2
1. Technical Data
1.1 Ducted Model Cooling Low Temperature Performance
With Connect To Single
E18JD3EA (5.0kW)
Outdoor Temp.
Indoor Temp.
o
C
5 10 20 25 35 40
Total
Capacity
W 6008 6033 5787 5600 5100 4639
27/19
o
C
Sensible
Capacity
W 4103 4121 3953 3825 3483 3169
Total
Capacity
W 4004 3937 3641 3611 5166 4753
23/15
o
C
Sensible
Capacity
W 3327 3272 3026 3001 4293 3950
Total
Capacity
W 2219 2071 1964 2055 5085 4825
19/12
o
C
Sensible
Capacity
W 2170 2025 1920 2010 4973 4718
E15JD3EA (4.0kW)
Outdoor Temp.
Indoor Temp.
o
C
5 10 20 25 35 40
Total
Capacity
W 4567 4617 4481 4440 4100 3730
27/19
o
C
Sensible
Capacity
W 3120 3153 3061 3033 2800 2547
Total
Capacity
W 3079 3001 2796 2862 4162 3797
23/15
o
C
Sensible
Capacity
W 2559 2494 2324 2378 3458 3155
Total
Capacity
W 1800 1706 1554 1648 3879 3887
19/12
o
C
Sensible
Capacity
W 1760 1668 1520 1612 3793 3801
E10JD3EA (2.5kW)
Outdoor Temp.
Indoor Temp.
o
C
5 10 20 25 35 40
Total
Capacity
W 2703 2738 2831 2740 2500 2334
27/19
o
C
Sensible
Capacity
W 1846 1870 1933 1871 1708 1594
Total
Capacity
W 1783 1660 1428 1556 2558 2370
23/15
o
C
Sensible
Capacity
W 1481 1379 1186 1293 2125 1969
Total
Capacity
W 1120 1052 1010 1039 2613 2440
19/12
o
C
Sensible
Capacity
W 1095 1029 988 1016 2555 2386
All manuals and user guides at all-guides.com