outlet Air intake...

Страница 14: ...14 5 2 Outdoor Unit Unit mm...

Страница 15: ...15 6 Refrigeration Cycle Diagram CS CU RE9JKE CS CU RE12JKE CS CU RE15JKE COOLING HEATING...

Страница 16: ...16 7 Block Diagram CS CU RE15JKE CS CU RE9 12JKE...

Страница 17: ...17 8 Wiring Diagram 6 8 5 6 8 5...

Страница 18: ...18 6 8 5...

Страница 19: ...19 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board TOP VIEW...

Страница 20: ...20 BOTTOM VIEW...

Страница 21: ...21 9 1 2 Indicator receiver TOP VIEW BOTTOM VIEW...

Страница 22: ...22 9 2 Outdoor Unit 9 2 1 CU RE9JKE CU RE12JKE TOP VIEW BOTTOM VIEW...

Страница 23: ...diation from the condenser is not obstructed x There should not be any animal or plant which could be affected by hot air discharged x Keep the spaces indicated by arrows from wall ceiling fence or ot...

Страница 24: ...m this line 1 Mount the installation plate on the wall with 5 screws or more If mounting the unit on the wall consider using anchor bolts Always mount the installation plate horizontally by aligning t...

Страница 25: ...25 10 2 3 Indoor Unit Installation...

Страница 26: ...mm 2 When installing at roof please consider strong wind and earthquake Please fasten the installation stand firmly with bolt or nails 10 3 2 Connecting the Piping 10 3 2 1 Connecting the piping to i...

Страница 27: ...2 UNF 20 threads 2 Connect the center hose of the charging set to a vacuum pump with check valve or vacuum pump and vacuum pump adaptor 3 Turn on the power switch of the vacuum pump and make sure that...

Страница 28: ...mper 4 Attach the control board cover back to the original position with the screw 5 For wiring stripping and connection requirement refer to instruction 10 2 4 of indoor unit 10 3 5 Pipe Insulation 1...

Страница 29: ...switch is continuously pressed between 16 to 21 seconds either H14 error detection selection mode or remote controller s signal receiving sound can be cancelled or turned on 11 2 Select Remote Contro...

Страница 30: ...e AIR SWING button 11 3 5 AIR SWING button To adjust vertical airflow directions by pressing AIR SWING button 5 options 11 3 6 QUIET POWERFULL button Press this button to switch among QUIET operation...

Страница 31: ...nce If the OFF ON button on the remote control or the AUTO Switch on the indoor unit is pressed the timer setting will be cancelled If Auto Restart Control occurs timer setting will be cancelled Durin...

Страница 32: ...point 12 1 3 Soft Dry Operation 12 1 3 1 Thermostat control The same as Cooling mode 12 1 4 Heating operation 12 1 4 1 Thermostat control Compressor is OFF when Intake Air Temperature Internal Settin...

Страница 33: ...ck control is performed once every second During fan motor on if fan motor feedback 2550 rpm or 50 rpm continue for 10 seconds then fan motor error counter increases fan motor then stops and restarts...

Страница 34: ...ontrol Once Quiet mode is active the unit will continuously operate in QUIET Mode until cancel the mode by pressing QUIET POWERFUL button on remote control 12 3 4 Powerful operation To cooling or heat...

Страница 35: ...urs 12 3 7 Timer control Delay ON Timer ca be set using remote controller the unit with timer set will start operate earlier than the setting time This is to provide a comfortable environment when rea...

Страница 36: ...y instructed for compressor operation will be decreased 2 If the running current does not exceed I1 A for 5 seconds the frequency instructed will be increased RE9JKE RE12JKE RE15JKE Operation mode I1...

Страница 37: ...tection Control a Control start conditions For 5 minutes the compressor continuously operates and outdoor total current is between 0 65A and 1 65A During Cooling and Soft Dry operations Indoor suction...

Страница 38: ...Cooling or Soft Dry Mode Indoor intake temperature is between 25 and 29 Outdoor air temperature is less than 30 This control stopped then receive air swing change signal from Remote Control 13 2 4 Ov...

Страница 39: ...ent the cold airflow from blowing If the piping temperature rises to 19 and the indoor fan speed and airflow direction varies with the indoor piping temperature the hot start control is completed 13 3...

Страница 40: ...oor temperature 35 C at cooling mode and 7 C at heating mode Compressor operates at rated frequency Different in the intake and outlet air temperatures Normal Value of electric current during operatio...

Страница 41: ...be restarted using AUTO Switch on the indoor unit In forced operation the frequency for compressor and fan speed can not be changed and the signal receiving sound is different Normal Operation ON pep...

Страница 42: ...42 14 2 3 Error Codes Table...

Страница 43: ...proceeding with repair work Failure to heed this caution may result in electric shocks 1 Open the intake grille and pull it to the horizontal position 2 Pull up the intake grille until it falls off 1...

Страница 44: ...ow Green and take out the sensor from the holder on evaporator Pull out the whole electronic controller Be sure to avoid cracking of the supporting hook 4 Remove the control board complete Loose the s...

Страница 45: ...or on the left side and pull out the whole evaporator 2 Loose the fixing screw of the cross flow fan 3 After removing the bearing indoor fan can be taken out from the left side 4 Lift up the indoor fa...

Страница 46: ...46 16 Exploded View and Replacement Pars List 16 1 Indoor Unit CS RE9JKE CS RE12JKE CS RE15JKE...

Страница 47: ...862 CWA20C2894 17 MAIN PCB 1 CWA73C3612 CWA73C3613 CWA73C3614 18 SENSOR 1 CWA50C2596 CWA50C2596 CWA50C2596 19 INDICATOR HOLDER FRONT 1 CWD933087 CWD933087 CWD933087 21 INDICATOR PCB 1 CWA745415 CWA745...

Страница 48: ...48 16 2 Outdoor Unit CU RE9JKE CU RE12JKE...

Страница 49: ...0300J 7080300J 20 SOUND PROOF BOARD 1 CWH151187 CWH151187 21 SOUND PROOF MATERIAL 1 CWG302433 CWG302433 22 TUBE NOISE SUPPRESSOR 1 CWB121016 CWB121016 23 REACTOR 1 G0C193J00007 G0C193J00007 24 CONTROL...

Страница 50: ...50 CU RE15JKE...

Страница 51: ...D PROOF MATERIAL 1 CWG302303 22 TUBE NOISE SUPPRESSOR 1 CWB14011 23 REACTOR 1 G0C203J00004 24 CONTROL BOX COMPLETE 1 CWH14C6795 26 TERMINAL BOARD ASS Y 1 CWA28K1185 27 CONTROL BOARD CASING 1 CWH102243...

Отзывы: