50
12.10. Indication Panel
Note:
• If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation mode judgment, or
ON timer sampling.
• If Timer LED is blinking, there is an abnormality operation occurs.
• If e-ion LED is blinking, there is an abnormality of e-ion occurs.
• If PATROL LED is blinking, there is a gas sensor error detection.
12.11. Patrol Operation
A. Purpose
To monitor air dirtiness level by using gas sensor and activates e-ion operation whenever air is dirty.
B. Control Condition
a. Patrol operation start condition
• When the unit operation is started with “OFF/ON” button.
• When the unit stops, “Patrol” button is pressed, Patrol individual operation will start.
• During cooling only operation, “Patrol” button is pressed.
b. Patrol operation stop condition
When any of the following condition is fulfilled:
• When “OFF/ON” button is pressed.
• During any operation with Patrol, “Patrol” button is pressed again.
• When “e-ion” button is pressed.
• When OFF Timer activates.
LED
POWER
TIMER
QUIET
POWERFUL
e-ion
PATROL SENSOR
Color
Green
Orange
Orange
Orange
Blue
Blue
Light ON
Operation ON
Quiet Setting ON
Quiet Mode ON
Powerful Mode ON
e-ion ON
PATROL ON
Light OFF
Operation OFF
Quiet Setting OFF
Quiet Mode OFF
Powerful Mode OFF
e-ion OFF
PATROL OFF
Содержание CS-E7HKEW
Страница 1: ... ...
Страница 13: ...13 2 5 Outdoor Unit CU 2E15GBE ...
Страница 14: ...14 2 6 Outdoor Unit 3E18EBE ...
Страница 15: ...15 2 7 Outdoor Unit CU 3E23CBPG CU 4E27CBPG ...
Страница 16: ...16 ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 21: ...21 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 22: ...22 5 Dimensions 5 1 Indoor Unit ...
Страница 23: ...23 5 2 Outdoor Unit 5 2 1 CU E7HKE CU E9HKE CU E12HKE 5 2 2 CU E15HKE ...
Страница 26: ...26 7 Block Diagram 7 1 CS E7HKEW CU E7HKE CS E9HKEW CU E9HKE CS E12HKEW CU E12HKE ...
Страница 27: ...27 7 2 CS E15HKEW CU E15HKE ...
Страница 28: ...28 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 29: ...29 8 2 Outdoor Unit 8 2 1 CU E7HKE CU E9HKE CU E12HKE ...
Страница 30: ...30 8 2 2 CU E15HKE ...
Страница 31: ...31 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 32: ...32 9 2 Outdoor Unit 9 2 1 CU E7HKE CU E9HKE CU E12HKE ...
Страница 33: ...33 9 2 2 CU E15HKE ...
Страница 34: ...34 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 36: ...36 10 2 Outdoor Unit 10 2 1 CU E7HKE CU E9HKE CU E12HKE ...
Страница 37: ...37 10 2 2 CU E15HKE ...
Страница 40: ...40 3 For the embedded piping This can be used for left rear piping and left bottom piping also ...
Страница 67: ...67 16 1 3 To remove discharge grille ...
Страница 68: ...68 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor ...
Страница 69: ...69 ...
Страница 72: ...72 17 Technical Data 17 1 Operation Characteristics 17 1 1 CS E7HKEW CU E7HKE ...
Страница 73: ...73 ...
Страница 74: ...74 ...
Страница 75: ...75 ...
Страница 76: ...76 17 1 2 CS E9HKEW CU E9HKE ...
Страница 77: ...77 ...
Страница 78: ...78 ...
Страница 79: ...79 ...
Страница 80: ...80 17 1 3 CS E12HKEW CU E12HKE ...
Страница 81: ...81 ...
Страница 82: ...82 ...
Страница 83: ...83 ...
Страница 84: ...84 17 1 4 CS E15HKEW CU E15HKE ...
Страница 85: ...85 ...
Страница 86: ...86 ...
Страница 87: ...87 ...