Chapter 4. Optional Display/User Interface
22
DewPro<Superscript>® MMR31 Installation & Operation Manual
4.3
Matrix Buttons - Special Functions
4.3.1
Reset to “Normal” Display
Pressing the
V
and
H
buttons simultaneously returns the user to
VH 00
(normal display).
4.3.2
Display Only
Eight (8) matrix locations are for display only and may not be changed by the user (see
“display only”
fields are as follows:
Table 4:
Location
Display Description
VH 00
Normal display (in dewpoint, % RH, mixing ratio or absolute humidity as selected in VH
01)
VH 08
Indicates digitized moisture signal
VH 40
Displays temperature
VH 48
Indicates digitized temperature signal
VH 90
During a system alarm, displays the error code for the fault encountered
VH 91
During normal operation, displays the previous error code for reference
VH 92
Displays the factory issued identification number
VH 93
Displays the factory-issued reference number designating the device type and
software version
4.3.3
Default Values
A default value is assigned to each programmable matrix field. These values are loaded after a reset to factory
programmed data has been executed (see
VH 95
).