– 17 –

CS-A120TE

Operation Details

3) Detail of Sleep Mode

Sleep Mode operates to match your sleeping condition.

1

At Cooling or Soft Dry operation

When you set the sleep Mode (

E

), the following movement will

start to avoid overcooling.
• The fan speed is automatically set to low.
• The setting temperature will be rise by 1

°

C at the start of

operation and by 1

°

C one hour later.

• The Automatic Restarting Control is changed from 7 minutes

to 5 minutes.

• The operation will stop after 5 hours.

2

At Heating operation

When you set the sleep Mode (

E

), the following movement will

start to avoid overheating.
• The fan speed is automatically set to low.
• The setting temperature will be dropped by 2

°

C at the start of

operation and by 3

°

C one hour later.

• The operation will stop after 5 hours.

4) Heating Mode Operation

When selecting the Heating (

#

) Mode Operation, the unit will

operate according to the setting by the Remote Control and the
operation is as the following.

1

Room temperature can be set in 1

°

C steps in the range of 16

to 30

°

C. Relationship between the remote control tempera-

ture adjustment knob and operation is shown in the diagram
below.

2

Taking the difference between the room temperature

distribution and intake air temperature, heating ON tem-
perature is set 3

°

C higher than the remote control setting.

(3

°

C higher than

the set temp.)

Untitled-10

6/19/00, 6:38 PM

17

Содержание CS-A120TE

Страница 1: ...14 15 Operation Details 16 18 Servicing Information 19 Troubleshooting Guide 20 21 Technical Data 22 Exploded View 23 25 Replacement Parts List 24 26 Electronic Parts List 27 CS A120TE CU A120TE CS A180TE CU A180TE CS A240TE CU A240TE ServiceManual 1997 Matsushita Industrial Corp Sdn Bhd 11969 T All rights reserved Unauthorized copying and distribu tion is a violation of law ...

Страница 2: ... and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individuals of potential dangers in attempting to service a product Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to service or repair the product or products dealt with in this service information by anyone el...

Страница 3: ...ange Timer in operation Soft Dry Operation Mode Intermittent operation of Fan at low speed Room Temperature Control Maintains the room temperature accordance with the Setting Temp Remote control Transmitter Indoor Unit e up to 12 up to 1 r e r Room Temperature Setting Time Setting Temperature Setting 20 C to 30 C o higher n standard m lower Automatic Operation Timer Operation Selection ON OFF Dual...

Страница 4: ...tchedtoLowfanspeedandthe unit will be stopped after 5 hours The setting temperature will be raised by 1 C at the starting and by 1 C one hour later Soft Dry of Cooling Operation The setting temperature will be dropped by 2 C at the starting and by 3 C one hour later Heating operation Deice defrost Control Both the indoor and outdoor fan stops during deicing Hot start after deice ends Starts operat...

Страница 5: ... W W A inch inch inch inch mm m m inch mm inch mm inch mm lb kg W W W rpm rpm rpm 3 40 3 35 11 600 11 400 4 10 4 00 13 900 13 600 2 0 4 2 Single 240 220 50 Cooling 1 30 1 27 Heating 1 35 1 27 Cooling 5 8 6 0 Heating 6 1 6 0 Cooling 2 6 2 6 Heating 3 0 3 1 25 CS A120TE SIDE VIEW 8 9 314 9 6 339 10 0 350 Cooling High 46 45 Low 42 41 Heating High 46 45 Low 42 41 G Half Union 1 2 L Half Union 1 4 G ga...

Страница 6: ... Fan Motor Capacitor Unit mm c c g oz mm s min mm Plate fin configuration forced draft Capillary Tube Specifications are subject to change without notice for further improvement CS A120TE Evaporator Copper Aluminium Louver Fin 1 10 21 900 254 22 Electronic Control P P Honeycomb 1 2 µF 400VAC CU A120TE Condenser Copper Aluminium Corrugated Fin 2 19 16 706 482 44 Capillary Tube SUNISO 4GDID or ATMOS...

Страница 7: ... 1 4 G gas side 1 2 L liquid side 1 4 20 2 2 3 3 1 5mm2 6 1 2 165 43 5 16 1 100 25 19 32 650 66 30 SIROCCO STYLAC 181 Induction 4 pole 67 7 40 1 170 1 250 1 340 Inner diameter Length Input Running Current COP Starting Current Cooling Capacity Heating Capacity Moisture Removal Power Source Airflow Method Air Volume Noise Level Electrical Data Piping Connection Port Flare piping Pipe Size Flare pipi...

Страница 8: ...ity Control Compressor Capacitor Fan Motor Capacitor Unit mm c c g oz mm s min mm Plate fin configuration forced draft Capillary Tube Specifications are subject to change without notice for further improvement CS A180TE Evaporator Copper Aluminium Louver Fin 2 10 20 900 254 44 Electronic Control P P Honeycomb 1 2 µF 450VAC CU A180TE Condenser Copper Aluminium Corrugated Fin 2 26 14 769 660 44 Capi...

Страница 9: ...n 1 4 G gas side 5 8 L liquid side 1 4 20 2 2 3 3 2 5mm2 6 1 2 165 43 5 16 1 100 25 19 32 650 66 30 SIROCCO STYLAC 181 Induction 4 pole 67 7 40 1 170 1 250 1 340 Inner diameter Length Input Running Current COP Starting Current Cooling Capacity Heating Capacity Moisture Removal Power Source Airflow Method Air Volume Noise Level Electrical Data Piping Connection Port Flare piping Pipe Size Flare pip...

Страница 10: ...ity Control Compressor Capacitor Fan Motor Capacitor Unit mm c c g oz mm s min mm Plate fin configuration forced draft Capillary Tube Specifications are subject to change without notice for further improvement CS A240TE Evaporator Copper Aluminium Louver Fin 2 10 20 900 254 44 Electronic Control P P Honeycomb 1 2 µF 450VAC CU A240TE Condenser Copper Aluminium Corrugated Fin 2 26 14 769 660 44 Capi...

Страница 11: ...utlet Wireless remote control transmitter Installation on the Wall Ceiling Ceiling Installation on the Ceiling Relative position between the hole and the bracket Wall Centre line for the piping hole Suspention bolt Installation bracket Floor Floor mount bracket Installation on the Floor for left rear piping for right rear piping Wall Wall mount bracket Piping hole ø70 Piping hole ø70 ...

Страница 12: ...mensions CU A120T 75 77 5 130 130 540 663 685 330 370 57 800 300 35 3 way valve at liquid side 3 way valve at gas side 22 106 5 67 93 105 105 570 494 505 280 312 57 780 245 27 5 3 way valve at liquid side 3 way valve at gas side 11 112 ...

Страница 13: ... 11 CS A120TE Refrigeration Cycle Diagram CS A120T CS A180T CS 240T Model A120T A180T A240T GAS 1 2 1 2 5 8 LIQUID 1 4 1 4 1 4 Pipe Size Max Piping Length m 12 15 15 Max Elevation m 5 8 8 ...

Страница 14: ... 12 CS A120TE Block Diagram CS A120T CU A120T ...

Страница 15: ... 13 CS A120TE Block Diagram CS A180T CU A180T CS A240T CU A240T ...

Страница 16: ... 2KS224D5AA02 Ω 2 45 3 86 Wiring Diagram Resistance of Indoor Fan Motor Windings NOTE B BLUE BL BLACK BR BROWN GR GRAY O ORANGE P PINK PU PURPLE R RED W WHITE Y YELLOW Y G YELLOW GREEN CONNECTION BLUE YELLOW YELLOW RED CWA95244 Ω 312 9 419 5 Resistance of Outdoor Fan Motor Windings Resistance of Comp Windings Resistance at 20 C of Ambient temp ...

Страница 17: ...NGE RED ORANGE CWA92139 Ω 122 7 87 0 45 3 193 0 NOTE B BLUE BL BLACK BR BROWN GR GRAY O ORANGE P PINK PU PURPLE R RED W WHITE Y YELLOW Y G YELLOW GREEN CWA92177 Ω 62 5 60 2 69 0 CWA92176 Ω 83 4 67 3 66 5 CONNECTION BLUE BROWN BROWN ORANGE RED BROWN Resistance of Outdoor Fan Motor Windings CONNECTION C R C S 2JS442D3BA01 Ω 0 95 4 39 2JS356D3BA01 Ω 0 97 3 92 Resistance of Comp Windings ...

Страница 18: ...n 6min 6min 6min 10min 10min 10min 10min 10min 10min 6min 6min 6min 6min INDOOR FAN COMPRESSOR Soft Dry Off Comp OFF Cooling OFF Set Temp Comp ON Room Temp 1 5 C 1 5 C 2 Soft Dry Mode Operation When selecting the Soft Dry f Mode Operation the operation will be cooling until the Room Temperature reaches the Set Temp on the remote control and then Soft Dry will activate During Soft Dry operation the...

Страница 19: ... start to avoid overheating The fan speed is automatically set to low The setting temperature will be dropped by 2 C at the start of operation and by 3 C one hour later The operation will stop after 5 hours 4 Heating Mode Operation When selecting the Heating Mode Operation the unit will operate according to the setting by the Remote Control and the operation is as the following 1Room temperature c...

Страница 20: ... blow out temperature Angle of the left right louver is manually adjusted 7 Automatic Operation When s automatic operation is set with the operation mode selector on the remote control the indoor fan runs at Low speed for 20sec the air conditioner unit senses the room temperature then automatically selects the operation mode and temperature setting Intake Temp C 25 21 Operation mode Cooling Soft D...

Страница 21: ...t Board and to the indoor unit Main Control P C B If the two or more air conditioners in one room have the same oscillation code all of them will be activated by operation of one Remote Control transmitter By adding a jumper wire at the Remote Control P C B side and a carbon resistor 1 4W to the Main Control P C B as shown in the table at the right any one of four oscillation codes including the o...

Страница 22: ... air temperature difference Less than 8 C at cooling mode Less than 14 C at heating mode Troubleshooting Guide Condition Indoor fan speed High Outdoor temperature is 35 C at cooling mode and 7 C at heating mode Gas pressure MPa kg cm2 G 0 4 0 6 4 6 1 5 2 1 15 21 Difference in the intake and outlet air temperatures Above 8 C 15 minutes after an operation is started at cooling mode Above 14 C 15 min...

Страница 23: ...en minutes after an operation is started Electric current during operation becomes approximately 20 lower than the normal value The discharge tube of the compressor becomes abnormally hot nor mally 70 to 90 C The difference between high pressure and low pressure becomes almost zero Electric current reaches a high level abnormally and the value exceeds the limit of an ammeter In some cases a breake...

Страница 24: ...ng Heating L L L L L Operation characteristics Cooling characteristics Outdoor temperature Conditions Room Temperature 27 C D B T Cooling operation at High Fan Heating characteristics Outdoor temperature Conditions Room Temperature 21 C D B T Heating operation at High Fan CS A120T CS A180T CS A240T ...

Страница 25: ... 23 CS A120TE CS A120T CS A180T CS A240T Exploded View ...

Страница 26: ... 25 CS A120TE Exploded View CU A120T CU A180T CU A240T CU A120T CU A180T CU A240T ...

Страница 27: ...HIGH FLARE NUT TUBE ASS Y LOW FLARE NUT DRAIN PAN ASS Y TAP DRAIN TRAY DISCHARGE GRILLE COMPLETE DISCHARGE GRILLE VANE AIR SWING VANE AIR SWING MOTOR INDICATOR SENSOR ASS Y INTAKE AIR RECEIVER COMPLETE CABINET FRONT PLATE CABINET RIGHT SIDE PLATE CABINET LEFT SIDE PLATE CONTROL BOARD COVER INTAKE GRILLE HOLDER INTAKE GRILLE RIGHT HOLDER INTAKE GRILLE UPPER HOLDER INTAKE GRILLE LEFT AIR FILTER REMO...

Страница 28: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 4 6 10 2 4 1 1 1 1 1 1 CU A120TE CWD50K550A CWH15214 CWD54155 CWA95244 CWH03K002 CWH56053 2KS224D5AA02 CWB81047 CWH50055 CWH4582065 CWBDCC004 CWB14010 CWH39K019A CWB01380 CWH6002140 1 4 CWB11025 CWT00C721 CWB01379 CWB00003 CWA43C439 CWT25007 1 2 CWH7080300 CWH17006 CWH7041200 CWA12049 CWH10661 CWA31602 1 2MF 400V CWA31647 30MF 370V ...

Страница 29: ...RATED CIRCUIT INTEGRATED CIRCUIT INTEGRATED CIRCUIT PHOTO COUPLER TRANSISTOR TRANSISTOR TRANSISTOR RELAY RELAY RESONATOR RESONATOR ZENAR DIODE ZNR PART NO A48039 A54MA165TA5 A54RA15 01KB A54CS1VB20E XBA2C20TR0 A52D7533U313 A52MN1551ABA A52MPC393C A52MPA2003C A52M54566P A52C050 A52LQT50 5X1 A52C057 A52LP620 GB A55DTC124EST A55C1740STPQ A55DTD123YST A00042 A00084 A45CSB400P19 A45ST4 0MGWT A54D6 2EL2...

Страница 30: ...MAICO Printed in Malaysia P971002200YH2 ...

Отзывы: