8.1.2.2.4. The frequency changed method
1. When intake-setting remains for 30 seconds in a domain after shifting to relative control, a tap is adjusted according to the
domain and frequency changes relatively to the present condition.
2. A suction-setup to other domains by load sudden change (remote control setting change, open air introduction, etc.).
When it moves, addition or subtraction tap is changed at the time of the following renewal of data.
3. When the load change was furthermore carried out and a suction-setup separates from the domain of relative control, it goes
to the clause of initial frequency and operation frequency is determined.
8.1.2.3. The frequency determination method (Soft Dry operation control)
8.1.2.3.1. Basic specification
The domain directions data (intake-setting) transmitted from indoor determines a changed part of frequency.
Then, a directed changed part changes frequency to the present frequency.
Change of frequency may be 1 tap = 1Hz.
It applies to cooling correspondingly.
8.1.2.3.2. Initial frequency determination
It shifts to initial frequency after a starting frequency end.
ID intake
22°C
ID intake < 22°C
Frequency
ESCHZ02
ESCHZ01
38 (E12), 31 (E9)
34 (E12), 28 (E9)
21
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE