Symbol
Diagnosis
Diagnosis method
H30
Outdoor discharge
pipe temp. sensor
Disconnected discharge sensor
•
When the condensation temperature is higher than the discharge tempe (plus) 6°C, a sensor
disconnection is detected, operation stops, and the error occurs (the timer lamp blinks).
<Diagnosis checkpoint>
1.
This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circuit (more than 500k ohms) or short-circuit (less than 0.5k ohms) is not
found, defective contact of the connector or a defective control P.C. Board is possible.
H32
Outdoor heat
exchanger temp.
sensor 2
(discharge pipe temp.)
This error occurs when a temperature of under approximately -60°C or over approximately 110°C has been
detected continuously for 2 to 5 seconds by the outlet temperature sensor of the heat exchanger.
<Diagnosis checkpoint>
1.
This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circuit (more than 500k ohms) or short-circuit (less than 0.5k ohms) is not
found, defective contact of the connector or a defective control P.C. Board is possible.
H34
Outdoor heatsink
temp. sensor
This error occurs when a temperature of under -43°C or above 80°C has been detected by the outdoor unit
radiator fin sensor continuously for 2 seconds.
<Diagnosis checkpoint>
1.
This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circuit (more than 500k ohms) or short-circuit (less than 0.5k ohms) is not
found, defective contact of the connector or a defective control P.C. Board is possible.
H35
Drainage or drain
pump abnormality
This error occurs if the float switch is open three times for 10 seconds or more during a twenty-minute period.
<Diagnosis checkpoint>
1.
Drain blockage
2.
Check the conductivity of float switch.
3.
Check that the resistance of the drain motor is about 200 ohms.
H36
Outdoor gas pipe
temp. sensor
This error occurs when a temperature of under -45°C or above approximately 149°C has been detected by the
outdoor unit gas side pipe temperature sensor continuously for 2 to 5 seconds.
<Diagnosis checkpoint>
1.
This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circuit (more than 500k ohms) or short-circuit (less than 0.5k ohms) is not
found, defective contact of the connector or a defective control P.C. Board is possible.
H37
Outdoor liquid pipe
temp. sensor
This error occurs when a temperature of under -45°C or above 149°C has been detected by the outdoor unit liquid
side pipe temperature sensor continuously for 2 seconds.
<Diagnosis checkpoint>
1.
This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circuit (more than 500k ohms) or short-circuit (less than 0.5k ohms) is not
found, defective contact of the connector or a defective control P.C. Board is possible.
H39
Abnormal indoor
operating unit or
standby units
This error occurs in rooms other than one in which indoor freezing error has occurred when the pipes have been
connected incorrectly, when an outdoor expansion valve is defective or when an expansion valve connector has
become disconnected.
H97
Outdoor fan motor
mechanism lock
When the fan motor speed detected when its maximum output is demanded is below 30 rpm. continuously for 15
seconds, the fan motor stops for 3 minutes and then restarted.
When this happens on 16 occasions (the error is cleared when the value is normal for 5 minutes), the H97
diagnostic symbol is stored in the memory, and the fan motor stops.
<Diagnosis checkpoint>
1.
Check the nature of the fan lockup error.
2.
Check for disconnections of the fan motor connectors and for defects in contact, in the fan motor and in the
control P.C. Board.
H98
Indoor high pressure
protection
The restriction on the compressor frequency is started when the temperature of the indoor unit heat exchanger
source is between 50°C and 52°C, the compressor stops at a temperature from 62°C to 65°C, it is restarted 3
minutes later at below 62°C to 65°C, and the restriction on the compressor frequency is released at a temperature
between 48°C and 50°C. (No error occurs.)
<Diagnosis checkpoint>
1.
Check the indoor unit heat exchanger temperature sensor (check for changes in its characteristics and check
its resistance): Symptoms include no hot start when operation is started, a failure of the thermostat to turn on
(no outdoor unit operation). And, frequent repetition of stopping and startup.
2.
Check also for short-circuits indoors and clogging of the air filters.
93
Содержание CS-ME10DTEG
Страница 6: ...2 1 Wall Type 2 1 1 Remote Control 6 ...
Страница 7: ...2 1 2 Indoor Unit 7 ...
Страница 8: ...8 ...
Страница 9: ...2 2 Duct Type 2 2 1 Remote Control 9 ...
Страница 10: ...2 2 2 Indoor Unit 10 ...
Страница 11: ...11 ...
Страница 12: ...2 3 Ceiling Floor Type 2 3 1 Remote Control 12 ...
Страница 13: ...2 3 2 Indoor Unit 13 ...
Страница 14: ...2 4 Mini Cassette Type 2 4 1 Remote Control 14 ...
Страница 15: ...2 4 2 Indoor Unit 15 ...
Страница 21: ...4 Dimensions 4 1 Wall Type 21 ...
Страница 22: ...22 ...
Страница 23: ...4 2 Duct Type 23 ...
Страница 24: ...24 ...
Страница 25: ...4 3 Ceiling Floor Type 25 ...
Страница 26: ...4 4 Mini Cassette Type 26 ...
Страница 27: ...4 5 Outdoor Unit 27 ...
Страница 28: ...5 Refrigeration Cycle Diagram 28 ...
Страница 29: ...6 Wiring Diagram 6 1 Wall Type 29 ...
Страница 30: ...6 2 Duct Type 30 ...
Страница 31: ...6 3 Ceiling Floor Type 31 ...
Страница 32: ...6 4 Mini Cassette Type 32 ...
Страница 33: ...6 5 Outdoor Unit 33 ...
Страница 34: ...7 Electronic Circuit Diagram 34 ...
Страница 35: ...Printed Circuit Board CU 3E18EBE 35 ...
Страница 42: ...B Indoor Fan Control i Indoor fan control operation outline 1 Cooling Soft Dry 42 ...
Страница 65: ...B Indoor Fan Control i Indoor fan control operation outline 1 Cooling Soft Dry 65 ...
Страница 79: ...B Indoor Fan Control i Indoor fan control operation outline 1 Cooling Soft Dry 79 ...
Страница 90: ...8 8 Outdoor Unit Check Point 90 ...
Страница 96: ...10 Installation Information 96 ...
Страница 97: ...11 Installation Instructions 97 ...
Страница 98: ...98 ...
Страница 99: ...99 ...
Страница 100: ...100 ...
Страница 101: ...101 ...
Страница 102: ...102 ...
Страница 103: ...103 ...
Страница 104: ...104 ...
Страница 105: ...105 ...
Страница 106: ...106 ...
Страница 107: ...107 ...
Страница 110: ...12 2 Duct Type 12 2 1 Detaching the Upper and Inner Casing 12 2 2 Detaching the Control Board 110 ...
Страница 111: ...12 2 3 Detaching the Fan 12 2 4 Detaching the Fan Motor and Drain Motor 111 ...
Страница 116: ...12 5 2 Removing the Control P C Board 12 5 3 Removing the Propeller Fan and Fan Motor 116 ...
Страница 117: ...13 Technical Data 13 1 Operation Characteristics 117 ...
Страница 118: ...118 ...
Страница 119: ...14 Exploded View and Replacement Parts List 14 1 Wall Type 14 1 1 Exploded View Indoor Unit 119 ...
Страница 121: ...14 1 3 Exploded View Indoor Unit 121 ...
Страница 123: ...14 1 5 Exploded View Indoor Unit 123 ...
Страница 125: ...14 2 Duct Type 14 2 1 Exploded View Indoor Unit 125 ...
Страница 127: ...14 3 Ceiling Floor Type 14 3 1 Exploded View Indoor Unit 127 ...
Страница 129: ...14 4 Mini Cassette Type 14 4 1 Exploded View Indoor Unit 129 ...
Страница 130: ...130 ...
Страница 132: ...14 4 3 Exploded View Indoor Unit Front Grille 132 ...
Страница 134: ...14 5 Outdoor Unit 134 ...