101
15.1.4 Compressor
Overheating Prevention Control
•
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
•
If compressor discharge temperature exceeds 107°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. (“F97” is indicated.)
15.1.5 Low Pressure Prevention Control (Gas Leakage Detection)
•
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A
(E7/9/12/15PK), 1.38A and 1.65A (E18/21/24/28PK).
o
During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4°C.
o
During Heating operations :
Indoor piping temperature - indoor suction is under 5°C.
•
Control
contents
o
Compressor stops (and restart after 3 minutes).
o
If the conditions above happen 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
15.1.6 Low
Frequency
Protection Control 1
•
When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
15.1.7 Low
Frequency
Protection Control 2
•
When all the below conditions comply, the compressor frequency will change to lower frequency.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (°C)
T < 14 or T
≥
30
T < 14 or T
≥
28
Outdoor air (°C)
T < 13 or T
≥
38
T < 4 or T
≥
24
Indoor heat exchanger (°C)
T < 30
T
≥
0
Содержание CS-E12PKEW
Страница 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 29: ...29 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E7PK CS E9PK CS E12PK CS E15PK CS XE7PK CS XE9PK CS XE12PK CS XE15PK ...
Страница 30: ...30 5 1 2 CS E18PK CS E21PK CS E24PK CS E28PK CS XE18PK CS XE21PK ...
Страница 31: ...31 5 2 Outdoor Unit 5 2 1 CU E7PKE CU E9PKE 5 2 2 CU E12PKE CU E15PKE ...
Страница 32: ...32 5 2 3 CU E18PKE CU E21PKE ...
Страница 33: ...33 5 2 4 CU E24PKE CU E28PKE ...
Страница 42: ...42 8 1 2 CS E28PKES ...
Страница 48: ...48 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 56: ...56 10 1 6 Human Activity Sensor Printed Circuit Board ...
Страница 57: ...57 10 2 Outdoor Unit 10 2 1 CU E7PKE ...
Страница 58: ...58 10 2 2 CU E9PKE CU E12PKE CU E15PKE ...
Страница 59: ...59 10 2 3 CU E18PKE CU E21PKE ...
Страница 60: ...60 10 2 4 CU E24PKE CU E28PKE ...
Страница 66: ...66 ...
Страница 68: ...68 For Gas side piping please refer table and diagram below ...
Страница 76: ...76 ...
Страница 140: ...140 Figure 3 Figure 4 18 1 1 3 To remove discharge grille Figure 5 ...
Страница 141: ...141 18 1 1 4 To remove control board Figure 6 18 1 1 5 To remove cross flow fan and indoor fan motor Figure 7 ...
Страница 142: ...142 Figure 8 Figure 9 ...
Страница 143: ...143 Figure 10 ...
Страница 145: ...145 18 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure 15 Figure 16 ...
Страница 147: ...147 Figure 20 Figure 21 ...
Страница 148: ...148 Figure 22 ...