![Panasonic CS-MC125KE Скачать руководство пользователя страница 88](http://html.mh-extra.com/html/panasonic/cs-mc125ke/cs-mc125ke_service-manual_257021088.webp)
(No refrigerant in the refrigeration cycle)
Procedure:
1. Connect the vacuum pump to the charge set’s centre
hose.
2. Evacuation for approximately one hour.
•
Confirm that the gauge needle has moved toward -0.1
MPa (-76 cmHg) [vacuum of 4 mmHg or less.]
3. Close the valve (Low side) on the charge set, turn off
the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning
off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
•
Vacuum pump oil
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.
12.5. Evacuation
88
CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE