background image

 

All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 

Product Leaflet 

Date of issue 

Revision / Date of revision  

MEW00132 2001-10-19 9 

2008-10-10 

 

Type numbers 

6295 

Enclosed heat detector, 57

°

C, class A2 S (54 to 70

°

C). 

6296 

Enclosed heat detector, 72

°

C, class B S (69 to 85

°

C). 

6297 

Enclosed heat detector, 87

°

C, class C S (84 to 100

°

C). 

6298 

Enclosed heat detector, 117

°

C, class E S (114 to 130

°

C). 

3390 

Label holder (100 holders per packet, excl. labels). 

3391 

Labels for 3390  (10 sheets à 132 labels) 

     

 

Detector mounting holes, 2x(4x7 mm) c/c = 70 mm.  

E+/E-

 = Ext. LED.  

A/B

 = zone line in/out 

(or end-of-line device).  Connectors for wire diameter 0.6 - 1.2 mm (approx. 0.3 - 1.13 mm

2

). 

Connection box mounting holes, 2x(5 mm) c/c = 108 mm.  The connection box is prepared for 
required number of compression glands, one, two or three.  A gland is approx. 30 mm high.   

Technical data 

Voltage (V DC) 

 

  rated 
  allowed 
  normal 

 
24 
12-30 
24  (zone line voltage) 

Current consumption at nom. 
voltage, quiescent (mA) 

 

Current limitation required, when 
active (mA) 

(EBL equipment has current limitation.)

 

6295-6297:  Must be min. 6 and max. 40 
6298:  Must be min. 6 and max. 30 
 

Ext. LED output 
  voltage (V) 
  current output (mA) 

 
Zone line voltage minus 2 V 
Max. 10  (no internal current limiter) 

Alarm resistance (

For 6295-6297:  approx. 400.    For 6298:  approx. 680 

Internal capacitance (nF)   
Internal inductance 

For 6295-6296:  max. 50 
For 6295-6296:  0 

Ambient temperature (

°

C) 

  operating 
    (Min. / 

Typical

 / Max.) 

  storage 

 

 

6295 (A2 S): 

6296 (B S): 

6297 (C S): 

6298 (E S): 

-40 /

+25

 /+50 

-40 /

+40

 /+65 

-40 /

+55

 /+80 

-40 /

+85

 /+110 

-45 to +70 

-45 to +70 

-45 to +70 

-45 to +70 

Ingress Protection rating  

IP67 (attached conn. box, silicon gasket and compression glands required) 

Static response temperature 

57, 72, 87, or 117

°

C depending on detector / class.  See text. 

Size 

 x h (mm) 

Detector:  95 x 42          Connection box:  100 x 35 
De Connection box:  100 x 75  (excl. compression glands) 

Weight (g) 

Detector:  82                Connection box (incl. 3 glands):  134 

Construction  
 
 
Colour 

Body (6295, 6296):  ABS 
Body (6297, 6298):  Modified Polycarbonate. 
Protector (on the body) & Connection box: Modified Polycarbonate.  
Grey  (N8, Munsell colour code) 

Approvals 

 05  EC Certificate no. 0845-CPD-232.1192   (6295);   EN54-5 
 05  EC Certificate no. 0845-CPD-232.1193   (6296);   EN54-5 
 05  EC Certificate no. 0845-CPD-232.1194   (6297);   EN54-5

 

 05  EC Certificate no. 0845-CPD-232.1195   (6298);   EN54-5 

ATEX classification (for 6295 & 
6296 only) 

6295:  

 II 3GD EEx nA II T5 (T100

°

C

), 

 -40

°

 T

a

 

 50

°

6296:  

 II 3GD EEx nA II T5 (T100

°

C

), 

 -40

°

 T

a

 

 65

°

 

Отзывы: