32
12.5.12. Hot Start Control
• Hot Start Control is to prevent cool air discharge into the room when heating operation start.
• When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
• Hot start is completed when indoor heat exchanger rises to 42°C or operation over 4 minutes.
12.5.13. Anti Cold Draft Control
12.5.14. Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
• Normal Deicing
Deice operations detection commences in Heating operation starts or 60 minutes after previous deice operation. If the outdoor
piping temperature drops to -4°C for 50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
• Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and after
compressor starts for 1 minutes, deicing starts.
• Deicing ends when
1. 12 minutes after deicing operation starts;
2. The outdoor piping temperature rises to 12°C.
• After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
Содержание CS-PW18GKE
Страница 8: ...8 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 10: ...10 5 2 Outdoor Unit ...
Страница 11: ...11 6 Refrigeration Cycle Diagram ...
Страница 12: ...12 7 Block Diagram ...
Страница 13: ...13 8 Wiring Connection Diagram ...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 2 Outdoor Unit ...
Страница 15: ...15 10 Printed Circuit Board 10 1 Indoor Unit ...
Страница 16: ...16 ...
Страница 17: ...17 10 2 Outdoor Unit ...
Страница 18: ...18 10 3 Indicator Receiver ...
Страница 21: ...21 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 33: ...33 a Normal Deicing Time Diagram b Overload Deicing Time Diagram ...
Страница 44: ...44 16 Technical Data 16 1 Thermostat Characteristics 16 1 1 CS PW18GKE ...
Страница 46: ...46 16 3 Operation Characteristics 16 3 1 CS PW18GKE CU PW18GKE ...
Страница 47: ...47 ...
Страница 48: ...48 ...
Страница 49: ...49 ...