Appendix A. EX 1.0 Feature Update
Section 300-Installation
Page A-20
DBS Manual - Revised April 2000
DBS-2.3/9.2-300
Notes
• Serial Port 2 requires a special interface cable.
• Serial Port 2 can be used for Bus Monitor/Maintenance only. You must
continue to use the backplane port (Serial Port 1) for SMDR.
• Port selections are made from the Attendant phone as follows:
• When Serial Port 2 is used (i.e., #92 has been entered), the internal RAI
modem cannot be accessed.
to set Serial Port 1 for...
and Serial Port 2 for...
dial #90
Bus Monitor/Maintenance
no output
dial #92
SMDR
Bus Monitor/Maintenance
dial #93
SMDR/Maintenance
no output
Содержание CPC-EX
Страница 12: ...About This Manual Section 300 Installation xii DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 18: ...Chapter 1 Requirements Section 300 Installation 1 6 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 20: ...2 2 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 28: ...Chapter 2 System Overview Section 300 Installation 2 10 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 30: ...3 2 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 48: ...Chapter 3 Cabinet Installation Section 300 Installation 3 20 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 50: ...4 2 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 94: ......
Страница 96: ...5 2 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 132: ...6 2 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 144: ...7 2 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 160: ...Chapter 7 Specifications Section 300 Installation 7 18 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...
Страница 204: ...Index Section 300 Installation Index 8 DBS Manual Revised April 2000 DBS 2 3 9 2 300 ...