48
13.1.5.
Compressor Overheating Prevention Control
• Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of
frequency are as below.
• If compressor discharge temperature exceeds 110
q
C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will
be blinking. (“F97” is indicated.)
13.1.6.
Low Pressure Prevention Control (Gas Leakage Detection)
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4
q
C.
• During Heating operations :
Indoor piping temperature - indoor suction is under 5
q
C.
b. Control contents
• Compressor stops (and restart after 3 minutes).
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated.
13.1.7.
Compressor Tank Temperature Rise Protection Control
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4
q
C.
Indoor temperature and outdoor temperature is 30±5
q
C.
Remote Control setting 16
q
C and Hi Fan Speed.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5
q
C.
Indoor temperature and outdoor temperature is 20 ± 2
q
C.
Remote control setting 30
q
C and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
13.1.8.
Low Frequency Protection Control 1
• When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency will be changed
to 23 Hz for 2 minutes.
Содержание CS-CE7HKEW
Страница 10: ...10 2 4 Outdoor Unit CU 2E15GBE ...
Страница 11: ...11 2 5 Outdoor Unit CU 3E18EBE ...
Страница 12: ...12 2 6 Outdoor Unit CU 3E23CBPG CU 4E27CBPG ...
Страница 13: ...13 ...
Страница 14: ...14 ...
Страница 15: ...15 ...
Страница 18: ...18 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 19: ...19 5 Dimensions 5 1 Indoor Unit ...
Страница 20: ...20 5 2 Outdoor Unit ...
Страница 22: ...22 7 Block Diagram ...
Страница 23: ...23 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 26: ...26 9 2 Outdoor Unit ...
Страница 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 29: ...29 10 2 Outdoor Unit ...
Страница 32: ...32 3 For the embedded piping This can be used for left rear piping and left bottom piping also ...
Страница 58: ...58 16 1 3 To remove discharge grille ...
Страница 59: ...59 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor ...
Страница 60: ...60 ...
Страница 62: ...62 17 Technical Data 17 1 Operation Characteristics 17 1 1 CS CE7HKEW CU CE7HKE ...
Страница 63: ...63 ...
Страница 64: ...64 ...
Страница 65: ...65 ...
Страница 66: ...66 17 1 2 CS CE9HKEW CU CE9HKE ...
Страница 67: ...67 ...
Страница 68: ...68 ...
Страница 69: ...69 ...
Страница 70: ...70 17 1 3 CS CE12HKEW CU CE12HKE ...
Страница 71: ...71 ...
Страница 72: ...72 ...
Страница 73: ...73 ...