Panasonic CS-F14DB4E5 Скачать руководство пользователя страница 12

12

Indoor unit: LED1 on P.C.B flashes
Outdoor unit: LED6, 7 on P.C.B flashes

4. The main power is turned on and the connection wire is all ok.

If operation starts in this condition, combination of the B50DBE8 outdoor unit and F24DB4E5 indoor unit will result in
abnormal operation.
Symptom
Remote control unit: “check” flashes
Error code: F30-01 (connected indoor capacity error)
Indoor unit: LED1 on P.C.B flashes
Outdoor unit: LED6, 7 on P.C.B flashes (connected indoor capacity error)

Remedy

1. Turn off the main power.

2. Connect the disconnected wire correctly.

3. Turn on the main power.

4. After 1 minute, start the operation using the remote control.

(Indoor unit operation will start according to the remote control setting.)
(Outdoor unit operation will start after 3-5 minutes.)

[PHAAM] Printed in Malaysia

SSBZ0605-00

Содержание CS-F14DB4E5

Страница 1: ...F14DB4E5 CU J28DBE5 3 2 2 CS F14DB4E5 CU J28DBE8 4 2 3 CS F18DB4E5 CU J34DBE5 5 2 4 CS F18DB4E5 CU J34DBE8 6 2 5 CS F24DB4E5 CU J43DBE8 7 2 6 CS F28DB4E5 CU J50DBE8 8 3 Twin Systems 9 3 1 Installation...

Страница 2: ...ible Indoor units with same horsepowers can even be used in combination Master unit and slave units can be set automatically in twin systems No address setting is necessary Multiple indoor units can b...

Страница 3: ...ype Drain mm O D 20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 1 phase brushless motor Rated Output kW 2 0 Fan Type Number of Set Turbo...

Страница 4: ...O D 20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 2 0 Fan Type Number of Set Turbo fan 1 Mix f...

Страница 5: ...0 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 1 phase brushless motor Rated Output kW 3 0 Fan Type Number of Set Turbo fan 1 Mix flow fa...

Страница 6: ...20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 3 0 Fan Type Number of Set Turbo fan 1 Mix flow...

Страница 7: ...D 20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 3 75 Fan Type Number of Set Turbo fan 1 Mix flo...

Страница 8: ...D 20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 4 5 Fan Type Number of Set Turbo fan 1 Mix flow...

Страница 9: ...9 3 Twin Systems 3 1 Installation Manual...

Страница 10: ...10...

Страница 11: ...er is turned on while the transmission wires between the indoor units are not connected open circuit at section C Symptom Remote control unit check flashes Error code F30 01 connected indoor capacity...

Страница 12: ...unit check flashes Error code F30 01 connected indoor capacity error Indoor unit LED1 on P C B flashes Outdoor unit LED6 7 on P C B flashes connected indoor capacity error Remedy 1 Turn off the main...

Отзывы: