8.2. Protection Control Features
8.2.1. Protection Control For All Operations
8.2.1.1. Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off for 20 seconds and on again or after 4-way valve deices condition.
8.2.1.2. 30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
8.2.1.3. Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 2 minutes.
Model
E15D
E18D
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
7.20
17
8.74
17
Cooling/Soft Dry (B) & (C)
6.30
17
7.70
17
Heating
8.60
17
10.71
17
4. The first 30 minutes of cooling operation, (A) will be applied.
8.2.1.4. IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 100°C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95°C.
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 22.33 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after 1 minute.
3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
26
CS-E15DD3EW CU-E15DBE / CS-E18DD3EW CU-E18DBE
Содержание CS-E15DD3EW
Страница 10: ...4 Dimensions 4 1 Indoor Unit Remote Control 4 1 1 CS E15DD3EW 10 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 11: ...4 1 2 CS E18DD3EW 11 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 12: ...4 2 Outdoor Unit 4 2 1 CU E15DBE CU E18DBE 12 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 13: ...5 Refrigeration Cycle Diagram 13 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 14: ...6 Block Diagram 14 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 15: ...7 Wiring Diagram 15 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 20: ...2 Heating ii Auto Fan Speed 1 Cooling 20 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 32: ...9 Operating Instructions 32 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 33: ...33 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 34: ...34 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 35: ...35 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 36: ...36 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 37: ...37 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 38: ...38 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 39: ...39 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 73: ...13 1 2 CS E18DD3EW CU E18DBE 73 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 85: ...18 3 Remote Control 85 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 86: ...18 4 Print Pattern Indoor Unit Printed Circuit Board 86 CS E15DD3EW CU E15DBE CS E18DD3EW CU E18DBE ...
Страница 88: ......