DISPOSAL OF OUTDOOR UNIT DRAIN WATER

     • 

• 

• 

• 

If a drain elbow is used, the unit should be placed on a
stand which is taller than 3 cm.

     • 

• 

• 

• 

If the unit is used in an area where temperature falls below
0°C for 2 or 3 days in succession, it is recommended not to
use a drain elbow, for the drain water freezes and the fan
will not rotate.

CHECK THE DRAINAGE

     • 

• 

• 

• 

Open front panel and remove air filters.
(Drainage checking can be carried out without removing the
front grille.)

     • 

• 

• 

• 

Pour a glass of water into the drain tray-styrofoam.

     • 

• 

• 

• 

Ensure that water flows out from drain hose of the indoor
unit.

EVALUATION OF THE PERFORMANCE

     • 

• 

• 

• 

Operate the unit at cooling operation mode for fifteen
minutes or more.

     • 

• 

• 

• 

Measure the temperature of the intake and discharge air.

     • 

• 

• 

• 

Ensure the difference between the intake temperature and
the discharge is more than 8°C.

CHECK ITEMS

Is there any gas leakage at flare nut connections?

Has the heat insulation been carried out at flare nut
connection?

Is the connecting cable being fixed to terminal board firmly?

Is the connecting cable being clamped firmly?

Is the drainage OK?
(Refer to “Check the drainage” section)

Is the earth wire connection properly done?

Is the indoor unit properly hooked to the installation plate?

Is the power supply voltage complied with rated value?

Is there any abnormal sound?

Is the cooling operation normal?

Is the thermostat operation normal?

Is the remote control’s LCD operation normal?

Is the air purifying filter installed?

36

CS-PW9CKE / CU-PW9CKE / CS-PW12CKE / CU-PW12CKE

Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oy

www.ilmalämpöpumput.com

Содержание CS-PW12CKE

Страница 1: ...pying and distribution is a violation of law CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE 10 Servicing Information 48 11 Troubleshooting Guide 52 12 Technical Data 54 13 Exploded View 58 14 Replacement Parts List 59 15 Exploded View 60 16 Replacement Parts List 61 17 Electronic Circuit Diagram 62 18 Electronic Circuit Diagram Remote Control 65 Room Air Conditioner CONTENTS Page Page Order No GMAC0311...

Страница 2: ...Setting ON TIMER OFF TIMER Timer Operation Selection SET CANCEL Timer Operation Set Cancel ON Timer and OFF Timer setting and cancellation AIR SWING AUTO Automatic Vertical Airflow Direction Control MANUAL Vertical Airflow Direction Manual Control 5 stages of adjustment Heating Cooling Soft Dry Operation Temperature Setting 16o C to 30o C Automatic Operation Operation with 2o C higher than standar...

Страница 3: ...t the 5th second Used when test running or servicing Press continuously for 10s and above to omit or resume the remote control signal receiving sound Beep beep sound will be heard at the 10th second Operation Indication Lamps LED Green Lights up in operation blinks in Automatic Operation Mode judging Operation Mode Heating Cooling Soft Dry and Automatic Mode Time Delay Safety Control Restarting is...

Страница 4: ...n 4 way valve stays at Heating position for 5 minutes Overload Protection Control Outdoor fan stops when indoor heat exchanger temperature rises to 51 C and above and restarts when the indoor heat exchanger temperature drops to 49 C and below Compressor stop when indoor heat exchanger temperature reaches 65 C or above Heating Operation Only Deice Control To prevent frosting at outdoor heat exchang...

Страница 5: ...ng 3 90 Heating 3 70 EER COP W W Cooling 3 01 Heating 3 43 Starting Current A 16 5 Piping Connection Port Flare piping Inch Inch G half union 3 8 L half union 1 4 G 3 way valve 3 8 L 2 way valve 1 4 Piping Size Flare piping Inch Inch G gas side 3 8 L liquid side 1 4 G gas side 3 8 L liquid side 1 4 Drain Hose Inner diameter mm 12 Length m 0 6 Power Supply Cord Length Number of core wire m 1 9 3 co...

Страница 6: ... 2 Refrigerant Control Device Capillary Tube Refrigeration Oil c c SUNISO 4GDID or ATMOS M60 350 Refrigerant R410A g 870 Thermostat Electronic Control Protection Device Overload Protector Capillary Length mm Cooling720 heating 742 Circulation L min Cooling 6 0 heating 7 5 Inner dia mm Cooling 1 2 heating 1 3 Air Filter P P Honeycomb Refrigerant Circulation Control Device Capillary Compressor Capac...

Страница 7: ...ting 4 9 EER COP W W Cooling 2 83 Heating 3 21 Starting Current A 21 1 Piping Connection Port Flare piping Inch Inch G half union 1 2 L half union 1 4 G 3 way valve 1 2 L 2 way valve 1 4 Piping Size Flare piping Inch Inch G gas side 1 2 L liquid side 1 4 G gas side 1 2 L liquid side 1 4 Drain Hose Inner diameter mm 12 Length m 0 6 Power Supply Cord Length Number of core wire m 2 2 3 core wire 1 5m...

Страница 8: ...Refrigerant Control Device Capillary Tube Refrigeration Oil c c SUNISO 4GDID or ATMOS M60 350 Refrigerant R410A g 1000 Thermostat Electronic Control Protection Device Overload Protector Capillary Length mm Cooling 270 heating 590 Circulation L min Cooling 5 0 heating 8 2 Inner dia mm Cooling 1 2 heating 1 3 Air Filter P P Honeycomb Refrigerant Circulation Control Device Capillary Compressor Capaci...

Страница 9: ...3 Dimensions 9 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 10: ...10 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 11: ...4 Refrigeration Cycle Diagram 11 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 12: ...5 Block Diagram 12 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 13: ...6 Wiring Diagram 13 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 14: ...ng temperature is reached during cooling operation the compressor stops and it will not start for 3 minutes The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor ON temperature and OFF temperature When the compressor outdoor fan motor and indoor fan motor are simultaneously started the indoor fan motor will operate 1 6 second...

Страница 15: ...ed for 3 times the compressor will stop totally The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch When Automatic Fan Speed is selected at Remote Control during cooling operation Fan speed rotates in the range of Hi to Me Deodorizing Control 15 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseud...

Страница 16: ...Cooling Operation Time Diagram 16 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 17: ... the compressor stops it will not start for 3 minutes during Cooling operation Same as Starting Current Control for Cooling Mode operation Same as Anti Freezing Control for Cooling Mode operation For Soft Dry region 6 minutes waiting is valid during compressor stops Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation For Soft Dry region 6 minutes waiting is valid duri...

Страница 18: ...Diagram Quiet Operation Control For Dry region at Soft Dry Mode 18 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 19: ...f the temperature of the indoor heat exchanger rises to 51 C Outdoor Fan stops The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49 C If the indoor heat exchanger becomes 65 C or more the compressor will stop and restart automatically Time Delay Safety Control 4 minutes waiting If the compressor is operating continuously for 5 minutes or longer and temperature difference...

Страница 20: ...r heat exchanger reaches 30 C as diagram shown Hot Start is completed when indoor heat exchanger rises to 39 C or over 4 minutes 20 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 21: ...ration Fan speed rotates in the range of Me SLo according to the heat exchanger temperature If use Manual Fan Speed at above diagram will operate with setting Fan Speed 21 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 22: ...f the outdoor Fan OFF duration due to overload control is accumulated up to 60 minutes and after compressor starts for 1 minutes deicing starts Deicing ends when 1 12 minutes after deicing operation starts 2 TRS senses the outdoor piping temperature rises to 4 C TRS OPEN 3 Deicing will not end immediately as time delay Td is valid as shown below Once deicing operation starts it will not end for 60...

Страница 23: ...icing Time Diagram Overload Deicing Time Diagram 23 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 24: ...eating 23 C Above Below 23 C O O Soft Dry 20 C Soft Dry Not Applicable Judgement Judgement Heating 20 C Above Below 20 C O O Heating Cooling Judgement Not Applicable Judgement 25 C Heating Above 25 C 25 C below Automatic Set Temperature Refer 3 as below 3 Automatic Set Temperature For each operation set temperature will automatically set as shown below However it can be selected 2 C higher or 2 C ...

Страница 25: ...t time For Heating mode the operation will start 30 minutes before the set time For Automatic mode the indoor fan will operate at SLo speed for 25 seconds 30 minutes before the set time to detect the intake air temperature to determine the operation mode The operation indication lamp will blink at this time 7 7 Remote Control Signal Receiving Sound Long beep sound will be heard when Stopping the A...

Страница 26: ...t 2 Horizontal Airflow Direction The louver can be selected between 14 36 as shown above when pressing Manual Airflow Direction Selection Button The louver can be selected between 0 61 as shown above when pressing Manual Airflow Direction Selection Button 7 8 Airflow Direction Control Cooling Ion and Soft Dry Mode The left and right airflow direction louvers can be adjusted manually 26 CS PW9CKE C...

Страница 27: ... the set s weight If the strength is not enough or installation is not properly done the set will drop and cause injury 5 For electrical work follow the local national wiring standard regulation and this installation instruction An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fir...

Страница 28: ...case of emergency In some countries permanent connection of this room air conditioner to the power supply is prohibited 1 Power supply connection to the receptacle using a power plug Use an approved 15A 16A power plug with earth pin for the connection to the socket 2 Power supply connection to a circuit breaker for the permanent connection Use an approved 16A circuit breaker for the permanent conn...

Страница 29: ...t direct sunlight or rain be careful that heat radiation from the condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles which may cause a short circuit of the discharged air If piping length is over the common length additional refrig...

Страница 30: ...late hole with ø70 mm hole core drill Line according to the arrows marked on the lower left and right side of the installation plate The meeting point of the extended line is the centre of the hole Another method is by putting measuring tape at position as shown in the diagram above The hole centre is obtained by measuring the distance namely 150 mm and 125 mm for left and right hole respectively ...

Страница 31: ...g This can be used for left rear piping left bottom piping also 31 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 32: ...heavier cord Ensure the color of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage Secure the cable onto the control board with the holder clamper 32 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panason...

Страница 33: ... the ON OFF changed over of remote control receiving sound 8 3 OUTDOOR UNIT 8 3 1 SELECT THE BEST LOCATION Refer to Select the best location section 8 3 2 INSTALL THE OUTDOOR UNIT After selecting the best location start installation according to Indoor Outdoor Unit Installation Diagram 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut ø10 mm 2 When installing at roof pl...

Страница 34: ... the charging set and turn off the vacuum pump Make sure that the needle in the gauge does not move after approximately five minutes Note BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighten the service port caps of the 3 way valve at torque of 18 N m with a torque wrenc...

Страница 35: ...s leakage for the left piping 8 3 6 CONNECT THE CABLE TO THE OUTDOOR UNIT 1 Remove the control board cover from the unit by loosening the screw 2 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 PW9CKE PW12CKE x 1 5 mm2 flexible cord type designation 245 IEC 57 or heavier cord 3 Secure the cable onto the control board with the holder clamper 4 Atta...

Страница 36: ...intake and discharge air Ensure the difference between the intake temperature and the discharge is more than 8 C CHECK ITEMS Is there any gas leakage at flare nut connections Has the heat insulation been carried out at flare nut connection Is the connecting cable being fixed to terminal board firmly Is the connecting cable being clamped firmly Is the drainage OK Refer to Check the drainage section...

Страница 37: ...ce it collects in the lower area of the room It also generates toxic gas when it is directly exposed to a flame so it must be used in a well ventilated environment where it will not collect Table 1 Physical comparison of R410A and R22 R410A R22 Composition wt R32 R125 50 50 R22 100 Boiling point C 51 4 40 8 Vaporizing pressure 25 C 1 56 Mpa 15 9 kgf cm2 0 94 Mpa 9 6 kgf cm2 Saturated vapor density...

Страница 38: ...kage electric shock fire etc 9 2 TOOL FOR INSTALLING SERVICING REFRIGERANT PIPING 9 2 1 Necessary Tools In order to prevent an R410A AC from mistakenly being charged with any other refrigerant the diameter of the 3 way valve service port on the outdoor unit has been changed Also to increase its ability to withstand pressure the opposing dimensions have been changed for the refrigerant pipe flaring...

Страница 39: ...posite side x torque 17 mm x 18 N m 180 kgf cm 17 mm x 18 N m 180 kgf cm For 3 3 opposite side x torque 22 mm x 42 N m 420 kgf cm 22 mm x 42 N m 420 kgf cm For 1 2 opposite side x torque 24 mm x 55 N m 550 kgf cm 26 mm x 55 N m 550 kgf cm Because the pressure is higher for the R410A type the conventional type cannot be used Table 6 Difference between R410A and conventional high low pressure gauges...

Страница 40: ... there is no chlorine in the refrigerant The present R134a leak detector can be used but the detection sensitivity will be lower setting the sensitivity for R134a at 1 the level for R410A will drop to 0 6 For detecting small amounts of gas leakage use the electric gas leak detector for HFC refrigerant Detection sensitivity with R410A is about 23 g year Fig 4 Manifold gauge charging hose Fig 5 Vacu...

Страница 41: ... cylinders The R410A cylinders are labeled with the refrigerant name and the coating color of the cylinder protector is pink which is the color stipulated by ARI of the U S Cylinder equipped with a siphon tube are available to allow the cylinder to stand upright for liquid refrigerant charging 10 Charging orifice and packing for refrigerant cylinders The charging orifice must match the size of the...

Страница 42: ...or clearance adjustment etc to ensure the correct A dimension see Fig 10 Fig 10 Flaring dimensions 9 3 1 Piping Materials It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg 10m Do not used pipes that are crushed deformed or discolored especially the inside surface If these inferior pipes are used impurities may clog the expansion valves or ...

Страница 43: ...h and tighten to the specified torque The tightening torque for R410A is the same as the conventional torque value for R22 Be careful because if the torque is too weak it may lead to a gas leak If it is too strong it may split the flare nut or make it impossible to remove the flare nut Table 15 R410A tightening torque Nominal diameter in Outside diameter mm Tightening torque N m kgf cm Torque wren...

Страница 44: ...NG SERVICING 9 4 1 Inspecting Gas Leaks with a Vacuum Pump for New Installations Using New Refrigerant Piping 1 From the viewpoint of protecting the global environment please do not release refrigerant into the atmosphere a Connect the projecting side pin pushing side of the charging hose for the manifold gauge to the service port of the 3 way valve 1 b Fully open the handle Lo of the manifold gau...

Страница 45: ...R22 and R410A the design pressure for the equipment is 1 6 times different the wall thickness of the piping must comply with that shown in Table 10 but this is not easy to check Also even if the thickness is correct there may be flattened or bent portions midway through the piping due to sharp curves Buried sections of the piping also cannot be checked 2 Pipe cleaning A large quantity of refrigera...

Страница 46: ...f the liquid at a time about 150 g time as a guideline If the charging amount is insufficient from one operation wait about one minute then use the same procedure to do the liquid charging again Precaution Never use the gas side to allow a larger amount of liquid refrigerant to be charged while operating the unit 10 Close the charging valve and after charging the liquid refrigerant inside the char...

Страница 47: ...igerant circuit oxidizes due to overheating scale occurs and stays in the circuit as dust thus exerting a fatally adverse effect So make brazing at adequate brazing temperature and with minimum of heating area 3 Overheating Protection In order to prevent components near the brazed part from overheating damaged or quality deterioration due to flame or heat take adequate steps for protection such as...

Страница 48: ...sing CN ION connector Fig 4 Releasing CN STM connector Fig 4 Removing the Earth Wire screw Fig 4 Releasing the Intake Air Sensor Fig 4 Releasing the Piping Sensor Fig 4 Fig 1 Fig 2 Fig 3 Fig 4 10 Servicing Information Caution Pb free solder has a higher melting point than standard solder Typically the melting point is 50 70 F 30 40 C higher Please use a high temperature soldering iron In case of t...

Страница 49: ...ctor lead wire Ionizer Fig 5 Release the Fan Motor leadwire by pressing the hook at the center of the connector Fig 6 Remove the screw at the Cross Flow Fan Fig 7 REMINDER To reinstall the Fan Motor adjust the connector of the Fan Motor as shown in the Fig 7 Fig 5 Fig 6 Fig 7 49 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalve...

Страница 50: ... Push up the Evaporator and pull out the Cross Flow Fan from shaft By then Fan Motor can be taken out Fig 9 Fig 8 Fig 9 50 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 51: ...tions will blink and the remote control might not work If this happen gently press the RESET button on the remote control with a pin it will return to normal 51 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 52: ...of a compressor and a fan The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table to the right 11 Troubleshooting Guide 11 1 Refrigeration cycle system 52 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalä...

Страница 53: ...current during operation becomes approximately 20 lower than the normal value Insufficient compressing of a compressor The discharge tube of the compressor becomes abnormally hot normally 70 to 90 C The difference between high pressure and low pressure becomes almost zero Electric current reaches a high level abnormally and the value exceeds the limit of an ammeter In some cases a breaker turns of...

Страница 54: ...Data Thermostat characteristics CS PW9CKE CS PW12CKE 54 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 55: ...Temp C Indoor wet bulb temp 30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17 0 C 3 71 2 81 1 01 3 47 2 70 1 08 3 22 2 59 1 16 2 93 2 46 1 25 19 0 C 3 74 1 10 19 5 C 4 07 2 94 1 03 3 81 2 83 1 10 3 54 2 72 1 18 3 22 2 59 1 27 22 0 C 4 44 3 05 1 05 4 15 2 94 1 12 3 86 2 83 1 20 3 51 2 70 1 30 TC Total Cooling Capacity kW Indoor 27 C 19 C SHC Sensible Heat Capacity kW Outdoor 35 C 24 C IP Input...

Страница 56: ...erating characteristics CS PW9CKE CU PW9CKE 56 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 57: ...rating characteristics CS PW12CKE CU PW12CKE 57 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 58: ...se of parts disassembly and replacement The non numbered parts are not kept as standard service parts 58 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 59: ...8 SENSOR COMPLETE 1 CWA50C2064 19 CONTROL BOARD FRONT COVER 1 CWH131102 20 CONTROL BOARD TOP COVER 1 CWH131103 21 INDICATOR 1 CWE39C1091 22 INDICATOR PCB 1 CWA743279 23 INDICATOR HOLDER 1 CWD932169 24 REMOTE CONTROL COMPLETE 1 CWA75C2564 25 FRONT GRILLE COMPLETE 1 CWE11C3020 26 SCREW FRONT GRILLE 2 XTT4 14C 27 CAP FRONT GRILLE 2 CWH521025F 28 AIR FILTER 2 CWD001050 29 DRAIN HOSE 1 CWH851033 30 INS...

Страница 60: ...se of parts disassembly and replacement The non numbered parts are not kept as standard service parts 60 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 61: ...026 CWH151063 20 CONTROL BOARD 1 CWH102146 21 TERMINAL BOARD ASS Y 1 CWA28K1051 22 CAPACITOR COMPRESSOR 1 DS371306CPXA DS371256CPXA 23 HOLDER CAPACITOR 1 CWH30170 24 CAPACITOR FAN MOTOR 1 DS441205XPQC CWA31618 25 CABINET SIDE PLATE L 1 CWE041038A 26 CABINET SIDE PLATE R 1 CWE041056A 27 CABINET FRONT PLATE 1 CWE06C1041 28 WIRE NET 1 CWD04C1007 CWD04C1009 29 CABINET TOP PLATE 1 CWE031015A 30 PLATE C...

Страница 62: ...F G H 1 2 3 4 5 SCHEMATIC DIAGRAM 1 3 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE 62 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 63: ...ATIC DIAGRAM 2 3 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE 63 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 64: ...EMATIC DIAGRAM 3 3 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE 64 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Страница 65: ...ic Circuit Diagram Remote Control 65 CS PW9CKE CU PW9CKE CS PW12CKE CU PW12CKE Printed in CHINA Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla Jäähdytinpalvelu RefGroup Oy www ilmalämpöpumput com ...

Отзывы: