Panasonic CS-PC12MKF Скачать руководство пользователя страница 1

© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2011.
Unauthorized copying and distribution is a violation of law.

Order No. PHAAM1101068C3

Air Conditioner

Indoor Unit 

Outdoor Unit

CS-PC12MKF CU-PC12MKF
CS-PC18MKF CU-PC18MKF
CS-PC24MKF CU-PC24MKF

TABLE OF CONTENTS

PAGE

PAGE

1 Safety Precautions

-----------------------------------------------

3

2 Specifications

-----------------------------------------------------

5

3 Features

-------------------------------------------------------------

9

4 Location of Controls and Components

------------------

10

4.1. Indoor Unit--------------------------------------------------10
4.2. Outdoor Unit -----------------------------------------------10
4.3. Remote Control -------------------------------------------10

5 Dimensions

-------------------------------------------------------

11

5.1. Indoor Unit ------------------------------------------------- 11
5.2. Outdoor Unit----------------------------------------------- 13

6 Refrigeration Cycle Diagram

--------------------------------

15

7 Block Diagram

---------------------------------------------------

16

7.1. CS-PC12MKF--------------------------------------------- 16
7.2. CS-PC18MKF  CS-PC24MKF ------------------------ 17

Содержание CS-PC12MKF

Страница 1: ...12MKF CS PC18MKF CU PC18MKF CS PC24MKF CU PC24MKF TABLE OF CONTENTS PAGE PAGE 1 Safety Precautions 3 2 Specifications 5 3 Features 9 4 Location of Controls and Components 10 4 1 Indoor Unit 10 4 2 Outdoor Unit 10 4 3 Remote Control 10 5 Dimensions 11 5 1 Indoor Unit 11 5 2 Outdoor Unit 13 6 Refrigeration Cycle Diagram 15 7 Block Diagram 16 7 1 CS PC12MKF 16 7 2 CS PC18MKF CS PC24MKF 17 ...

Страница 2: ...2 7 Horizontal Airflow Direction Control 43 12 8 Timer Control 43 12 9 Random Auto Restart Control 44 12 10 Remote Control Signal Receiving Sound 44 12 11 ECONAVI AUTO COMFORT Operation 45 13 Protection Control 49 13 1 Restart Control Time Delay Safety Control 49 13 2 7 Minutes Time Save Control 49 13 3 60 Seconds Forced Operation 49 13 4 Starting current Control 49 13 5 Freeze Preventive Control ...

Страница 3: ...it capacity is not enough or defect found in electrical work it will cause electrical shock or fire 9 This equipment is strongly recommended to install with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 10 Use the specified cable 1 5 mm2 and connect tightly for indoor outdoor co...

Страница 4: ...0 F 600 C 7 Power supply connection to the air conditioner Connect the power supply cord of the air conditioner to the mains using one of the following methods Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency In some countries permanent connection of this room air conditioner to the power supply is prohibited i Power supply conne...

Страница 5: ...der rolling piston type Motor Type Induction 2 poles Output Power W 1 0k Indoor Fan Type Cross flow Fan Material ASG20K1 Motor Type DC Motor 4 poles Input Power W 36 37 Output Power W 24 Speed Lo rpm 810 Me rpm 940 Hi rpm 1120 SHi rpm Outdoor Fan Type Propeller Fan Material PP Resin Motor Type Induction 6 poles Input Power W 80 3 89 1 Output Power W 45 Speed Hi rpm 875 905 Moisture Removal L h Pt ...

Страница 6: ...ft 7 5 24 6 Length range min max m ft 3 15 9 8 49 2 I D O D Height different m ft 5 16 4 Additional Gas Amount g m oz ft 10 0 1 Length for Additional Gas m ft 7 5 24 6 Drain Hose Inner Diameter mm 16 Length mm 550 Indoor Heat Exchanger Fin Material Aluminium Pre Coat Fin Type Slit Fin Row Stage FPI 2 15 21 Size W H L mm 610 315 25 Outdoor Heat Exchanger Fin Material Aluminium Blue Coat Fin Type Co...

Страница 7: ...door Fan Type Cross flow Fan Cross flow Fan Material ASG20K1 ASG20K1 Motor Type DC Motor 8 poles DC Motor 8 poles Input Power W 94 8 94 8 94 8 94 8 Output Power W 40 40 Speed Lo rpm 1120 1120 1150 1150 Me rpm 1200 1200 1240 1240 Hi rpm 1280 1280 1390 1390 SHi rpm Outdoor Fan Type Propeller Fan Propeller Fan Material PP Resin PP Resin Motor Type Induction 6 poles Induction 6 poles Input Power W 87 ...

Страница 8: ... different m ft 20 65 6 20 65 6 Additional Gas Amount g m oz ft 20 0 2 30 0 3 Length for Additional Gas m ft 7 5 24 6 7 5 24 6 Drain Hose Inner Diameter mm 14 14 Length mm 550 550 Indoor Heat Exchanger Fin Material Aluminium Pre Coat Aluminium Pre Coat Fin Type Slit Fin Slit Fin Row Stage FPI 2 15 21 2 15 21 Size W H L mm 810 315 25 4 810 315 25 4 Outdoor Heat Exchanger Fin Material Aluminium Blue...

Страница 9: ...uality Improvement Random auto restart after power failure for safety restart operation Gas leakage protection Prevent compressor reverse cycle Overload protector to protect Compressor Noise prevention during soft dry operation Blue Coated Condenser for high resistance to corrosion Operation Improvement 24 hour timer setting ...

Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...

Страница 11: ...11 5 Dimensions 5 1 Indoor Unit 5 1 1 CS PC12MKF ...

Страница 12: ...12 5 1 2 CS PC18MKF CS PC24MKF ...

Страница 13: ...13 5 2 Outdoor Unit 5 2 1 CU PC12MKF CU PC18MKF ...

Страница 14: ...14 5 2 2 CU PC24MKF ...

Страница 15: ...15 6 Refrigeration Cycle Diagram ...

Страница 16: ...16 7 Block Diagram 7 1 CS PC12MKF ...

Страница 17: ...17 7 2 CS PC18MKF CS PC24MKF ...

Страница 18: ...essor Windings Note Resistance at 20 C of ambient temperature Resistance of Outdoor Fan Motor Windings Note Resistance at 25 C of ambient temperature MODEL CS PC12MKF CONNECTION CWA921434 BLUE YELLOW 351 3 Ω YELLOW RED 343 9 Ω MODEL CU PC12MKF CONNECTION 2KS210D5AA06 C R 2 279 Ω C S 3 526 Ω MODEL CU PC12MKF CONNECTION CWA951676 BLUE YELLOW 198 Ω YELLOW RED 293 Ω ...

Страница 19: ...gs Note Resistance at 25 C of ambient temperature Resistance of Compressor Windings Note Resistance at 20 C of ambient temperature MODEL CU PC18MKF CONNECTION CWA951676 BLUE YELLOW 198 Ω YELLOW RED 293 Ω MODEL CU PC18MKF CONNECTION 2KS324D5AB06 C R 1 642 Ω C S 4 316 Ω ...

Страница 20: ...Resistance at 25 C of ambient temperature Resistance of Compressor Windings Note Resistance at 20 C of ambient temperature MODEL CU PC24MKF CONNECTION CWA951689 BLUE YELLOW 64 Ω YELLOW ORANGE 90 Ω YELLOW RED 55 Ω MODEL CU PC24MKF CONNECTION 2JS438D3CB04 C R 1 121 Ω C S 2 535 Ω ...

Страница 21: ...21 9 Electronic Circuit Diagram 9 1 CS PC12MKF CU PC12MKF ...

Страница 22: ...22 9 2 CS PC18MKF CU PC18MKF ...

Страница 23: ...23 9 3 CS PC24MKF CU PC24MKF ...

Страница 24: ...24 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS PC12MKF ...

Страница 25: ...25 10 1 1 2 CS PC18MKF CS PC24MKF ...

Страница 26: ...26 10 2 Indicator Printed Circuit Board 10 3 Receiver Printed Circuit Board 10 4 Comparator Printed Circuit Board 10 5 Human Activity Sensor Printed Circuit Board ...

Страница 27: ...nded installation height for indoor unit shall be at least 2 5 m 11 1 2 Outdoor Unit If an awning is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not plac...

Страница 28: ...chor bolts Always mount the installation plate horizontally by aligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with ø70 mm hole core drill Putting measuring tape at position as shown in the diagram above The hole center is obtained by measuring the distance namely 128 mm for left and right hole respectively Another method is intersection point of...

Страница 29: ...1 2 3 Indoor Unit Installation 11 2 3 1 For the right rear piping 11 2 3 2 For the right and right bottom piping 11 2 3 3 For the embedded piping This can be used for left rear piping and botom piping also ...

Страница 30: ...e if the existing wire from concealed wiring or otherwise is too short In unavoidable case joining of power supply cord between isolating devices and terminal board of air conditioner shall be done by using approved socket and plug rated 15 16A 1 5HP or 16A 2 0HP or 20A 2 5HP Wiring work to both socket and plug must follow to national wiring standard 4 Bind all the power supply cord lead wire with...

Страница 31: ...lose grille door by tighten with screw and close the front panel Note Isolating Devices Disconnecting means should have minimum 3 0mm contact gap Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively Earth wire shall be Yellow Green Y G in colour and longer than the other AC wires as shown in the figure for the electrical safety in case of the sl...

Страница 32: ...32 11 2 5 Wire Stripping And Connecting Requirement ...

Страница 33: ...g Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with torque wrench in specified torque as stated in the table 11 3 2 2 Connecting The Piping To Outdoor Decide piping length and then cut by using pipe cutter Remove burrs from cut edge Make flare after inserting the flare nut locate at valve onto the copper pipe Align center of piping to...

Страница 34: ... the charging set and turn off the vacuum pump Make sure that the needle in the gauge does not move after approximately five minutes Note BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighten the service port caps of the 3 way valve at a torque of 18 N m with a torque wrenc...

Страница 35: ...e Outdoor Unit 1 Remove the control board cover from the unit by loosening the screw 2 Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 1 5 mm2 1 5HP 3 2 5 mm2 2 0 2 5HP flexible cord type designation 245 IEC 57 or heavier cord Do not use joint connection cable Replace the wire if the existing wire from concealed wiring or otherwise is too short 3 ...

Страница 36: ...ecting piping is in the room where dew may form please increase the insulation by using POLY E FOAM with thickness 6mm or above 11 3 7 Cutting And Flaring The Piping 1 Please cut using pipe cutter and then remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping end down to avoid the metal powder entering the pipe 3 Please make flare aft...

Страница 37: ...om temperature reaches the setting temperature set on the remote control The remote control setting temperature which takes the reading of intake air temperature sensor can be adjusted from 16 C to 30 C During cooling operation the compressor will stop running and restart as shown in figure below 12 1 1 Cooling Operation Time Diagram For PC12MKF ...

Страница 38: ...ing temperature on the remote control When operation begins Soft Dry will be switched ON for a maximum 10 minutes then Soft Dry operation will be turned OFF for a minimum 6 minutes After that the Soft Dry operation will be ON and OFF based on the setting temperature as shown in figure below However after 3 minutes of compressor off during Soft Dry OFF within 6 minutes Soft Dry restart control the ...

Страница 39: ...39 12 2 1 Soft Dry Operation Time Diagram For PC12MKF 12 2 2 Soft Dry Operation Time Diagram For PC18MKF PC24MKF ...

Страница 40: ... determined operation mode until it is switched off using remote control with the setting temperature as shown in table below The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as shown in below table by pressing on the temperature up or temperature down button at remote control The operation mode judging temperature and stand...

Страница 41: ...oor fan will be switched to Hi fan speed from Lo after 70 seconds from the start of compressor This cause the room temperature to achieve the setting temperature quickly 4 During compressor stop indoor fan will operate at Lo for the beginning 3 minutes to prevent higher volume of refrigerant in liquid form returning to the compressor 5 After the compressor at turn off condition for 3 minutes indoo...

Страница 42: ...speed settings Lo Me Hi 12 4 4 Indoor Fan Motor RPM Abnormal Control Immediate after the fan motor is started rpm abnormal control is performed once every second During fan motor on if fan motor feedback 2550 or 50 rpm continuously for 10 seconds the fan motor error counter increased fan motor is then stopped and restarted If the fan motor error counter increased to 7 the air conditioner will stop...

Страница 43: ...rizontal Airflow Direction Control The horizontal airflow direction louvers can be adjusted manually by hand 12 8 Timer Control 12 8 1 ON Timer When the ON Timer is set by using the remote control the unit will start to operate slightly before the set time so that the room will reach nearly to the set temperature by the set time For Cooling and Soft Dry operation the operation will start 15 minute...

Страница 44: ...ach unit to operate will be decided randomly using 4 parameters intake air temperature setting temperature fan speed and air swing louver position This Random Auto Restart Control is not available when Timer is set This control can be omitted by open the circuit of JX02 refer to printed circuit board indoor unit 12 10 Remote Control Signal Receiving Sound Short beep sound will be heard when turn O...

Страница 45: ... OFF After ECONAVI AUTO COMFORT Sensor unit power is OFF for 5 seconds Retry the ECONAVI AUTO COMFORT operation When Abnormal counter reach 4 counts ECONAVI AUTO COMFORT sensor abnormality is confirmed Abnormal counter is cleared when sensor power ON and maintain normal for 120 seconds and above or Clear Anormal counter by power reset Save ECONAVI AUTO COMFORT Sensor Abnormality no Timer LED blink...

Страница 46: ...rizontal vane will set to Auto Swing When Hi activity judge Fan speed change to Hi Fan and ECONAVI AUTO COMFORT LED ON When Lo activity judge Fan speed change to Lo Fan and ECONAVI AUTO COMFORT LED OFF No setting temperature adjustment During ECONAVI AUTO COMFORT operation the internal setting temperature and fan speed are adjusted in order to provide comfort and energy saving ECONAVI Start condit...

Страница 47: ...failure Timer Operation When unit is turn on by ON Timer and ECONAVI AUTO COMFORT operation is ON during previous operation before OFF ECONAVI AUTO COMFORT operation will not be ON automatically When unit is turn on by ON Timer and ECONAVI AUTO COMFORT operation is OFF during previous operation before OFF ECONAVI AUTO COMFORT operation will not be ON automatically Other Information ECONAVI AUTO CO...

Страница 48: ...ditions are formed Operation stops Timer Cancel button pressed When ECONAVI AUTO COMFORT sensor check mode signal is not received for more than 30 seconds 3 Control content During ECONAVI AUTO COMFORT mode ON when check signal is received if 1 or 2 is detected ECONAVI AUTO COMFORT LED start blinking ECONAVI AUTO COMFORT sensor operation stops but the unit operates as normal and ECONAVI AUTO COMFOR...

Страница 49: ...ill not stop within 60 seconds in a normal operation although the intake air temperature has reached the thermo off temperature However force stop by pressing the OFF ON operation button at the remote control is permitted The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return back to the outdoor unit 13 4 Starting current...

Страница 50: ... one of the following condition happen Unit is OFF by remote control or AUTO OFF ON button Indoor intake temperature indoor piping temperature 5 C for 1 minute or more Operation mode change The unit could be ON by pressing OFF ON button at remote control but the TIMER LED will continue blinking TIMER LED blinking will reset if Indoor intake temperature indoor piping temperature 5 C for 1 minute or...

Страница 51: ... remote control receiving sound Short beep Turn ON remote control receiving sound Long beep Turn OFF remote control receiving sound After Auto OFF ON Button is pressed the 20 seconds counter for Remote Control Receiving Sound OFF ON Mode is restarted ii Remote Control Number switch There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor unit The indoo...

Страница 52: ...button until a beep sound is heard as confirmation of transmission code change 14 2 2 RESET To clear and restore the remote control setting to factory default Press once to clear the memory 14 2 3 TIMER To change indoor unit indicator s LED intensity Press continuously for 5 seconds 14 2 4 TIMER To change remote control display from Degree Celsius C to Degree Fahrenheit F Press continuously for 10...

Страница 53: ...trical problems before inspecting the refrigeration cycle Such problems include insufficient insulation problem with the power source malfunction of a compressor and a fan The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table to the right ...

Страница 54: ...logged capillary tube or Strainer Short circuit in the indoor unit Heat radiation deficiency of the outdoor unit Inefficient compression Nature of fault Symptom Electric current during operation becomes approximately 20 lower than the normal value Insufficient compressing of a compressor The discharge tube of the compressor becomes abnormally hot normally 70 to 90 C The difference between high pre...

Страница 55: ...emoval Procedures 16 1 1 1 To remove Front Grille 16 1 1 2 To remove Electronic Controller WARNING High Voltage is generated in the electrical parts area by the capacitor Ensure that the capacitor has discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks ...

Страница 56: ...56 16 1 1 3 To remove Discharge Grille ...

Страница 57: ...57 16 1 1 4 To remove Control Board 16 1 1 5 To remove Cross Flow Fan and Indoor Fan Motor ...

Страница 58: ...58 ...

Страница 59: ...59 16 2 CS PC18MKF CS PC24MKF 16 2 1 Indoor Electronic Controllers and Control Board Removal Procedures 16 2 1 1 To remove Front Grille 16 2 1 2 To remove Electronic Controller ...

Страница 60: ...60 16 2 1 3 To remove Discharge Grille ...

Страница 61: ...61 16 2 1 4 To remove Control Board 16 2 1 5 To remove Cross Flow Fan and Indoor Fan Motor ...

Страница 62: ...62 ...

Страница 63: ...63 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...

Страница 64: ...64 17 2 Operation Characteristics 17 2 1 CS PC12MKF CU PC12MKF Cooling Characteristics Condition Room temperature 27 C DBT 19 C WBT Cooling condition At High fan Piping length 7 5m ...

Страница 65: ...65 Piping Length Characteristics Condition Room temperature 27 C DBT 19 C WBT Cooling condition At High fan Piping length 7 5m ...

Страница 66: ...66 17 2 2 CS PC18MKF CU PC18MKF Cooling Characteristics Condition Room temperature 27 C DBT 19 C WBT Cooling condition At High fan Piping length 5 0m ...

Страница 67: ...67 Piping Length Characteristic Condition Room temperature 27 C DBT 19 C WBT Cooling condition At High fan Piping length 5 0m ...

Страница 68: ...68 17 2 3 CS PC24MKF CU PC24MKF Cooling Characteristics Condition Room temperature 27 C DBT 19 C WBT Cooling condition At High fan Piping length 5 0m ...

Страница 69: ...69 Piping Length Characteristic Condition Room temperature 27 C DBT 19 C WBT Cooling condition At High fan Piping length 5 0m ...

Страница 70: ...7 CS PC18MKF CU PC18MKF Hi Me Lo Indoor Fan Speed rpm 1280 1200 1120 Air Flow m3 min 16 90 15 60 14 30 ft3 m 597 551 505 Outdoor Fan Speed rpm 875 905 Air Flow m3 min 31 6 32 6 ft3 m 1120 1150 CS PC24MKF CU PC24MKF Hi Me Lo Indoor Fan Speed rpm 1390 1240 1150 Air Flow m3 min 18 10 15 70 14 30 ft3 m 639 554 505 Outdoor Fan Speed rpm 860 890 440 500 Air Flow m3 min 55 0 57 0 26 6 30 3 ft3 m 1940 201...

Страница 71: ...71 17 4 Cooling Capacity Performance Data CS CU PC12MKF 220V ...

Страница 72: ...72 CS CU PC12MKF 240V CS CU PC18MKF 220V ...

Страница 73: ...73 CS CU PC18MKF 240V ...

Страница 74: ...74 CS CU PC24MKF 220V ...

Страница 75: ...75 CS CU PC24MKF 240V ...

Страница 76: ...76 17 5 Sound Data CS PC18MKF ...

Страница 77: ...77 CS PC24MKF ...

Страница 78: ...d View and Replacement Parts List 18 1 Indoor Unit 18 1 1 CS PC12MKF Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 79: ...CTRONIC CONTROLLER MAIN 1 CWA73C5191 O 24 ELECTRONIC CONTROLLER INDICATOR 1 CWA746317 O 25 ELECTRONIC CONTROLLER RECEIVER 1 CWA745288 O 26 INDICATOR HOLDER 1 CWD933021 27 SENSOR COMPLETE 1 CWA50C2401 O 28 CONTROL BOARD FRONT COVER 1 CWH13C1183 29 CONTROL BOARD TOP COVER 1 CWH131350 31 REMOTE CONTROL COMPLETE 1 CWA75C3712 O 32 FRONT GRILLE COMPLETE 1 CWE11C4794 O 33 INTAKE GRILLE COMPLETE 1 CWE22C1...

Страница 80: ...80 18 1 2 CS PC18MKF CS PC24MKF Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 81: ... 2 CWH621103 29 VERTICAL VANE 13 CWE241355 30 CONNECTING BAR 1 CWE261230 31 CONNECTING BAR 1 CWE261231 32 CONNECTING BAR 1 CWE261232 33 CONNECTING BAR 1 CWE261233 34 CONNECTING BAR 1 CWE261234 37 A S MOTOR DC SINGLE 12V 300OHM 1 CWA981241 O 39 CAP DRAIN TRAY 1 CWH521096 40 HORIZONTAL VANE 1 CWE24C1295 41 BACK COVER CHASSIS 1 CWD933031 42 REMOTE CONTROL COMPLETE 1 CWA75C3712 O 43 FRONT GRILLE COMPL...

Страница 82: ...82 18 2 Outdoor Unit 18 2 1 CU PC12MKF Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 83: ...COMPRESSOR MOUNT 3 CWH561049 12 CONDENSER 1 CWB32C2821 13 CAPILLARY TUBE ASS Y 1 CWB15K1165 14 STRAINER 1 CWB111011 15 HOLDER COUPLING 1 CWH351023 16 2 WAY VALVE LIQUID 1 CWB021362 O 17 3 WAY VALVE GAS 1 CWB011482 O 20 TERMINAL COVER 1 CWH171012 21 NUT TERMINAL COVER 1 CWH7080300J 22 SOUND PROOF BOARD 1 CWH151023 23 TERMINAL BOARD ASS Y 1 CWA28K1064J 24 CAPACITOR COM 1 F0GAH356A001 O 25 HOLDER CAP...

Страница 84: ...84 18 2 2 CU PC18MKF Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 85: ...NUT COMPRESSOR MOUNT 3 CWH561049 13 CONDENSER 1 CWB32C3166 14 CAPILLARY TUBE ASS Y 1 CWB15K1365 16 HOLDER COUPLING 1 CWH351046 17 2 WAY VALVE LIQUID 1 CWB021362 O 18 3 WAY VALVE GAS 1 CWB011482 O 19 TERMINAL COVER 1 CWH171012 20 NUT TERMINAL COVER 1 CWH7080300J 21 SOUND PROOF BOARD 1 CWH151023 22 TERMINAL BOARD ASS Y 1 CWA28K1064J 23 CAPACITOR COM 1 DS441456CPND O 24 HOLDER CAPACITOR 1 CWH301054 2...

Страница 86: ...86 18 2 3 CU PC24MKF Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 87: ...UT COMPRESSOR MOUNT 3 CWH561049 13 CONDENSER 1 CWB32C3108 14 CAPILLARY TUBE ASS Y 1 CWB15K1366 15 STRAINER 1 CWB11025 16 HOLDER COUPLING 1 CWH351036 17 2 WAY VALVE LIQUID 1 CWB021175 O 18 3 WAY VALVE GAS 1 CWB011484 O 21 TERMINAL COVER 1 CWH171012 22 NUT TERMINAL COVER 1 CWH7080300J 23 SOUND PROOF BOARD 1 CWH151237 24 TERMINAL BOARD ASS Y 1 CWA28K1064J 26 CAPACITOR COM 1 DS441456CPNC O 27 HOLDER C...