6295-6298 ENCLOSED HEAT DETECTOR
- FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
5
3. GENERAL DESCRIPTION
The heat detectors are conventional fixed temperature heat detectors. The detectors will give an alarm at a certain fixed tempera
-
ture (57 °C / 72 °C / 87 °C / 117 °C).
The detector is intended for outdoor use or indoor use in high humidity premises.
2
1
75
100
95
(Measure in mm)
1. Detector
2. Connection box
3.1.
DETECTOR
The sensing element is a heat pick-up shield and a bimetal switch.
The detectors will give an alarm within a response temperature range in accordance with EN54-5, see table below.
Type
Static response temperature
Category
6295
57 °C
A2 S
6296
72 °C
B S
6297
87 °C
C S
9298
117 °C
E S
3.1.1.
LATCHING
The detector is latching. The detector will not be automatically reset if the temperature, after the alarm, falls below the detector's
static response temperature. The detector's LED and a connected external LED will be lit until the detector is reset via the CIE.