3

2 Product Specification

2.1.

CS-F18DTE5 CU-B34DBE5

1. Cooling capacities are based on indoor temperature of 27

°

C D.B. (80.6

°

F D.B.), 19.0

°

C W.B. (66.2

°

F W.B.) and outdoor air

temperature of 35

°

C D.B. (95

°

F D.B.), 24

°

C W.B. (75.2

°

F W.B.)

2. Heating capacities are based on indoor temperature of 20

°

C D.B. (68

°

F D.B.) and outdoor air temperature of 7

°

C D.B. (44.6

°

F

D.B.), 6

°

C W.B. (42.8

°

F W.B.)

ELECTRICAL DATA (50 Hz)

ITEM / MODEL

 

Indoor Unit

Outdoor Unit

Main Body

CS-F18DTE5 

×

 2

CU-B34DBE5

Remote

Control

CZ-RD513C (Wired)

CZ-RL513T (Wireless)

Cooling Capacity

kW

10.0

BTU/h

34,100

Heating Capacity

kW

11.2

BTU/h

38,200

Refrigerant Charge-less

m

30

Standard Air Volume for High, 

m

3

/min

14

94

cfm

494

3316

Outside Dimension (H x W x D)

mm

210 

×

 1245 

×

 700

1170 

×

 900 

×

 320

inch

8-9/32 

×

 49-1/64 

×

 27-9/16

40-1/16 

×

 35-7/16 

×

 12-19/32

Net Weight

kg (lbs)

33 (73)

102 (225)

Piping
Connection

Refrigerant

Gas

mm (inch)

O.D Ø 12.70 (1/2) Flared Type

Liquid

mm (inch)

O.D Ø 6.35 (1/4) Flared Type

Drain

O.D Ø 20

I.D Ø 20

Compressor

Type, Number of Set

 

-

Hermetic, 1

Starting Method

 

-

Permanent Split Capacitor

Motor

Type

 

-

2-pole 1 phase brushless motor

Rated Output

kW

-

3.0

Fan

Type, Number of Set

 

Sirocco fan-4

Mix flow fan,1

Motor

Type

 

4-pole single phase induction motor

6-pole single phase induction motor

Rated Output

kW

0.022

0.07 

×

 2

Air-heat Exchanger (Row x Stage x FPI)

 

Louver-fin type (2 

×

 12 

×

 18)

Corrugate-fin type (2 

×

 44 

×

 20)

Refrigerant Control

 

-

Expansion Valve

Refrigerant Oil (Charged)

cm

3

-

DAPHNE FVC68D (1500)

Refrigerant (Charged) R410a

kg (oz)

-

2.70 (96)

Running
Adjustment

Control Switch

 

Wireless or Wired Remote Control

-

Room Temperature

 

Thermostat

-

Noise Level

 dB (A)

Cooling:       41/37

55/-

Heating:       41/37

56/-

Power Level 

dB

Cooling:       58/54

69/-

Heating:       58/54

70/-

Moisture Removal

 L/h (Pt/h)

6.0 (12.6)

EER

 W/W

2.52/2.49/2.46

COP

 W/W

2.84/2.81/2.77

 ITEM / MODEL

Condition by ISO5151

Volts

V

220

230

240

Phase

 Single

Single

Single

Power Consumption

kW

Cooling

3.85

3.90

3.95

Heating

3.94

3.99

4.04

Running Current

A

Cooling

17.8

18.2

18.7

Heating

18.0

18.2

18.4

Starting Current

A

92

95

98

Power Factor

%

Cooling

99

94

91

Heating

99

95

91

*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Panasonic

Power source

AC, 1~220V,230V, 240V 50Hz

Содержание CS-F18DTE5

Страница 1: ...on 3 2 1 CS F18DTE5 CU B34DBE5 3 2 2 CS F18DTE5 CU B34DBE8 4 2 3 CS F24DTE5 CU B43DBE8 5 2 4 CS F28DTE5 CU B50DBE8 6 3 Twin Systems 7 3 1 Installation Manual 7 4 Troubleshooting Guide 9 4 1 During twin operation 9 Please file and use this manual together with the service manual for Model No CS F24DTE5 CU B24DBE5 CS F28DTE5 CU B28DBE5 CS F28DTE5 CU B28DBE8 CS F34DTE5 CU B34DBE5 CS F34DTE5 CU B34DBE...

Страница 2: ...sible Indoor units with same horsepowers can even be used in combination Master unit and slave units can be set automatically in twin systems No address setting is necessary Multiple indoor units can be operated simultaneously with a single remote control unit Note that individual operation is not possi ble ...

Страница 3: ...tic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 1 phase brushless motor Rated Output kW 3 0 Fan Type Number of Set Sirocco fan 4 Mix flow fan 1 Motor Type 4 pole single phase induction motor 6 pole single phase induction motor Rated Output kW 0 022 0 07 2 Air heat Exchanger Row x Stage x FPI Louver fin type 2 12 18 Corrugate fin type 2 44 20 Refrigerant Control Expansion Valve Re...

Страница 4: ...tarting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 3 0 Fan Type Number of Set Sirocco fan 4 Mix flow fan 1 Motor Type 4 pole single phase induction motor 6 pole single phase induction motor Rated Output kW 0 022 0 07 2 Air heat Exchanger Row x Stage x FPI Louver fin type 2 12 18 Corrugate fin type 2 44 20 Refrigerant Control Expansion Valve Refrigera...

Страница 5: ...ting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 3 75 Fan Type Number of Set Sirocco fan 4 Mix flow fan 1 Motor Type 4 pole single phase induction motor 6 pole single phase induction motor Rated Output kW 0 04 0 07 2 Air heat Exchanger Row x Stage x FPI Slit fin type 2 12 18 Corrugate fin type 2 44 20 Refrigerant Control Expansion Valve Refrigerant Oi...

Страница 6: ...Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 4 5 Fan Type Number of Set Sirocco fan 4 Mix flow fan 1 Motor Type 4 pole single phase induction motor 6 pole single phase induction motor Rated Output kW 0 04 0 07 2 Air heat Exchanger Row x Stage x FPI Slit fin type 2 12 18 Corrugate fin type 2 44 20 Refrigerant Control Expansion Valve Refrigerant...

Страница 7: ...7 3 Twin Systems 3 1 Installation Manual ...

Страница 8: ...8 ...

Страница 9: ...wer is turned on while the transmission wires between the indoor units are not connected open circuit at section C Symptom Remote control unit check flashes Error code F30 01 connected indoor capacity error Indoor unit No 1 LED1 on P C B flashes Indoor unit No 2 no power supply Outdoor unit LED5 6 on P C B flashes connected indoor capacity error 3 The main power is turned on and the connection wir...

Страница 10: ...l unit check flashes Error code F30 01 connected indoor capacity error Indoor unit LED1 on P C B flashes Outdoor unit LED6 7 on P C B flashes connected indoor capacity error Remedy 1 Turn off the main power 2 Connect the disconnected wire correctly 3 Turn on the main power 4 After 1 minute start the operation using the remote control Indoor unit operation will start according to the remote control...