MEW00852 2007-01-11 

2008-09-18 

 

Type number 

4318 Combination 

heat 

detector 

 

 

     

Zone line

Ext. LED

End-of-line

device

C.i.e

. EBL5

12 / EBL128 

EBL50

0

Zon

e

 li

n

e

 input

+

-

+

Mark

Mark

A+

B- L

B-

A+

A+

B- L

B-

A+

 

In the detector: 

See also "Engineering Instructions for detectors Type 435x".

 

A

 

Contact for base 2324 

B

 

Contact for base 2324 

The detector is plugged in a base 2324.  End-of-line device depending on the zone line input. 

 

Technical data 

Voltage (V DC) 

  rated 
  allowed 
  normal 

 

24 
10-30 
24 

Current consumption at nom. volt. 
(mA) 

  quiescent  (detector only) 
  active  (detector only) 

Depending on the type of base it is plugged into.  For more details see 
the Product Leaflet respectively, e.g. MEW00008 (Base 2324). 

0.015 
min. 3 

Ambient temperature (

°

C) 

  operating 
  storage 

 

-10 to +50 
-25 to +70 

Application temperature class A1 (

°

C) 

  typical  /  max. 

 

+25  /  +50 

Ambient humidity (% RH) 

max. 95, non condensing 

Ingress Protection rating (estimated) 

IP51 

Alarm temp. (T=

°

C;  

deltaT=

°

C/168s

59;  

18

      (T=static response temp.  Class A1  T

min.

=54;  T

max.

=65.) 

Size 

 x h (mm) 

102 x 39 

Weight (g) 

54 

Construction / Colour 

Modified polycarbonate / Grey (N8, Muncell colour code) 

Approvals 

 07  EC Certificate no. 0845-CPD-232.1566;  EN54-5, class A1R. 

 