Common specifications

Item

Specifications

Output frequency

Frequency 

range

VF control: 0.2Hz to 400Hz

Sensorless vector control: 0.5Hz to 120Hz

Frequency 

display

Digital display

Frequency 

precision

Analog setting: within 

±

0.5% of maximum set frequency (25

 

±

 

10

)

Digital setting: within 

±

0.01% of maximum set frequency (-10

 to 

+ 50

)

Frequency 

resolution

Analog setting : 0.1Hz (in 50/60Hz mode)

Digital setting : 0.1Hz

Inverter control 

mode

High carrier frequency sinusoidal PWM control

(V/F control or sensorless vector control is available.)

Carrier frequency

· V/F control setting: 9 options (adjustable from 0.8kHz to 15kHz) 

can be selected.

· Sensorless vector control setting: 6 options (adjustable from 

2.5kHz to 15kHz) can be selected. (0.8kHz, 1.1kHz, 1.6kHz, 

2.5kHz, 5.0kHz, 7.5kHz, 10.0kHz, 12.5kHz, 15.0kHz)

Operation

Start/Stop

· Operation panel buttons

· 1a contact signal and 3-wire input (1a and 1b contact signals) can 

be selected.

· RS485 communication

· Wait time (0.1s to 100s) can be set.

Forward/

Reverse run

· Operation panel buttons

· 1a contact signal (reverse run can be disabled.)

· RS485 communication

Jogging 

operation

Operating frequency: adjustable from 0.2Hz to 400Hz

Acceleration/deceleration time: adjustable from 0.04s to 3600s

Stop mode

Deceleration stop / coast-to-stop (switchable)

Reset 

function

Reset by stop signal/reset by external devuce/reset by

operation panel(optional) / reset by power supply

Starting 

frequency

Adjustable from 0.2Hz to 60Hz

Stop 

frequency

Adjustable from 0.2Hz to 60Hz

Ride-through 

restart 

selection

0Hz restart/operation frequency restart/speed search restart 

(switchable)

Speed 

search

Speed search during startup (optional)

Retry 

function

Retry selection: validity of function, selection of details of retry 

faults

Retry operations: adjustable from 1 to 10 operations

Содержание AMK3000114

Страница 1: ... 06 MK300 panasonic net id pidsx global 1 phase 200V 0 2kW 2 2kW 3 phase 400V 0 75kW 15kW INSTALLATION MANUAL Inverter Applicable models Before starting to use the product please read through this manual carefully for proper use ...

Страница 2: ...re using this product in special applications such as machinery or systems in movable object medical aerospace nuclear energy control submarine relay equipments or systems please contact us Although this product was manufactured under strict quality control system it is strongly recommended to install safety devices to prevent serious accidents when used in facilities where a breakdown of this pro...

Страница 3: ...o the Instruction Manual Failure to do so may result in personnel injury by its dropping Do not install or operate an inverter that is damaged or with part s missing Failure to do so may result in personnel injury Do not connect an AC power supply to output terminals U V W Failure to do so may result in personnel injury or fire Make sure that the rated voltage of inverter matches with voltage of AC...

Страница 4: ...ignal present the inverter may restart suddenly Always take measures to ensure personal safety Failure to do so may result in personnel injury When retry function is in use the inverter may automatically start restart suddenly so do not approach it Always take measures to ensure personal safety Failure to do so may result in personnel injury While auto tuning function is in use the inverter will a...

Страница 5: ... component and may interfere with communicating equipment such as AM radio nearby The severity of interference depends on the radio field strength and is hard to be eliminated completely While it may be reduced by relocating radio antenna using noise filter housing the inverter in a metal box or routing cables in conduit Please consult with us separately Do not conduct insulation resistance test bet...

Страница 6: ...y the wiring fault or damage of internal parts of inverter etc Determine the trip reason of circuit breaker and turn it ON again after troubleshooting Take measures against higher harmonics The higher harmonics generated by inverter may cause overheating of or damage to phase advance capacitor or generator Precautions on 400V series motor When 400V series motor is driven by the inverter use the mo...

Страница 7: ...6 2 2 Part Name FWD REV ALM MODE STOP RUN ESC PROG AM AT 8 9 AM AL For 200V 0 2kW 0 4kW AK FWD REV ALM MODE STOP RUN ESC PROG AM AM AM AM AT AK 9 8 AL For other models ...

Страница 8: ...necting option unit RJ45 Casing of Cooling fan 2 9Terminal block for control circuit signal input output BKInternal component cooling fan 3 A Terminal block for control circuit relay output BLCasing of internal component cooling fan 3 AKTerminal block for main circuit BMFixing screw for casing of internal component cooling fan 3 ALGround terminal B Wiring nameplate 1 Check that the rating nameplat...

Страница 9: ...tor red Indicates abornality and alarm 5 PROG indicator green Lights up during changing of parameter setting mode 6 RUN button A button for making inverter running 7 STOP button A button for making inverter stopping 8 MODE button Swithches between Operation Status Display and Function Setting and displays data A button for switching to mode display 9 ESC button Returns to the previous operation du...

Страница 10: ...and panel size Allowable ambient temperature 10 to 50 5 5kW 7 5kW 11kW 15kW Temperature for 10 to 40 light load specification Ambient temperature should be measured at a point 5cm away from the inverter In case multiple inverters are installed If multiple inverters are installed side by side ambient temperature should be within 10 to 40 Install the inverter vertically Installing the inverter in any...

Страница 11: ... 63 72 131 140 146 5 AMK3000P42 AMK3000P72 100 110 130 140 156 5 AMK3001P52 AMK3002P22 130 140 130 140 156 5 H H1 W1 W FWD REV ALM MODE STOP RUN ESC Unit mm PROG For 0 75kW or above 4 φd Mounting hole Note 1 D 5 H1 H D 5 2 φd Mounting hole Note 1 10 W1 W 24 For 200V 0 2kW 0 4kW Unit mm ...

Страница 12: ... 140 156 5 AMK3001P54 AMK3002P24 130 140 130 140 156 5 AMK3003P74 AMK3005P54 150 160 190 200 185 5 AMK3007P54 AMK3000114 204 220 265 280 198 7 AMK3000154 Note 1 M6 screws are used in mounting holes for AMK3000114 and AMK3000154 while M4 screws are used in other mounting holes Unit mm ...

Страница 13: ...f the terminal cover 1 Removal and installation of terminal cover 2 terminal casing for main circuit Removal While holding the center part of the terminal casing for main circuit pull it up lightly until the mounting jaw releases Installation Insert the mounting jaw of terminal casing for main circuit into the slot on the casing then lightly press it down For 7 5kW or below For 11kW 15kW Note The ...

Страница 14: ...00V 0 2kW 0 4kW Ground terminal Motor IM Braking resistor Symbol for grounding Power supply Circuit breaker for wiring MCCB P DB N DB L1 L2 U V W 1 Phase 200V 0 75kW to 2 2kW Power supply Circuit breaker for wiring Ground terminal Motor Symbol for grounding Braking resistor MCCB IM 3 Phase 400V 0 75kW to 15kW Power supply Circuit breaker for wiring Ground terminal Motor Symbol for grounding Brakin...

Страница 15: ...For 1 phase 200V type connect to terminal L1 and L2 U V W Inverter output Connects to 3 phase motor P DB DB Braking resistor connection Connects to braking resistor N Internal DC voltage negative Negative terminal of internal DC voltage 2 个 Ground Ground terminal For 1 phase 200V type Grounding resistance of 100Ω or less 3 phase 400V ground resistance 10Ω or less Ground the neutral of power supply...

Страница 16: ...wired prior to control circuit Otherwise re tightening operation is not possible after control circuit wiring is completed When connecting directly to a transformer of large capacity 500kVA or more always install an AC reactor on the input side of the inverter Note 1 Maximum number of terminal blocks for main circuit 2 Note 2 It is recommended to use teflon insulated wire 600V Class 2 continuous ma...

Страница 17: ...W 20A M4 1 2 N m 1 5kW 30A 2 2kW 40A 3 5mm2 AWG12 3 5mm2 AWG12 80Ω 120W 3 phase 400V Inverter capacity Rated current of circuit breaker MCCB for wiring Wire size Screw size Tightening torque Braking resistor 1 L1 L2 U V W Ground wire Allowable braking duty factor Resistance Allowable continuous power 0 75kW 10A 2mm2 AWG14 2mm2 AWG14 M4 1 2 N m 5 470Ω 80W 1 5kW 15A 5 470Ω 80W 2 2kW 20A 5 320Ω 120W ...

Страница 18: ...roperly but the higher power can make the resistor generate a lot of heat 300 Please consult with resistor manufacture and provide protection during installation 3 Allowable braking duty factor The higher the allowable continuous power for braking resistor is the higher duty factor can be used theoretically But the internal resistor of inverter will overheat therefore please use duty factor of 5 s...

Страница 19: ... non voltage contact resistive load A B C NO NC COM Relay output 1 2 3 4 5 6 7 8 9 10 E C2 C1 0V 10V D D E 11 12 13 14 15 16 17 18 SW1 SW2 SW3 VR 0V 5V 0V 10V 4mA 20mA 0mA 20mA SW4 SW5 SW6 0V 5V 0V 10V 4mA 20mA 0mA 20mA COM COM Analog output RS485 communication port Open collector output TR1 TR2 resistive load Open collector specification 50V DC 50mA ...

Страница 20: ...C2 Collector AT COM terminal for open collector output E Emitter AK Connection terminal for frequency setting potentiometer 5 V AL Input terminal for analog signal of frequency setting AM Input terminal for 2nd analog signal AN COM terminal for analog signals AK AL AM AO AO Output terminal for multi function analog signal 0 to 10 V AP Positive terminal for RS485 communication transmission line D A...

Страница 21: ...e and tightening torque for control circuit terminal Terminal symbol Screw size Tightening orque N m Wire size Stripped length of cable sheath A B C 1 to M3 0 3 to 0 4 0 25mm2 to 0 75mm2 AWG24 to AWG18 6mm Screwdriver Small size screwdriver Stripped length of wir e sheath Thickness of the edge 0 4mm Width of the edge 2 5mm Terminal block for main curcuit Terminal block for control circuit Relay ou...

Страница 22: ... malfunction Note that the 0V COM terminal is internally connected with the terminal A and the internal circuit 0V Moreover never ground it Each terminal has a max SINK current of 8mA SINK Input decision circuit SOURCE Input decision circuit 4 7kΩ Terminal SOURCE current Max 8mA 0V Terminal 6 W S 1 W S Terminal 0V COM 0V 5V SINK Input decision circuit SOURCE Input decision circuit 4 7kΩ 0V 5V SW1 ...

Страница 23: ...inals used when connection is made between PC and PLC via RS485 communication lines D D D D D D E Terminal station Jumping out Use the shielded twisted pair cable as communication cable and separate it from power lines or high voltage circuits 20cm or more The total wiring length of the communication cables must not exceed 500m Jump out the terminal D and E of inverter used as terminal station Jum...

Страница 24: ...works Changing parameters from the main unit of MK300 only monitoring function works If AMK300 REM1 is disconnected for more than 1 second the main unit of MK300 will automatically enable operation from the main unit of MK300 by default CAUTION When AMK300 REM1 is connected parameters for the main unit of MK300 cannot be set but can only be monitored After the main unit of MK300 and AMK300 REM1 ar...

Страница 25: ...y and frequency command monitoring Rotation Direction Setting Mode For rotation direction setting of panel operation and control status operation panel external control communication monitoring RUN command status Rotation direction Control Status Monitoring Mode For monitoring of control status and abnormality P0 to P3 Parameter Setting Mode For changing and monitoring parameter data as well as us...

Страница 26: ...knob down Return to the previous operation during parameter setting MODE ESC Display is changable Operation status display Frequency setting mode Parameter selection Parameter selection Parameter No selection Parameter No selection Parameter No selection Parameter No selection Parameter No selection Parameter selection Parameter selection Parameter selection Parameter selection Rotation direction ...

Страница 27: ...Check output for open phase and eliminate sharp fluctuations at load side Extend acceleration deceleration time parameters P001 P002 and P317 to P322 Adjust torque boost level parameter P011 Check for restart operation during normal operation Stop ON OFF operation of magnetic contactor at load side OC2 Overcurrent at constant speed OC3 Overcurrent during deceleration OU1 Internal DC overvoltage dur...

Страница 28: ...rminal Set parameters P101 to P106 to 2 or r2 Turn function setting button ON once and OFF again to reset and then restart the inverter Reset by communication command Write 0x9696 into register No 505 DT505 to reset the inverter The error codes of SC6 and CPU cannot be reset through Reset by stop signal Reset by operation panel Reset by multi function terminal and Reset by communication command th...

Страница 29: ...upply cable and the motor cable with a megger always disconnect the wires connected to the inverter first before measuring Do not make such measurement on the control circuit The inverter is mainly consisted of semiconductor elements To prevent the negative effects arising from the temperature humidity dust and vibration etc in working environment and the malfunctions caused by components aging an...

Страница 30: ...erature Generally speaking rising of 10 in temperature reduces the service life of an aluminum electrolytic capacitor by half which also affects the service life of inverter When the inverter is used under high temperature the aluminum electrolytic capacitor may suffer from wear out faults prior to other components in normal status and must be replaced to extend the service life of inverter Compon...

Страница 31: ...k if there is any sign of component overheating 3 Cleaning 1 Strengthen the fasteners 2 Check visually 1 2 In normal state Connected conductors and wires 1 Check if conductors are crooked 2 Check if the wire insulation is broken 1 2 Check visually 1 2 In normal state Transformer Check if there is burning smell Just smell In normal state Terminal block Check if there is sign of damage Check visuall...

Страница 32: ...er voltmeter Whole unit 1 Check if there is burning smell and discoloration 2 Check if there is heavy rustling 1 2 Smell and check visually 1 2 In normal state Capacitor Check for liquid leakage and deformation Check visually In normal state Cooling system Cooling fan 1 Check for abnormal vibration and noise 2 Check if connected parts are loose 1 Just listen 2 Strengthen the fasteners 1 2 In norma...

Страница 33: ...0 3 Power supply capacity kVA 4 3 1 4 8 7 2 11 4 12 4 17 6 23 8 32 1 Light load specificaion Applicable motor output kW 1 1 5 2 2 3 7 5 5 7 5 11 0 15 0 18 5 Rated output current A 2 3 6 5 4 6 9 11 1 17 0 17 0 31 0 38 0 Rated output capacity kVA 3 2 9 4 3 5 5 8 8 13 5 13 5 24 7 30 3 Rated input current A 4 5 4 8 1 10 4 16 7 22 1 22 1 40 3 49 4 Power supply capacity kVA 4 4 3 6 5 8 2 13 3 17 6 17 6 3...

Страница 34: ... 5 1 4 2 4 2 3 3 3 3 AMK3003P74 11 1 9 5 11 1 9 5 11 1 9 5 9 5 9 5 8 1 8 1 6 7 6 7 5 2 5 2 AMK3005P54 17 0 12 0 12 0 12 0 10 8 10 8 9 6 9 6 8 4 8 4 7 2 7 2 6 0 6 0 AMK3007P54 17 0 17 0 17 0 17 0 15 3 15 3 13 6 13 6 11 9 11 9 10 2 10 2 8 5 8 5 AMK3000114 31 0 23 0 31 0 23 0 23 0 23 0 20 7 20 7 18 4 18 4 16 1 16 1 13 8 13 8 AMK3000154 38 0 31 0 38 0 31 0 31 0 31 0 27 9 27 9 24 8 24 8 21 7 21 7 18 6 ...

Страница 35: ...Operation continues when voltage is above 165V AC Operation continues for 15ms when voltage drops below 165V AC Standard specifications 3 phase 400V input type Item Specitications Standard output of applicable motor kW 0 75kW to 15kW Rated output Rated voltage 3 phase 380V to 460V AC proportional to power supply voltage Overload current rating Heavy load specification 150 of rated output current 1 m...

Страница 36: ...Operation Start Stop Operation panel buttons 1a contact signal and 3 wire input 1a and 1b contact signals can be selected RS485 communication Wait time 0 1s to 100s can be set Forward Reverse run Operation panel buttons 1a contact signal reverse run can be disabled RS485 communication Jogging operation Operating frequency adjustable from 0 2Hz to 400Hz Acceleration deceleration time adjustable fro...

Страница 37: ... characteristics base frequency 3 piont type V F mode electronic thermal analog frequency setting Multi step speed frequency setting Multi step speed operation up to 16 step speed setting No limitation to frequency setting Timer operation up to 8 step speed settings No limitation to frequency setting It can be linked with acceleration deceleration time Skip frequency setting Up to 3 settings skip ...

Страница 38: ...ion direction Ouput voltage internal DC voltage set frequency communication station No operation times of timer alarm type control circuit terminal status I O signal operation status PID setting value mesured value and output value progress of automatic tuning accumulative operating time accumulative operating time of fan Details of abnormality Specific symbol is indicated when the protection funct...

Страница 39: ...ID Target Value PV Displays the target value during PID control PV n013 PID Output Value MV Displays the output value during PID control MV n014 Accumulative Operation Time Displays the accumulative operation time of inverter n015 Accumulative Operation Time of Fan Displays the accumulative operation time of inverter fan n016 Abnormality Display Latest Displays abnormalities n017 Abnormality Displ...

Страница 40: ... SW2 OFF Reverse SW2 ON 3 Yes External control Operation SW1 ON Stop SW1 OFF Forward SW2 OFF Reverse SW2 ON 4 NO External control Forward run SW1 ON Stop SW1 OFF Reverse ru SW2 ON Stop SW2 OFF 5 Yes External control Forward run SW1 ON Stop SW1 OFF Reverse run SW2 ON Stop SW2 OFF 6 NO Communication Communication command 7 Yes Communication Communication command P004 Frequency Setting Signal 0 Panel...

Страница 41: ...leration deceleration Quadratic curve 2 S shaped acceleration deceleration Cubic curve 0 P009 V FMode 50 50Hz mode 60 60Hz mode FF Free mode 3C 3 point type 3C1 3 point fixing 1 3C2 3 point fixing 2 3C3 3 point fixing 3 3C4 3 point fixing 4 3C5 3 point fixing 5 3C6 3 point fixing 6 50 P010 V FCurve 0 Constant torque mode 1 Reduced torque mode 0 P011 Torque Boost 7 0 to 40 Manual torque boost Auto Automa...

Страница 42: ...ntion function OFF 1 Overcurrent stall prevention function ON Overcurrent trip prevention function ON 2 Overcurrent stall prevention function OFF Overcurrent trip prevention function ON 3 Overcurrent stall prevention function ON Overcurrent trip prevention function OFF 1 P026 Overvoltage Stall Prevention Function 0 Stall prevention function OFF 1 Stall prevention function ON Regenerative braking r...

Страница 43: ...op Frequency during Forward Reverse Run 0 2 to 60 0 0 1 Hz 0 2 P041 DC Braking Time durig Forward Reverse Run 0 0 to 120 0 0 1 sec 0 0 P042 DC Braking Level during Forward Reverse Run 0 to 100 1 0 P043 DC Braking Time during Startup 0 0 to 120 0 0 1 sec 0 0 P044 DC Braking Level during Startup 0 to 100 1 0 P045 Lower Frequency Limit 0 2 to 400 0 0 1 Hz 0 2 P046 Upper Frequency Limit 0 2 to 400 0 0...

Страница 44: ...4 Linear Speed Multiplier 0 1 to 100 0 1 Multiplier 3 0 P055 Setting Data Clear 0 Normal condition 1 Restore all tha data motor constant excluded to factory settings 2 Restore all the data to factory settings 0 P056 Alarm LED Operation Selection 0 No setting 1 Full monitor alarm 2 Output voltage 3 Overload 4 Abnormal temperature 5 Timer operation stop 6 Abnormal cooling fan 0 P057 Upper Voltage Li...

Страница 45: ...nd is OFF FAn2 Trip Yes 1 ON when Run command is ON and internal temperature is 40 or above OFF when Run command is OFF and internal temperature is 30 or below or power is turned off FAn2 Trip Yes 2 ON when Run command is ON OFF when Run command is OFF FAn2 Trip No Alarm goes off 3 ON when Run command is ON and internal temperature is 40 or above OFF when Run command is OFF or internal temperature...

Страница 46: ...r15 Winding length clear 16 r16 Run stop 17 r17 Forward reverse run 18 r18 Forward run by jogging 19 r19 Reverse run by jogging 20 r20 Invalid 16 P102 SW2 Function Selection 2 0 No setting 1 r1 Multi step speed 2 r2 Reset 3 r3 Reset lock 4 r4 Jogging selection 5 r5 Stop by external fault 6 r6 Parameter setting disabled 7 r7 Coast to stop 8 r8 Switching of frequency signal 9 r9 2nd characteristics ...

Страница 47: ...verse run 18 r18 Forward run by jogging 19 r19 Reverse run by jogging 20 r20 Frequency increment setting 0 P104 SW4 Function Selection 2 0 No setting 1 r1 Multi step speed 2 r2 Reset 3 r3 Reset lock 4 r4 Jogging selection 5 r5 Stop by external fault 6 r6 Parameter setting disabled 7 r7 Coast to stop 8 r8 Switching of frequency signal 9 r9 2nd characteristics selection 10 r10 Switching of PID contr...

Страница 48: ...8 Forward run by jogging 19 r19 Reverse run by jogging 20 r20 Frequency memory setting 0 P106 SW6 Function Selection 2 0 No setting 1 r1 Multi step speed 2 r2 Reset 3 r3 Reset lock 4 r4 Jogging selection 5 r5 Stop by external fault 6 r6 Parameter setting disabled 7 r7 Coast to stop 8 r8 Switching of frequency signal 9 r9 2nd characteristics selection 10 r10 Switching of PID control 11 r11 3 wire s...

Страница 49: ... 0 0 1 0 0 P116 2nd Gain Frequency Setting 0 0 to 500 0 0 1 100 0 P117 2nd Analog Direction Mode 0 No setting 1 Analog input can be reversed Forward Reverse 2 Analog input can be reversed Reverse Forward 0 P118 2nd Analog Input Function Selection 0 2nd frequency setting signal 1 Measured value of PID control PV 2 Base frequency PID adjusted value 3 Base frequency Auxiliary frequency setting signal...

Страница 50: ...tion 13 PWM output 14 Pulse train output 0 P125 Output TR2 Function Selection 0 Run signal 1 Reverse run signal 2 Arrival signal 3 Overload alarm 4 Frequency detection 5 Current detection 1 6 Current detection 2 7 Fault alarm 1 8 Fault alarm 2 9 Timer operation stop after one cycle 10 Timer operation stop 11 Alarm 12 Speed search operation 0 P126 Output RY Function Selection 3 0 r0 Run signal 1 r1...

Страница 51: ...t 1 P135 RS485 Parity Check 6 0 Without parity check 1 Odd parity 2 Even parity 0 P136 RS485 Timeout Detection 6 0 0 0 1 to 60 0 0 1 sec 0 0 P137 Waiting Time for RS485 Transmission 6 1 to 1000 1 msec 1 P138 Judging Time for RS485 TEXT Completion 6 3 to 200 1 msec 3 P139 2nd Base Frequency 45 0 to 400 0 0 1 Hz 50 0 P140 2nd Torque Boost 7 0 to 40 Manual torque boost Auto Automatic torque boost 1 4...

Страница 52: ... Duty Ratio 25 to 75 1 50 P149 Analog Output Voltage Compensation 25 to 100 1 100 P150 TR1 output ON delay time 0 00 0 01 to 99 99 0 01 sec 0 00 P151 TR1 output OFF delay time 0 00 0 01 to 99 99 0 01 sec 0 00 P152 TR2 output ON delay time 0 00 0 01 to 99 99 0 01 sec 0 00 P153 TR2 output OFF delay time 0 00 0 01 to 99 99 0 01 sec 0 00 P154 RY output ON delay time 0 00 0 01 to 99 99 0 01 sec 0 00 P1...

Страница 53: ...01 Ω 4 P210 Exciting Inductance 0 0 to 999 9 1000 to 5000 in increments of 1 mH 0 1 mH 4 P211 Leakage Inductance 0 0 to 999 9 0 1 mH 4 P212 Exciting Current 0 01 to 99 99 0 01 A 4 P213 Speed Control Proportion Amplitude 0 01 to 10 00 0 01 4 P214 Speed Control Integral Amplitude 0 01 to 10 00 0 01 4 P215 Torque Limit Level 50 to 400 1 4 P216 2nd Motor Capacity 0 2 0 2kW 0 4 0 4kW 0 7 0 75kW 1 5 1 5...

Страница 54: ... 2nd 3rd 4th acceleration deceleration function 2 Acceleration deceleration linked with multi step speed frequency operation 3 Multi step speed frequency operation by timer 4 Aceleration deceleration linked with multi step speed frequency operation by timer 0 P302 2nd Step Speed Frequency 0 0 0 2 to 400 0 0 1 Hz 5 0 P303 3rd Step Speed Frequency 0 0 0 2 to 400 0 0 1 Hz 10 0 P304 4th Step Speed Fre...

Страница 55: ...th Acceleration Time 0 04 to 3600 0 01 sec 9 4 P322 4th Deceleration Time 0 04 to 3600 0 01 sec 9 4 P323 Rotation Direction of Timer Operation 0 to 255 0 P324 Continuous Operation Times of Timer 0 1 to 9999 1 times 1 P325 Continuous Operation Mode of Timer 0 Return to zero dead stop status and then start next cycle 1 Change to 1st multi step speed frequency for the next cycle 0 P326 Continuous Sta...

Страница 56: ...oint random swing mode 0 P341 Maximum Random Rise Time Coefficient 0 0 to 100 0 0 1 50 0 P342 Mimimum Random Rise Time Coefficient 0 0 to 100 0 0 1 50 0 P343 Winding Length Multiplier 0 to 9999 1 P344 Winding Stop Length 0 1 to 9999 1 000 to 60 00 1 m 0 P345 PID Target Value 0 0 to 100 0 0 1 0 0 P346 PID Upper Limit 0 0 to 100 0 0 1 100 0 P347 PID Lower Limit 0 0 to 100 0 0 1 0 0 P348 PID Bias Value...

Страница 57: ... also valid 2 When the set value displayed with r it indicates the contact b output If r is not displayed it indicates contact a output 3 When the set value displayed with r ON indicates non exciting operation If r is not displayed ON indicates exciting operation 4 Initial value varies with inverter capacity 5 Initial value varies with applicable input voltage of inverter It is 200 for 200 V volta...

Страница 58: ...dous substances contained in all homogeneous materials for this component is below the standard specified in GB T 26572 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Information Products Indicates that the content of toxic or hazardous substances contained in at least one homogeneous material for this component is above the standard specified in GB T 26572 Requ...

Страница 59: ...58 ...

Страница 60: ...tomer Service Hotline 400 920 9200 Panasonic Industrial Devices Sales China Co Ltd Address No 97 Huoju Road New District Suzhou Jiangsu Province China Postal Code 215009 Tel 0512 6843 2580 URL panasonic net id pidsx global Panasonic Industrial Devices SUNX Suzhou Co Ltd 2017 Issued in November 2017 PRINTED IN CHINA ME MK300SG Panasonic Industrial Devices SUNX Suzhou Co Ltd ...

Отзывы: