8.  Next, insert a small amount of same refrigerant into the system through the centre hose, until the pressure 

reaches about 1MPa (10 BarG). 

 

2

2

N

2

R-###

(Low/Gas)

pressure gauge

(High/Liquid) pressure gauge

An example illustrations of setup for

refrigerant leak detection.

3

7

4

8

 

 
Step 2: Refrigerant leak detection through Electronic halogen leak detector and/or ultrasonic leak detector: 
1.  Use any one of below detector to check leaking. 

  Electronic halogen leak detector. 

  Switch on the unit. 

  Cover the test area from direct draft. 

  Pass the detection probe near test area and wait for audible and visible signals. 

  Ultrasonic Leak Detector 

  Make sure the area is quiet. 

  Switch on the ultrasonic leak detector. 

  Move the probe along your air conditioning system to test for leaks, and mark for repair. 

2.  Any leak detected at this level shall be repaired and retested, starting from “Step 1: Pressure test”. 
 
NOTE: 

  Always recover the refrigerant and Nitrogen gas into recovery cylinder after completion of a test. 

  You must use the detection equipment with Detectable Leak Rate of 10

-6

 Pa.m

3

/s or better. 

  Do not use refrigerant as test medium for system with total refrigerant charge more than 5kg. 

  Test shall be performed with dry Nitrogen or another non-flammable, non-reactive, dried gas. Oxygen, air or 

mixtures containing them shall not be used. 

 
Step 3: Vacuum test: 
1.  Perform Vacuum test to check leak / moisture if present. 
2.  Refer to section “EVACUATION OF THE EQUIPMENT” to vacuum gas out of the air conditioning system. 
3.  Wait for a few hours, depending on the size of the refrigerating system and monitor the pressure rise. 

If the pressure rises until 1 bar absolute, then there is leak. 
If the pressure rises, but it is lower than 1 bar absolute, then moisture is present. 

 
Next, remove the moisture, or repair, and redo the refrigerant leak testing, starting from “Step 1: Pressure test”. 

 

2

2

3

Vacuum pump

Handle

(Low/Gas)

pressure gauge

(High/Liquid) pressure gauge

An example illustrations of setup for

refrigerant leak detection.

 

Содержание Aquarea WH-SXC12H6E5

Страница 1: ...o service or repair the products dealt with in this service information by anyone else could result in serious injury or death There are special components used in this equipment which are important for safety These parts are marked by in the Schematic Diagrams Circuit Board Diagrams Exploded Views and Replacement Parts List It is essential that these critical parts should be replaced with manufac...

Страница 2: ...12 0 12 0 13 0 Tbivalent TOL C 2 2 10 10 15 22 SCOP ns W W 4 02 158 3 32 130 3 20 125 Annual Consumption kWh 3990 7466 10012 Heating ErP Class A A A Condition Ambient Water A35W7 A7W35 A2W35 dB A Cooling 50 Heating 52 Noise Level Power Level dB Cooling 68 Heating 69 Air Flow m 3 min ft 3 min Cooling 93 3 3290 Heating 80 0 2830 Refrigeration Control Device Expansion Valve Refrigeration Oil cm 3 FV5...

Страница 3: ...5 Input Power kW Cooling 3 56 Heating 2 53 Heating 3 49 Maximum Input Power For Heatpump System kW 6 27 Power Supply 1 Phase Ø Max Current A Max Input Power W 1Ø 29 0 6 27k Power Supply 2 Phase Ø Max Current A Max Input Power W 1Ø 26 0 6 00k Power Supply 3 Phase Ø Max Current A Max Input Power W Starting Current A 16 5 Condition Ambient Water A35W7 A7W35 A2W35 Running Current A Cooling 16 5 Heatin...

Страница 4: ...er W 92 Type Brazed Plate No of Plates 36 Size W H L mm 65 119 376 Hot Water Coil Water Flow Rate l min m 3 h Cooling 28 7 1 7 Heating 34 4 2 1 Pressure Relief Valve Water Circuit kPa Open 300 Close 266 and below Flow Switch Electronic Sensor Protection Device A Residual Current Circuit Breaker 40 Volume I 10 Expansion Vessel MWP bar 3 Capacity of Integrated Electric Heater kW 6 00 Note Cooling ca...

Страница 5: ... function Weekly timer setting A class energy efficiency pump Water pump speed can be set by selection at control panel Improved deice cycle Protection Feature Random auto restart after power failure for safety restart operation Gas leakage protection Prevent compressor reverse cycle Inner protector to protect compressor Serviceability Feature Breakdown Self Diagnosis function System Status Check ...

Страница 6: ...B ELCB Backup Heater Control board cover Control board Flow sensor Air purge valve Backup heater Overload protector 2 pieces for SXC09 3E5 or 3 pieces for SXC12 6E5 Expansion vessel Pressure relief valve Water pressure gauge Water filter Water pump 1 3 2 4 5 1 5 2 6 7 13 14 12 10 11 8 9 15 16 1 2 3 4 6 7 8 5 2 5 1 9 10 11 12 13 14 15 16 ...

Страница 7: ...Outdoor Unit Air inlet rear Air outlet Air inlet side ...

Страница 8: ...mm 340 500 58 9 141 9 100 88 3 30 6 49 129 5 250 156 980 892 326 9 476 424 5 404 1 437 3 360 180 54 6 69 5 56 1 51 5 339 3 45 Top View Front View Side View Bottom View 1556 from 5 5 200 756 160 70 Indoor Unit body ground Installation plate Installation plate Bolt size M8 Wall Wall More than 375 More than 375 ...

Страница 9: ...Outdoor Unit Unit mm Top View Front View Side View 900 400 320 355 900 318 5 253 218 165 243 1340 615 320 40 40 20 110 356 5 Side view Back view 30 ...

Страница 10: ...er Strainer Strainer 4 Way Valve Gas Side 3 Way Valve Liquid Side 3 Way Valve 2 Way Valve Accumulator in out Pressure Switch High Pressure Sensor Compressor Discharge Temp Sensor Compressor Water Pressure Gauge Capillary Tube Strainer Strainer Subcooler Expansion Valve Bypass Muffler Expansion Valve Model Piping size Rated Length m Gas Liquid For Heat Pump Indoor Unit For Hydromodule Tank Max Elev...

Страница 11: ...R B W W W W W CN PWR3 Green CN PWR2 Blue CN PWR4 Black CN CNT CN PWR BLK CN203 CN202 CN COMM YLW CN PWR202 YLW ACL BLK ACN WHT CN PWR204 YLW DCP RED DCN BLU ELECTRONIC CONTROLLER SUB CN201 CN209 CN208 CN210 CN206 CN207 CN204 CN205 CN CNT WHITE 5 1 SSR204 1 2 3 4 5 2 4 1 3 2 1 1 1 2 1 3 3 1 2 1 SIGNAL DETECTION CIRCUIT SIGNAL DETECTION CIRCUIT SSR201 SSR200 SSR203 SSR202 RY1 SOLAR WATER PUMP POOL W...

Страница 12: ...K FUSE1 1 4 7 7 4 V U U RED P N V BLUE TO INDOOR UNIT BLUE BLACK 3 FG1 GREEN G MS R DCP IN WHITE BL CAPACITOR ELECTRONIC CONTROLLER AC C BLACK B REACTOR GR A BL BL DCN OUT CIRCUIT W R B BR Y CIRCUIT CIRCUIT R TERMINAL BOARD TERMINAL BOARD 2 1 CN DIS C47 1µ 6 3V R102 4 99k 1 t 5V ELECTRO MAGNETIC COIL BYPASS EXPANSION VALVE 1 2 3 4 5 6 M IC16 IC16 IC16 IC16 IC16 IC16 IC16 IC15 IC15 IC15 IC15 IC15 I...

Страница 13: ...the wall The distance from installation plate edge to ground should more than 1556 mm Always mount the installation plate horizontally plate by aligning the marking thread and using a level gauge Mount the installation plate on the wall with 6 sets of plug bolt and washer all non supply with size M8 To Drill A Hole In The Wall And Install A Sleeve Of Piping 1 Insert the piping sleeve to the hole 2...

Страница 14: ...d outlet connection and clean all pipings with tap water before connecting to the indoor unit Cover the pipe end to prevent dirt and dust when inserting it through a wall Choose proper sealer which can withstand the pressures and temperatures of the system If an existing tank is to be connected to this indoor unit ensure the pipes are clean before water pipe installation is carried out Be sure to ...

Страница 15: ...only Do not insert this hose into sewage or drain pipe that may generate ammonia gas sulfuric gas etc If necessary use hose clamp to further tighten the hose at drain hose connector to prevent leakage Water will drip from this hose therefore the outlet of this hose must be installed in an area where the outlet cannot become blocked Packing Drain Elbow 3 2 Pressure Relief Valve Drainage Pipework Co...

Страница 16: ...ower Supply Cord Cable Size Isolating Devices Recommended RCD 1 3 min 4 0 mm 2 30A 30mA 2P type A 2 3 min 4 0 mm 2 30A 30mA 2P type A 3 To avoid the cable and cord being damaged by sharp edges the cable and cord must be passed through a bushing located at the bottom of Control Board before terminal board The bushing must be used and must not be removed Terminals on the Outdoor Unit 1 2 3 1 2 3 Col...

Страница 17: ...an be moved to the room and serve as Room Thermostat Installation Location Install at the height of 1 to 1 5 m from the floor Location where average room temperature can be detected Install vertically against the wall Avoid the following locations for installation 1 By the window etc exposed to direct sunlight or direct air 2 In the shadow or backside of objects deviated from the room airflow 3 Lo...

Страница 18: ... of the bottom case Hole for screw Screw field supply Claw 2 places Bottom case Back side Top case Back side Remote controller terminal board Remove the coating Approx 6 mm Make sure the wiring connection is in the correct direction Claw 2 places Mount the bottom case to the wall Pass the wire through the hole in the centre of the bottom case Connect the remote control wiring 11 1 6 5 Replace The ...

Страница 19: ...3 Start filling water with pressure more than 0 1 MPa 1 bar to the Indoor Unit via water inlet Stop filling water if the free water flow through Pressure Relief Valve drain hose 4 Turn ON the power supply and make sure Water Pump 16 is running 5 Check and make sure no water leaking at the tube connecting points ...

Страница 20: ... to 1 pole switch with min 3 0 mm contact gap Its cable must be 2 min 0 5 mm2 double insulation layer of PVC sheathed or rubber sheathed cable note Switch used shall be CE compliance component Maximum operating current shall be less than 3Arms 8 Tank sensor shall be resistance type please refer to Graph 7 1 for the characteristic and details of sensor Its cable shall be 2 min 0 3 mm2 double insula...

Страница 21: ...ignal cable shall be 3 min 0 3 mm2 double insulation layer of PVC sheathed or rubber sheathed cable 12 Heat Cool switch cable shall be 2 min 0 3 mm2 double insulation layer of PVC sheathed or rubber sheathed cable 13 External compressor switch cable shall be 2 min 0 3 mm2 double insulation layer of PVC sheathed or rubber sheathed cable Bind optional cables with these bands Optional PCB 7 Bind all ...

Страница 22: ...r relocation and extension Total cable length shall be 50m or less Outputs 3 way valve AC230V N Neutral Open Close direction For circuit switching when connected to DHW tank 2 way valve AC230V N Neutral Open Close Prevent water circuit pass through during cooling mode Extra pump AC230V Used when indoor unit pump capacity is insufficient Booster heater AC230V Used when using booster heater in DHW t...

Страница 23: ...sions mm 3 Outdoor sensor PAW A2W TSOD If the installation location of the outdoor unit is exposed to direct sunlight the outdoor air temperature sensor will be unable to measure the actual outdoor ambient temperature correctly In this case optional outdoor temperature sensor can be fixed at a suitable location to more accurately measure ambient temperature 70 93 46 Dimensions mm 4 Room sensor PAW...

Страница 24: ...or to the CN CNT connector on the printed circuit board Pull the cable out of the Indoor Unit so that there is no pinching If an optional PCB has been install in the Indoor Unit connect the CN CNT connector to Optional PCB 7 Connection examples H series CN CNT cable Without Optional PCB CN CNT cable With Optional PCB 2 Insert a flat head screwdriver into the slot on the top of the adaptor and remo...

Страница 25: ... CNT cable to the wall Pull the cable around as shown in the diagram so that external forces cannot act on the connector in the adaptor Furthermore on the Indoor Unit end use the included cable tie to fix the cables together Cord clamp Cable tie ...

Страница 26: ...oduct in a place where it will be affected by typhoon or strong wind such as wind blowing between buildings including the rooftop of a building and a place where there is no building in surroundings fix the product with an overturn prevention wire etc Overturn prevention fitting model number K KYZP15C If piping length is over 10 m additional refrigerant should be added as shown in the table Piping...

Страница 27: ... UX09 E5 UX12 E5 UD12 E5 UD16 E5 UX09 E8 UX12 E8 UX16 E8 UD09 E8 UD12 E8 UD16 E8 620 140 15 355 450 44 Unit mm After selecting the best location start installation according to Installation Diagram 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut ø10 mm 2 When installing at roof please consider strong wind and earthquake Please fasten the installation stand firmly with...

Страница 28: ...r this pull the service panel toward you to remove it Front pipe panel Rear pipe panel Mounting screws Service panel Rear direction Side panel Downward direction Forward direction Close the tube joining area with putty heat insulator local supply without any gap as shown in right figure To prevent insects or small animal entering Putty or Heat insulator local supply CUTTING AND FLARING THE PIPING ...

Страница 29: ...are tightened further continue working from step 3 If the leak does not stop when the connections are retightened repair the location of leak Do not release refrigerant during piping work for installation and reinstallation Take care of the liquid refrigerant it may cause frostbite Air Tightness Test on the Refrigerating System Before system charged with refrigerant and before the refrigerating sy...

Страница 30: ... recover the refrigerant and Nitrogen gas into recovery cylinder after completion of a test You must use the detection equipment with Detectable Leak Rate of 10 6 Pa m3 s or better Do not use refrigerant as test medium for system with total refrigerant charge more than 5kg Test shall be performed with dry Nitrogen or another non flammable non reactive dried gas Oxygen air or mixtures containing th...

Страница 31: ...ty reason Models Flexible cable specification UX09 E8 UX12 E8 UX16 E8 UD09 E8 UD12 E8 UD16 E8 6 min 1 5 mm 2 1 2 3 4 5 1 2 3 4 5 Terminals on the indoor unit Colour of wires Terminals on the outdoor unit Earth Wire must be longer than others cables for safety reason CAUTION For three phase model never operate the unit by pressing the electromagnetic switch Never correct the phase by switching over...

Страница 32: ...insert Conductor fully insert PROHIBITED PROHIBITED Pipe Insulation 1 Please carry out insulation at pipe connection portion as mentioned in Indoor Outdoor Unit Installation Diagram Please wrap the insulated piping end to prevent water from going inside the piping 2 If drain hose or connecting piping is in the room where dew may form please increase the insulation by using POLY E FOAM with thickne...

Страница 33: ...is manually adjusted by the installer according to water circuit pressure drop However the following sequences do not follow maximum pump duty setting by remote control Pump down mode Air purge mode Normal deice 1 P Q graph for different pump HEX duty 0 150 140 130 120 110 100 90 80 70 60 Pressure P kpa Water Flow Rate Q L min P Q 50 40 30 20 10 0 10 20 30 40 50 60 Max Duty C5 Min Duty 5A WH SXC12...

Страница 34: ...T 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7 m Outdoor Temperature C Outdoor Temperature C Input Power kW Outdoor Temperature C Capacity kW 1 000 2 000 3 000 4 000 5 000 6 000 15 11 7 3 1 5 9 13 17 21 25 10 000 11 000 12 000 13 000 14 000 15 000 15 11 7 3 1 5 9 13 17 21 25 ...

Страница 35: ...T C WBT Indoor water inlet temperature 12 C Indoor water outlet temperature 7 C Piping length 7 m Outdoor Temperature C Capacity kW Outdoor Temperature C Input Power kW 0 500 1 500 2 500 3 500 4 500 5 500 18 21 24 27 30 33 36 39 42 45 7 000 8 000 9 000 10 000 11 000 12 000 18 21 24 27 30 33 36 39 42 45 ...

Страница 36: ... C WBT Indoor water inlet temperature 19 C Indoor water outlet temperature 14 C Piping length 7 m Outdoor Temperature C Capacity kW Outdoor Temperature C Input Power kW 0 500 1 500 2 500 3 500 4 500 5 500 18 21 24 27 30 33 36 39 42 45 8 000 10 000 12 000 14 000 16 000 18 000 18 21 24 27 30 33 36 39 42 45 ...

Страница 37: ...T C WBT Indoor water inlet temperature 23 C Indoor water outlet temperature 18 C Piping length 7 m Outdoor Temperature C Capacity kW Outdoor Temperature C Input Power kW 0 500 1 500 2 500 3 500 4 500 5 500 18 21 24 27 30 33 36 39 42 45 5 000 7 000 9 000 11 000 13 000 15 000 18 21 24 27 30 33 36 39 42 45 ...

Страница 38: ...WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7 m Piping Length m Piping Length m Input Power kW Piping Length m Capacity kW 8 000 9 000 10 000 11 000 12 000 13 000 3 6 9 12 15 18 21 24 27 30 1 500 2 000 2 500 3 000 3 500 4 000 3 6 9 12 15 18 21 24 27 30 ...

Страница 39: ... C DBT C WBT Indoor water inlet temperature 12 C Indoor water outlet temperature 7 C Piping length 7 m Piping Length m Capacity kW Piping Length m Input Power kW 3 300 3 400 3 500 3 600 3 700 3 800 3 6 9 12 15 18 21 24 27 30 6 000 7 000 8 000 9 000 10 000 11 000 3 6 9 12 15 18 21 24 27 30 ...

Страница 40: ...r W 15 12000 4750 12000 4960 12000 5410 11000 5380 10800 5820 10500 6260 7 12000 3850 12000 4410 12000 4980 12000 5540 12000 5900 12000 6260 2 12000 3190 12000 3490 12000 3870 12000 4250 12000 4860 12000 5470 7 12000 2180 12000 2530 12000 2960 12000 3390 12000 3780 12000 4160 25 13600 1550 13600 1760 13400 2100 13200 2430 12600 2660 12000 2890 Cooling Capacity Table WH SXC09H3E5 WH UX09HE5 Water I...

Отзывы: