13 Protection Operation
13.1. Restart Control (Time Delay Safety Control)
•
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
•
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.2. 7 Minutes Time Save Control
•
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature and compressor OFF temperature during the period.
• This phenomenon is to reduce the built up humidity inside a room.
13.3. 60 Seconds Forced Operation
•
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
•
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
13.4. Starting current Control
•
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
•
The reason of the difference is to reduce the starting current flow.
Содержание CS-C12HKD
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS C7HK CS C9HK CS C12HK ...
Страница 14: ...14 5 2 Outdoor Unit 5 2 1 CU C7HK CU C9HK CU C12HK ...
Страница 15: ...15 6 Refrigeration Cycle Diagram ...
Страница 16: ...16 7 Block Diagram ...
Страница 18: ...18 9 Electronic Circuit Diagram ...
Страница 19: ...19 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board TOP VIEW ...
Страница 20: ...20 BOTTOM VIEW ...
Страница 21: ...21 10 1 2 Power Printed Circuit Board TOP VIEW BOTTOM VIEW ...
Страница 22: ...22 10 1 3 Indicator TOP VIEW BOTTOM VIEW ...
Страница 51: ...51 ...
Страница 52: ...52 16 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Страница 53: ...53 ...
Страница 54: ...54 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...
Страница 55: ...55 17 2 Operation Characteristics 17 2 1 CS C7HK CU C7HK ...
Страница 56: ...56 ...
Страница 57: ...57 17 2 2 CS C9HK CU C9HK ...
Страница 58: ...58 ...
Страница 59: ...59 17 2 3 CS C12HK CU C12HK ...
Страница 60: ...60 ...