Indoor Unit
:
CS-KE36NKU
Outdoor Unit :
CU-KE36NKU
Power Supply : 230V Single Phase 60Hz
< Heating Capacity >
TH : Total Heating Capacity (BTU/h)
1. Rating conditions (#) : Indoor Unit Entering Air Temp. 70 °F (21.1 °C) DB
: Outdoor Ambient Temp. 47 °F (8.3 °C) DB / 43 °F (6.1 °C) WB
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
RATING CAPACITY:
36,000 BTU/h
AIR FLOW RATE:
671 CFM
OUTDOOR
INDOOR
ENT. TEMP.
o
F (
o
C)
AMBIENT TEMP.
o
F (
o
C)
WB
60
65
70
75
80
(15.6)
(18.3)
(21.1)
(23.9)
(26.7)
0 (-17.8)
TH
19,760
19,860
19,940
20,010
20,080
CI
2.08
2.17
2.26
2.36
2.45
3 (-16.1)
TH
20,420
20,510
20,600
20,670
20,740
CI
2.11
2.21
2.31
2.40
2.50
8 (-13.3)
TH
21,990
22,090
22,180
22,260
22,330
CI
2.20
2.31
2.41
2.52
2.62
13 (-10.6)
TH
23,630
23,730
23,830
23,920
23,990
CI
2.30
2.42
2.53
2.65
2.76
18 (-7.8)
TH
25,440
25,560
25,660
25,750
25,820
CI
2.42
2.54
2.67
2.79
2.91
23 (-5.0)
TH
27,360
27,480
27,590
27,680
27,140
CI
2.54
2.68
2.81
2.94
3.01
28 (-2.2)
TH
29,370
29,490
29,600
29,700
27,580
CI
2.68
2.82
2.97
3.11
3.01
33 (0.6)
TH
31,460
31,590
31,700
31,560
27,940
CI
2.82
2.98
3.13
3.27
3.01
38 (3.3)
TH
33,540
33,670
33,780
31,900
28,210
CI
2.97
3.14
3.31
3.27
3.01
43 (6.1)
TH
35,760
35,890
# 36,000
32,150
28,410
CI
3.14
3.32
3.50
3.27
3.01
48 (8.9)
TH
38,030
38,160
36,450
32,300
28,520
CI
3.32
3.51
3.53
3.27
3.01
53 (11.7)
TH
40,340
40,460
36,500
32,330
28,530
CI
3.72
3.53
3.53
3.27
3.01
58 (14.4)
TH
42,580
41,040
36,420
32,230
28,430
CI
3.73
3.78
3.53
3.27
3.01
63 (17.2)
TH
44,920
40,770
36,160
32,000
28,210
CI
3.96
3.78
3.53
3.27
3.01
65 (18.3)
TH
44,920
40,610
36,020
31,870
28,090
CI
4.03
3.78
3.53
3.27
3.01
28