(Re-installation)
1.
Remove the cap nut from 3-way valves.
•
Remove the cap nut from 3-way valves after carefully
checked whether the piping connection was properly
and certainly done.
2.
Confirm that the valve in both 3-way valves are set to
the CLOSED position.
3.
Connect the gas cylinder to the liquid-side (high-
pressure) 3-way valve and the charge set to the gas
side (low-pressure) 3-way valve.
•
Remove the flare nut from the service port to connect
the charge set and gas cylinder.
•
Close the valves on the gas cylinder and charge set.
4.
Air purging.
•
Open the valve on the gas cylinder.
•
Open the valve on the charge set, discharge for three
seconds and wait for one minute. Repeat this three
times.
5.
Check for gas leakage.
•
Check the flare connections for gas leakage.
6.
Discharge the refrigerant.
•
Close the valve on the gas cylinder and discharge the
refrigerant until the gauge indicates 3 to 5 kg/cm
2
G.
7.
Disconnect the charge set and the gas cylinder.
8.
Mount the valve stem cap nuts and the flare nuts for
service port onto the 3-way valves.
9.
Mount the cap nut and service port nut onto the 3-way
valves.
•
Be sure to use a torque wrench (CWHAD-9211) to
tighten the service port nut.
•
Be sure to check for gas leakage.
11.2.1. Re-air purging
Procedure:
46
CS-MC12DKV CU-2C24DKV
Содержание CS-MC12DKV
Страница 3: ...2 Functions 3 CS MC12DKV CU 2C24DKV ...
Страница 4: ...4 CS MC12DKV CU 2C24DKV ...
Страница 8: ...4 Dimensions 4 1 Indoor Unit Remote Control 8 CS MC12DKV CU 2C24DKV ...
Страница 9: ...4 2 Outdoor Unit 9 CS MC12DKV CU 2C24DKV ...
Страница 10: ...5 Refrigeration Cycle Diagram 10 CS MC12DKV CU 2C24DKV ...
Страница 11: ...6 Block Diagram 11 CS MC12DKV CU 2C24DKV ...
Страница 12: ...7 Wiring Diagram 12 CS MC12DKV CU 2C24DKV ...
Страница 26: ...9 Operating Instructions 26 CS MC12DKV CU 2C24DKV ...
Страница 27: ...27 CS MC12DKV CU 2C24DKV ...
Страница 28: ...28 CS MC12DKV CU 2C24DKV ...
Страница 29: ...29 CS MC12DKV CU 2C24DKV ...
Страница 30: ...30 CS MC12DKV CU 2C24DKV ...
Страница 31: ...31 CS MC12DKV CU 2C24DKV ...
Страница 56: ...14 Technical Data 14 1 Thermostat characteristics 14 2 Cooling Characteristic 56 CS MC12DKV CU 2C24DKV ...
Страница 57: ...14 3 Piping Length Characteristic Cooling 57 CS MC12DKV CU 2C24DKV ...
Страница 67: ...67 CS MC12DKV CU 2C24DKV ...
Страница 69: ...19 1 Remote Control 69 CS MC12DKV CU 2C24DKV ...
Страница 70: ...19 2 Print Pattern Indoor Unit Printed Circuit Board 70 CS MC12DKV CU 2C24DKV ...
Страница 71: ...71 CS MC12DKV CU 2C24DKV ...
Страница 72: ...19 3 Print Pattern Indicator Printed Circuit Board 72 CS MC12DKV CU 2C24DKV PHAAM Printed in Malaysia ...