4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 
presence of a fl ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts 

specifi ed by the manufacturer. Unspecifi ed 
parts by manufacturer may result ignition of 
refrigerant in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 
sources such as compressors or fans.

6. Detection of 

fl

 ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching 
or detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked fl ame) shall not be used.

7. Leak detection methods

• Electronic leak detectors shall be used 

to detect fl ammable refrigerants, but the 
sensitivity may not be adequate, or may 
need re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 
refrigerant used.

• Leak detection equipment shall be set at 

a percentage of the LFL of the refrigerant 
and shall be calibrated to the refrigerant 
employed and the appropriate percentage of 
gas (25 % maximum) is confi rmed.

• Leak detection fl uids are suitable for use with 

most refrigerants but the use of detergents 
containing chlorine shall be avoided as the 
chlorine may react with the refrigerant and 
corrode the copper pipe-work.

• If a leak is suspected, all naked fl ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. Oxygen free 
nitrogen (OFN) shall then be purged through 
the system both before and during the 
brazing process.

8. Removal and evacuation

• When breaking into the refrigerant circuit to make 

repairs – or for any other purpose – conventional 
procedures shall be used.
However, it is important that best practice is 
followed since fl ammability is a consideration.
The following procedure shall be adhered to:
remove refrigerant -> purge the circuit with inert 
gas -> evacuate -> purge again with inert gas -> 
open the circuit by cutting or brazing

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be “fl ushed” with OFN to 

render the unit safe.

• This process may need to be repeated several times.
• Compressed air or oxygen shall not be used 

for this task.

• Flushing shall be achieved by breaking the 

vacuum in the system with OFN and continuing 
to fi ll until the working pressure is achieved, 
then venting to atmosphere, and fi nally pulling 
down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the fi nal OFN charge is used, the system 

shall be vented down to atmospheric pressure 
to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any ignition sources and there is 
ventilation available.

9. Charging procedures

• In addition to conventional charging procedures, 

the following requirements shall be followed.

 

- Ensure that contamination of different 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible to 

minimize the amount of refrigerant contained 
in them.

 

- Cylinders shall be kept upright.

 

- Ensure that the refrigeration system is earthed 

prior to charging the system with refrigerant.

 

- Label the system when charging is complete 

(if not already).

 

- Extreme care shall be taken not to over fi ll the 

refrigeration system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior to 

leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant.
To avoid fi re or explosion, dissipate static 
electricity during transfer by grounding and 
bonding containers and equipment before 
charging/discharging.

Safety precautions

ACXF55-1915_OL.ai   8   6/1/2018   1:19:57 PM

ACXF55-1915_OL.ai   8   6/1/2018   1:19:57 PM

Содержание CS-QN12UKY Series

Страница 1: ...tioner Thank you for purchasing Panasonic Air Conditioner Installation instructions attached Before operating the unit please read these operating instructions thoroughly and keep them for future reference C POWERFUL POWERFUL SLEEP SLEEP POWER POWER ACXF55 1915_OL ai 1 6 1 2018 1 19 49 PM ACXF55 1915_OL ai 1 6 1 2018 1 19 49 PM ...

Страница 2: ...ess SET or CLOCK again Operating the unit at 25 C or higher degrees may save energy Better comfort condition at 25 C or higher degrees ACXF55 1915_OL ai 2 6 1 2018 1 19 56 PM ACXF55 1915_OL ai 2 6 1 2018 1 19 56 PM ...

Страница 3: ...FAN Safety precautions 4 9 How to use 10 11 Cleaning instructions 12 Troubleshooting 13 Information 14 ACXF55 1915_OL ai 3 6 1 2018 1 19 57 PM ACXF55 1915_OL ai 3 6 1 2018 1 19 57 PM ...

Страница 4: ...liances etc Refer to Table A of Installation instructions table for Amin m Be aware that refrigerant may not contain an odour highly recommended to ensure suitable flammable refrigerant gas detectors are present operating and able to warn of a leak Please consult authorised dealer or specialist to clean the internal parts repair install remove and reinstall the unit Improper installation and handi...

Страница 5: ...R410A R22 models Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especially when replacing a refrigerant R22 model with a new refrigerant R32 model always replace the conventional piping and flare nuts with the R32 and R410A piping and flare nuts on the outdoor unit side For R32 and R410A the same flare nut ...

Страница 6: ...authorizes their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall b...

Страница 7: ...o any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded 2 8 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures Initial safety checks shall...

Страница 8: ... and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important that best practice is followed since flammability is a consideration The following procedure shall be adhered to remove refrigerant purge the circuit with inert gas evacuate purge again with inert gas open the circuit by cutting or brazin...

Страница 9: ...tied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 12 Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrig...

Страница 10: ...IDU fan running as per remote setting fan speed and air flow direction Indoor unit temperature display will show standard set temperature of 30 ºC and no set temperature is displayed on remote controller display SLEEP Room temperature 23 C above Below 23 C 25 C 22 C Standard setting temperature ACXF55 1915_OL ai 10 6 1 2018 1 19 58 PM ACXF55 1915_OL ai 10 6 1 2018 1 19 58 PM ...

Страница 11: ...u can restore the timer again by pressing or then press The nearest timer setting will be displayed and will activate in sequence When ON Timer is set the unit may start earlier up to 15 minutes before the actual set time in order to achieve the desired temperature on time Timer operation is based on the clock set in the remote control and repeats daily once set For clock setting please refer to Q...

Страница 12: ...Please remove the PM2 5 Filter before wash rinse the filter with water 12 ACXF55 1915_OL ai 12 6 1 2018 1 19 58 PM ACXF55 1915_OL ai 12 6 1 2018 1 19 58 PM ...

Страница 13: ...The unit stops and some alpha numeric codes appear on IDU display 13 ACXF55 1915_OL ai 13 6 1 2018 1 20 00 PM ACXF55 1915_OL ai 13 6 1 2018 1 20 00 PM ...

Страница 14: ...nic com in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should be handed over only to authorized recycler for disposal 3 4 5 6 Keep the product in isolated area after it becomes non functional un repairable so as to prevent its accidental breakage Provide in...

Страница 15: ...English Information Memo 15 ACXF55 1915_OL ai 15 6 1 2018 1 20 00 PM ACXF55 1915_OL ai 15 6 1 2018 1 20 00 PM ...

Страница 16: ...here is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows that a service personnel should be handling this equipment with reference to the Installation Instructions This symbol shows that there is information included in the Operation Instructions and or Installation Instructions ACXF55 1915_OL ai 16 6 1 2018 1 20 00 PM ACXF55 19...

Отзывы: