30
12.3 Powerful Mode Operation
When the powerful mode is selected, the internal setting temperature will shift higher up to +10.8°F (for Heating) or
lower up to 7.2°F (for Cooling/Soft Dry) than remote control setting temperature for 20 minutes to achieve the setting
temperature quickly.
12.4 Timer Control
12.4.1 ON
Timer
Control
ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is
to provide a comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
Indoor intake air
temperature (ºF)
Indoor intake air
temperature (ºF)
(ºF)
Outdoor air
temperature (ºF)
Outdoor air
temperature (ºF)
86
77
59
41
5 min
Cooling/Soft Dry
Heating
86
95
10 min
15 min
(ºF)
41
32
35 min
30 min
25 min
12.4.2 OFF Timer Control
OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
12.5 Auto Restart Control
1 When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
2 This type of control is not applicable during ON/OFF Timer setting.
3 This control can be omitted by open the circuit of JP10 at indoor unit printed board.
12.6 Indication Panel
LED OFF/ON
Operation
Color Green
Light ON
Operation ON
Light OFF
Operation OFF
Note:
If OFF/ON operation LED is OFF and OFF indicator does not shown on remote control display, there is an
abnormality operation occurs.
Содержание CS-ME5SD3UA
Страница 1: ......
Страница 3: ......
Страница 4: ......
Страница 10: ......
Страница 11: ......
Страница 13: ...13 7 Block Diagram 7 1 Indoor Unit FUSE FM DM SC Indoor Unit 1 2 3 ...
Страница 15: ......
Страница 16: ......
Страница 17: ......
Страница 19: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 31: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 41: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 49: ......
Страница 50: ......
Страница 51: ......
Страница 52: ......
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......