
40
13 Protection Control
13.1. Protection Control For All Operations
13.1.1.
Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
13.1.2.
30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
13.1.3.
Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
13.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 110
q
C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95
q
C.
3. If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96 is indicated).
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 30.0 ± 5.0 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two
minutes.
3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If
this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off, timer LED will be blinking
(“F99” is indicated).
RE18JK
RE24JK
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
10.7
15.0
11.0
15.0
Cooling/Soft Dry (B)
7.7
15.0
9.6
15.0
Heating
10.7
15.0
11.5
15.0
Содержание CS-RE18JKE
Страница 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control...
Страница 11: ...11 5 2 Outdoor Unit 5 2 1 CU RE18JKE...
Страница 12: ...12 5 2 2 CU RE24JKE...
Страница 13: ...13 6 Refrigeration Cycle Diagram...
Страница 14: ...14 7 Block Diagram 7 1 CS RE18JKE CU RE18JKE...
Страница 15: ...15 7 2 CS RE24JKE CU RE24JKE...
Страница 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 17: ...17 8 2 Outdoor Unit 8 2 1 CU RE18JKE...
Страница 18: ...18 8 2 2 CU RE24JKE...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 20: ...20 9 2 Outdoor Unit 9 2 1 CU RE18JKE...
Страница 21: ...21 9 2 2 CU RE24JKE...
Страница 22: ...22 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 23: ...23 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board...
Страница 24: ...24 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE18JKE...
Страница 25: ...25 10 2 2 Main Printed Circuit Board 10 2 2 1 CU RE24JKE...
Страница 26: ...26 10 2 3 Power Printed Circuit Board 10 2 3 1 CU RE24JKE...
Страница 29: ...29 1 For the right rear piping 2 For the right and right bottom piping 3 For the embedded piping...
Страница 76: ...76 16 1 3 To remove power electronic controller...
Страница 77: ...77 16 1 4 To remove discharge grille 16 1 5 To remove control board...
Страница 78: ...78 16 1 6 To remove cross flow fan and indoor fan motor...
Страница 79: ...79...
Страница 90: ...90 18 Exploded View and Replacement Parts List 18 1 Indoor Unit...