15.4.27 F97 (Compressor Overheating)
Malfunction Decision Conditions
•
During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the
compressor tank temperature sensor.
Malfunction Caused
•
Refrigerant shortage (refrigerant leakage).
•
2/3 way valve closed.
•
Detection error due to faulty compressor tank temperature sensor.
Troubleshooting
2/3 way valve closed?
When F97 indication happens
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Check the compressor tank temperature
sensor
●
Open the 2/3 way valve
YES
NO
Does it conform to the sensor
characteristic chart?
●
Replace the compressor tank
temperature sensor
NO
YES
Check for gas leakage
Oil oozing out from the 2/3 way valve?
●
Repair the pipe flare or union nuts
Reclaim and recharge refrigerant
●
Replace the capillary tube or dryer
Capillary tube or dryer clogged?
YES
NO
YES
Charge a specified amount of fresh
refrigerant
Refrigerant cycle abnormality error again?
NO
NO
YES
●
Replace outdoor unit PCB
●
Replace outdoor unit compressor
●
Procedure complete
Содержание CS-NE12PKE
Страница 22: ...22 10 1 3 Receiver Printed Circuit Board CN RCV 10 1 4 High Voltage Power Supply Printed Circuit Board ...
Страница 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 89: ...89 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Страница 90: ...90 16 1 1 4 To remove control board Figure 6 16 1 1 5 To remove cross flow fan and indoor fan motor Figure 7 ...
Страница 91: ...91 Figure 8 Figure 9 ...
Страница 92: ...92 Figure 10 ...