Installing the water heater :

This water heater must be installed in accordance with these instructions, local codes, utility company
requirements, and/or in the absence of local codes, use the latest edition of the American National
Standard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association,
400 North Capitol Street Northwest, Washington, DC  20001 as ANSI standard Z223.1 or National Fire
Protection Association, 1 Batterymarch Park, Quincy, MA 02269 as NFPA 54.  In Canada, the latest
edition of the CSA B149.1 Natural Gas and Propane Installation, and the Canadian Electrical Code,
CSA C22.1 Part 1, in the absence of local codes.

Location of Water Heater

The water heater should not be located
in an area where leakage of the heat
exchanger or connections will result in
damage to the area adjacent to it or to
lower floors of the structure. 

When such areas cannot be avoided it is
recommended that a suitable catch pan,
adequately drained, must be installed
under the water heater.

The pan must not restrict combustion air
flow.

A gas fired water heater or any other
appliance should not be installed 
in a space where liquids which give off
flammable vapors are to be used or stored.
Such liquids include gasoline, LP gas
(butane or propane), paint or adhesives and
their thinners, solvents or removers.

Because of natural air movement in a room
or other enclosed space, flammable vapors
can be carried some distance from where
their liquids are being used or stored. The
open flame of the water heater’s main
burner can ignite these vapors causing an
explosion or fire which may result in severe
burns, death or property damage.

The water heater must be located so it is not
subject to physical damage, for example, by
moving vehicles, area flooding, etc. 

If the water heater is installed in a garage, it
should be installed so that the direct
ignition system and main burner are no less
than 18 inches (45 cm) above the garage
floor.

Raising the gas fired water heater will
reduce BUT NOT eliminate the possibility
of lighting the vapor of any flammable
liquids which may be improperly stored or
accidentally spilled.

l

The water heater should be installed as
close as practical to the vent termination
to minimize vent length and the number
of elbows required for venting.

The water heater should be installed with
the proper venting materials and
termination suitable for Category III
venting.

A fire stop plate should be installed at
every penetration of a floor or ceiling if

the vent is not running in a fire-rated
shaft.

Failure to install and properly vent the
water heater to the outdoors as outlined
in the Venting Section of this manual can
result in unsafe operation.

l

Long hot water lines should be insulated to
conserve water and energy.

l

The water heater and water lines should
be protected from exposure to freezing
temperatures.

l

Do not 

install the water heater in

bathrooms, bedrooms, any occupied
rooms normally kept closed, or in
outdoor areas.

l

Do not

install the water heater in small,

poorly ventilated rooms, or in air tight
rooms with air-conditioning.

l

Do not

install water heater where subject

to vibrations.

l

Do not

install the water heater in

Recreational Vehicles, Mobile Homes,
Boats and other Watercrafts.

l

Do not

install the water heater near vents

for heating or cooling.  A minimum of 4
feet (1.2 m) should be maintained.

l

Minimum clearance from combustible
and non-combustible construction is 0”
around the air intakes pipe, 1/2” (1.3 cm)
sides, 0” rear (with support bracket); 12”
(30 cm) from the bottom; 12” (30 cm)
from the front of the water heater; and
12” (30 cm) from the top, (24” (61 cm)
from front and top is recommended for
servicing purposes).  Refer to Figure on
page 8.

l

Maintain a minimum clearance of
1” (2.5 cm) between the vent outlet pipe
and air intake pipe. Also, maintain a 3”
(8 cm) clearance between the vent pipe
and combustible or non-combustible
construction, unless otherwise specified
by vent manufacturer or installed in an
enclosed space. If the clearances stated
on the Instruction/Warning Label,
located on the front panel of the heater
differ, install the water heater according
to the clearances stated on the label.
Refer to Figure on page 8.

7

WARNING: Combustible

construction refers to
adjacent walls and ceilings
and should not be confused
with combustible or
flammable products and
materials. Combustible
and/or flammable products
and materials should never
be stored in the vicinity of
this or any gas appliance.

!

Содержание Tankless Water Heater

Страница 1: ...er heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also includes a parts list It is very impor...

Страница 2: ...ers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date is needed to obtain service under the warranty You can also registe...

Страница 3: ...ER INSTALLAND PROPERLY VENT THE WATER HEATER Gasoline as well as other flammable materials and liquids adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT...

Страница 4: ...switch adjustment Only qualified service personnel should perform this adjustment Only factory authorized remote control s should be used Notice When this water heater is supplying general purpose hot...

Страница 5: ...P gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level l Before attempting to light the water heater make sure to loo...

Страница 6: ...ormation in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage personal injury or loss of life FOR INSTALLATIONS IN THE STATE OF CALIFO...

Страница 7: ...l The water heater should be installed as close as practical to the vent termination to minimize vent length and the number of elbows required for venting l The water heater should be installed with...

Страница 8: ...y other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Imm...

Страница 9: ...they must be corrected in accordance with the venting instructions in this manual before completing the installation and putting the water heater into service DANGER Failure to install the appliance...

Страница 10: ...hould have a downward slope towards the vent termination The vent should have a 1 4 per foot DOWNWARD slope towards the vent terminal as shown above If the air intake pipe or duct is connected to the...

Страница 11: ...t 91 cm J Clearance to nonmechanical air supply inlet to the combustion air inlet to any building or other appliance 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 00...

Страница 12: ...ate can freeze on the exterior wall under the eaves and on surrounding objects Some discoloration to the exterior of the building is to be expected However improper location or installation can result...

Страница 13: ...ocated in the female end of the 4 7 concentric vent pipe section When fully assembled the outer female end see Figure to left will overlap the male end by approximately 1 inch 25 4 mm Use the self tap...

Страница 14: ...ale end of the air intake connection of the air intake tee Install the appliance adapter onto the appliance outlet and inlet and clamp as required Now attach other required vent and air intake materia...

Страница 15: ...5 m If required use silicone sealant at the point the vent connector joins the water heater Chase Requires 6 15 cm Clearance to Combustibles Firestop Firestop Tall Cone Flashing Vent Adapter 3 8 cm C...

Страница 16: ...carried out by a qualified plumber in accordance with local codes Use approved plumbing materials only The diameter of the pipe lines should be a minimum of 3 4 To conserve energy and to prevent free...

Страница 17: ...e water inlet and the hot water outlet as shown on the water heater If reversed the water heater will not function Installation of unions or flexible copper connections are recommended on the HOT and...

Страница 18: ...be installed in the discharge line Notice Local codes govern the installation of relief valves If local codes require that a temperature and pressure relief valve should be installed the manufacturer...

Страница 19: ...e gas supply line which does not exceed the maximum supply pressure DO NOT use an industrial type gas regulator High Altitude Gas Supply The supplied Manual Gas Appliance Shutoff Valve must be install...

Страница 20: ...with this water heater DO NOT attempt to disassemble the remote control WARNING Field wiring connections and electrical grounding must comply with local codes or in the absence of local codes with th...

Страница 21: ...able from the water heater l l Place the remote control over the base plate Ensure the projections in the base plate fit into the housings in the remote control l l Fix the control to the base plate a...

Страница 22: ...lt interrupter l An ON OFF switch must be provided and installed for the incoming 120VAC power l Wire the water heater exactly as shown below A wiring Figure is also found inside of the cover panel l...

Страница 23: ...valve See NFGC B149 for complete instructions Local codes or plumbing authority requirements may vary from the instructions or figures provided and take precedent over these instructions Vacuum Relief...

Страница 24: ...s Inlet Check Valve Inlet Pipe Cold Water Hot Water Insulate all the way to the top Insulation Blankets Insulation blankets available to the general public for external use on gas water heaters are no...

Страница 25: ...ion and sediment trap q Approved pipe joint compound used q Soap and water solution used to check all connections and fittings for possible gas leak q Gas Company inspected installation if required D...

Страница 26: ...s label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait...

Страница 27: ...g valves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information...

Страница 28: ...that hotter water increases the risk of scald injury Always supervise young children or others who are incapacitated The water heater is equipped with a device that will shut off the gas supply to th...

Страница 29: ...pection maintenance and or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and disconnect the...

Страница 30: ...cleaning a vacuum cleaner can be used on the burner Proper burner pattern Care and cleaning of the water heater Vacation and Extended Shut Down If the water heater is to remain idle for an extended p...

Страница 31: ...breaker at least 10 seconds after step 1 Open all hot water faucets Before proceeding to the next step make sure that COLD water is coming out of all hot water faucets Close the water shut off valve...

Страница 32: ...pplied and or water supply is adequate Unit is not ON l Turn the unit ON by the button The temperature may be set too low Mixing Valve Malfunctions if applicable l Check and replace if necessary Error...

Страница 33: ...evices Refer repairs to qualified service personnel CAUTION Make certain power to water heater is OFF before removing protective cover FOR ANY REASON CAUTION Label all wires prior to disconnection whe...

Страница 34: ...nt Water Heater Instructions For Placing a Parts Order Address parts orders to the distributor or store from where the water heater was purchased All parts orders should include The model and serial n...

Страница 35: ...setting to 120 49 C Follow first four bullets points listed above then continue as listed below l Press the Min button on the left hand side of the PCB for more than 1 second The LED on the PCB starts...

Страница 36: ...omplete satisfaction you should then contact the following address 2151 Eastman Avenue Oxnard CA 93030 Phone 805 278 5499 When contacting the manufacturer the following information will be requested a...

Страница 37: ...line without the use of a temperature sensor timer or a continuously operating pump All Applicable Warranty Periods will be limited to one 1 year from the Effective Date if the water heater is instal...

Страница 38: ...ter heater or component part s Paloma will not reimburse any party for these or any other fees not specifically covered in this Limited Warranty document HOW TO OBTAIN WARRANTY CLAIM ASSISTANCE Any cl...

Страница 39: ...Paloma Industries Inc 2151 Eastman Avenue Oxnard CA 93030 PRINTED IN JAPAN 31 51901 00...

Отзывы: