2. Hot Start
·
At the start of heating operation, the indoor fan stops and Comp. Operation Frequency Command Number at Fh max. This
is to heat up the indoor heat exchanger in order to avoid cold air discharged.
·
Hot Start ends when
a. Indoor heat exchanger temperature reaches over 15°C
or
b. 4 minutes after heating operation starts
·
After Hot Start operation, Comp. Operation Frequency Command Number at Fh max for 2 minutes.
8.6.3. Standby Control
1. The purpose of Standby Control is to warm up the compressor when outdoor temperature is low.
the standby control will be activated when all of the followings occur.
·
Unit is not operating.
·
Compressor temperature is below 7°C.
2. When the standby control is activated, low electricity will be supplied to compressor for 3 minutes and stops for 7 minutes.
This condition is repeated until standby control is cancelled.It will consume about 35W of electric power.
3. Standby control will be cancelled when one of the following conditions occurs.
·
Unit starts operation.
·
Compressor temperature is over 9°C.
4. When the unit is switched on by the remote control, the compressor operates at frequency as shown in below:-
5. The standby control can be cancelled by cutting off the jumper wire on the outdoor electronic controller.
8.6.4. Deice Operation
Deice operation occurs when the deice operation starting signal is generated. This happens when one of the following conditions
occurs. However, the first deice operation will begin 1 hour after start of heating operation.
Note:
The above 4 cases are under compressor operating condition.
23
CS-MVG103KE / CU-MVG153KE
Содержание CS-MVG103KE
Страница 3: ...2 Functions 2 1 REMOTE CONTROL 3 CS MVG103KE CU MVG153KE ...
Страница 4: ...2 2 INDOOR UNIT 4 CS MVG103KE CU MVG153KE ...
Страница 5: ...5 CS MVG103KE CU MVG153KE ...
Страница 6: ...2 3 OUTDOOR UNIT 6 CS MVG103KE CU MVG153KE ...
Страница 9: ...4 Dimensions 4 1 CS MVG103KE INDOOR UNIT 9 CS MVG103KE CU MVG153KE ...
Страница 10: ...4 2 CU MVG153KE OUTDOOR UNIT 10 CS MVG103KE CU MVG153KE ...
Страница 15: ...8 Operation Details FUNCTIONS 8 1 SIMULTANEOUS OPERATION CONTROL 15 CS MVG103KE CU MVG153KE ...
Страница 53: ...11 2 3 PIPING LENGTH 53 CS MVG103KE CU MVG153KE ...
Страница 54: ...11 3 INDOOR OUTDOOR UNIT INSTALLATION DIAGRAM 54 CS MVG103KE CU MVG153KE ...
Страница 62: ...12 4 2 Removal of Electronic Controller Procedure Fig5 Fig6 Fig7 Fig8 Fig9 Fig10 62 CS MVG103KE CU MVG153KE ...
Страница 63: ...12 4 3 Indoor Fan Motor Removal Procedure Fig11 Fig12 Fig13 Fig14 Fig15 63 CS MVG103KE CU MVG153KE ...
Страница 69: ...13 Technical Data 13 1 OPERATION CHARACTERISTICS 69 CS MVG103KE CU MVG153KE ...
Страница 70: ...70 CS MVG103KE CU MVG153KE ...
Страница 78: ...CS MVG103KE Main PCB Back Side Receiver PCB 78 CS MVG103KE CU MVG153KE ...
Страница 79: ...15 2 OUTDOOR UNIT MAIN PCB CU MVG153KE Main PCB Front Side CS MVG103KE CU MVG153KE 79 ...
Страница 80: ...CU MVG153KE Main PCB Back Side CS MVG103KE CU MVG153KE 80 ...
Страница 82: ...16 Exploded View Replacement Parts List 16 1 CS MVG103KE 16 1 1 Exploded View 82 CS MVG103KE CU MVG153KE ...
Страница 84: ...16 2 CU MVG153KE 16 2 1 Exploded View 84 CS MVG103KE CU MVG153KE ...