All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
Date of issue
Revision / Date of revision
MEW00852 2007-01-11
3
/
2008-09-18
Type number
4318 Combination
heat
detector
Zone line
Ext. LED
End-of-line
device
C.i.e
. EBL5
12 / EBL128
/
EBL50
0
Zon
e
li
n
e
input
+
-
+
Mark
Mark
A+
B- L
B-
A+
A+
B- L
B-
A+
In the detector:
See also "Engineering Instructions for detectors Type 435x".
A
Contact for base 2324
B
Contact for base 2324
The detector is plugged in a base 2324. End-of-line device depending on the zone line input.
Technical data
Voltage (V DC)
rated
allowed
normal
24
10-30
24
Current consumption at nom. volt.
(mA)
quiescent (detector only)
active (detector only)
Depending on the type of base it is plugged into. For more details see
the Product Leaflet respectively, e.g. MEW00008 (Base 2324).
0.015
min. 3
Ambient temperature (
°
C)
operating
storage
-10 to +50
-25 to +70
Application temperature class A1 (
°
C)
typical / max.
+25 / +50
Ambient humidity (% RH)
max. 95, non condensing
Ingress Protection rating (estimated)
IP51
Alarm temp. (T=
°
C;
deltaT=
°
C/168s
)
59;
18
(T=static response temp. Class A1 T
min.
=54; T
max.
=65.)
Size
∅
x h (mm)
102 x 39
Weight (g)
54
Construction / Colour
Modified polycarbonate / Grey (N8, Muncell colour code)
Approvals
07 EC Certificate no. 0845-CPD-232.1566; EN54-5, class A1R.
A
B
The zone line is connected to the base 2324 (A+ & B-)
Ext. LED is connected to the base 2324 (A+ & L).