13. Protection
control
13.1 Protection Control For All Operations
13.1.1 Time Delay Safety Control
ϥ
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
ϥ
This control is not applicable if the power supply is cut off and on again.
ϥ
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.1.2 30 Seconds Forced Control
ϥ
Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
ϥ
The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
13.1.3 Total running current control
1. If the outdoor unit total running current is detected exceeding I
1
(A), the frequency instructed for compressor
operation will be decreased.
2. If the running current does not exceed I
1
(A) for 5 seconds, the frequency instructed will be increased.
RE9HKE RE12HKE
Operation mode
I
1
(A) I
1
(A)
Cooling/ Soft Dry /Fan A*
5.8
7.4
Cooling/ Soft Dry /Fan B
5.6
7.3
Heating
7.01
8.05
*The first 30 minutes of cooling operation, A will be applied.
13.1.4 IPM (Power transistor) Protection Control.
1. DC Peak Current Control
ϥ
When electric current to IPM exceeds set value of DC17.3 1A, the compressor will stop. It will restart after
three minutes.
ϥ
If the set value is exceeded again within 30 seconds, the operation will restart after one minute.
ϥ
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
ϥ
Error code [F99] will be displayed.
2. Overheating protection control
When the IPM temperature rises to 90.0
к
, compressor will stop immediately.
Compressor restarts after three minutes if the temperature decreases to 85
к
13.1.5 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated compressor
discharge temperature. The change of frequency is as below.
Содержание CS-RE9HKE
Страница 11: ...11 5 Dimensions 5 1 Indoor Unit...
Страница 12: ...12 5 2 Outdoor Unit Unit mm...
Страница 13: ...13 6 Refrigeration Cycle Diagram...
Страница 14: ...14 7 Block Diagram...
Страница 16: ...16 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board TOP VIEW...
Страница 17: ...17 BOTTOM VIEW...
Страница 18: ...18 9 1 2 Indicator TOP VIEW BOTTOM VIEW...
Страница 21: ...21 10 2 3 Indoor Unit Installation...
Страница 38: ...38 14 2 3 Error Codes Table...
Страница 40: ...40...
Страница 41: ...41...
Страница 42: ...42 16 Exploded View and Replacement Pars List 16 1 Indoor Unit 35 36 38 37...
Страница 44: ...44 16 2 Outdoor Unit...